NO TICE
● When connecting the indoor and outdoor units, seal the pipe if the welding
break exceeds 15 minutes to prevent dust and water from entering the pipe.
● To avoid burning the bottom panel, top panel, side panel, internal components,
other pipes, thermal insulation foam, power cables, and labels, take protective
measures, such as spreading a piece of wet cloth, around the welding position.
● During and after the welding, avoid exposing the refrigerant pipe for over 15
minutes because this may influence the system reliability.
● Take appropriate sealing and protective measures when routing welded pipes
through holes to prevent air channel leaks and copper pipe damage. Otherwise,
other components may be damaged by impurities.
● Avoid elbows and ensure that the connection between the indoor and outdoor
units is the shortest.
● The refrigerant pipes should be wrapped with thermal insulation foam.
Procedure
Step 1 Weld pipes in the medium segment by referring to
.
NO TICE
Exercise caution during welding to avoid burning components, such as rubber
rings, inside the cabinet.
During the welding, charge a little nitrogen into the pipes to avoid internal
oxidation, as shown in
.
Figure 3-20 Welding pipes
●
When the direction of the refrigerant pipe is changed, add a support at the
position that is 500 mm away from the changing point.
●
If the refrigerant pipe is straight, add a support every 1500 mm.
Figure 3-21 Support positions for refrigerant pipes
NetCol8000-A013 In-room Air Cooled Smart Cooling
Product
User Manual (600 mm Width)
3 Installation Guide
Issue 02 (2020-11-09)