Menu
Name
Default
Value
Settings Range
Temp for HT Start All
Hide or
31
24.0°C to 35.0°C
Low Temp Start All
Hide or
Disable
Enable/Disable
Temp for LT Start All
Hide or
13
10.0°C to 18.0°C
Setting > User Menu >
Temp&Humid Setting
Return Air Temp Set
24.0
The minimum
temperature
setting to the
maximum
temperature
setting
Return Air Humid Set
50.0
The minimum
humidity setting
to the maximum
humidity setting
Setting > User Menu >
Comm Setting
Baud Rate
9600
9600/19200
Comm Address
Setting
1 to 255
Enable Monitoring
Resistor
No
Yes/No
Setting > User Menu >
Password Setting
/
000001
Six-digit number
Setting > Admin Menu
> Alarm Setting >
Temp&Humid Sensor
Return Air HT Alarm
Enable
Enable/Disable
Return Air HT Thres
32.0°C
25°C to 40.0°C
Return Air LT Alarm
Enable
Enable/Disable
Return Air LT Thres
12.0°C
5°C to 24.0°C
High Humid Alarm
Enable
Enable/Disable
High Humid Thres
85.0%
RH
65.0% RH to
95.0% RH
Low Humid Alarm
Enable
Enable/Disable
Low Humid Thres
10.0%
RH
5.0% RH to
35.0% RH
Temp&Humid Alarm
Delay
60s
5s to 999s
Setting > Admin Menu
> Alarm Setting >
Compressor
Run Time out Alarm
Enable
Enable/Disable
NetCol8000-A013 In-room Air Cooled Smart Cooling
Product
User Manual (600 mm Width)
E Controller Menu
Issue 02 (2020-11-09)
Copyright © Huawei Technologies Co., Ltd.
168