Alarm
ID
Alarm Name
System
Action
Possible Causes
Solution
105
InFan Run
Timeout Alarm
--
The runtime of the
indoor fan exceeds the
preset threshold.
Replace the indoor fan
and clear the
cumulative runtime.
106
Air Filter Run
Timeout Alarm
--
The runtime of the air
filter exceeds the
preset threshold.
Replace the air filter
and clear the
cumulative runtime.
201
Comp Discharge
HP Alarm
The
compressor
shuts down.
1. The condenser fins
are dirty or blocked.
2. The outdoor fan or
its drive is faulty.
3. The high pressure
sensor cable is not
properly connected.
4. The high pressure
sensor is faulty.
5. The refrigerant is
overfilled.
6. The outdoor unit is
not properly
installed.
1. Clean the condenser
fins.
2. Maintain or replace
the outdoor fan
drive or outdoor
fan.
3. Check the cable
connections to the
high pressure
sensor.
4. Maintain or replace
the high pressure
sensor.
5. Decrease certain
amount of
refrigerant.
6. Reinstall the
outdoor unit.
202
Comp Discharge
HP Lock Alarm
The
compressor
shuts down.
(The alarm
needs to be
manually
cleared.)
The Comp Discharge
HP Alarm is triggered
multiple times within a
specified period of
time.
Refer to the solution to
the Comp Discharge
HP Alarm.
NetCol8000-A013 In-room Air Cooled Smart Cooling
Product
User Manual (600 mm Width)
5 System Operation and Maintenance
Issue 02 (2020-11-09)
Copyright © Huawei Technologies Co., Ltd.
85