UPS5000-E-(400 kVA-600 kVA)
User Manual (60 kVA Power Modules)
4 User Interface
Issue 05 (2019-12-24)
Copyright © Huawei Technologies Co., Ltd.
106
Item
Description
Power factor
Proportion of the bypass input active power to the bypass
input apparent power.
Table 4-8
Battery status
Item
Description
Battery Status
The value can be
Not connected
,
Equalized charging
,
Float charging
,
Hibernating
,
discharging
, or
Not chg.
or dis
.
Voltage (V)
Voltage of the battery string.
Current (A)
Current of the battery string (the current is
+
when
batteries are being charged and
–
when discharged).
Temperature (°C)
Battery operating temperature (A battery sensor is
required. If the sensor is not installed,
NA
is displayed).
Backup time (min)
Battery backup time estimated at the current load.
Remaining cap. (%)
Remaining battery capacity.
SOH
State of health.
Table 4-9
Total runtime
Item
Description
Bypass runtime (h)
Time for which the UPS runs in bypass mode.
Inv. runtime (h)
Time for which the UPS runs in inverter mode.
The value must be an integer. For example:
If the value is less than 1, the value takes 0.
If the value is greater than or equal to 1 and less than 2, the value takes 1.
Table 4-10
Environment data
Item
Description
Ambient temperature (°C)
Temperature measured by the ambient temperature and
humidity sensor. (An ambient temperature and humidity
sensor is required. If no sensor is connected, the ambient
temperature sampled by the bypass unit is displayed.)
Ambient humid. (%)
Humidity measured by the ambient temperature and
humidity sensor. If the sensor is not installed,
NA
is