RRU3832&RRU3632
Installation Guide
3 Information About the Installation
Issue 05 (2014-06-30)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
29
If an RU is installed on the bitumen ground, the RU must be at least 500 mm (700 mm or
more as recommended) away from the bitumen ground. The following describes the space
requirements for installing multiple RUs on the non-bitumen ground.
The recommended clearances ensure normal running and provide an appropriate space for operation
and maintenance (OM). If there is sufficient space, retain the recommended clearances.
The minimum clearances ensure normal running and heat dissipation but do not allow OM activities
such as checking indicator status and opening the cabling cavity. If the installation space is
insufficient, retain the minimum clearances after the installation.
Recommended Clearances for Three or More RUs Installed on a Pole
shows the recommended clearances for multiple RUs installed in centralized
mode.
Figure 3-28
Recommended clearances for three or more RUs installed on a pole
Minimum Clearances for Three or More RUs Installed on a Pole
shows the minimum clearances for multiple RUs installed in centralized mode.