Alarm
ID
Alarm Name
System
Action
Possible Causes
Solution
205
Comp HP Switch
Alarm
The
compressor
shuts down.
1. The condenser fins
are dirty or blocked.
2. The outdoor fan or
its drive is faulty.
3. The cables to the
high pressure switch
are loose or
damaged.
4. The high pressure
switch is faulty.
5. The refrigerant is
overfilled.
6. The outdoor unit is
not properly
installed.
1. Clean the condenser
fins.
2. Maintain or replace
the outdoor fan
drive or outdoor
fan.
3. Check the cable
connections to the
high pressure
switch.
4. Maintain or replace
the high pressure
switch.
5. Decrease certain
amount of
refrigerant.
6. Reinstall the
outdoor unit.
206
Comp HP Switch
Lock Alarm
The
compressor
shuts down.
(The alarm
needs to be
manually
cleared.)
The Comp HP Switch
Alarm is triggered
multiple times within a
specified period of
time.
Refer to the solution to
the Comp HP Switch
Alarm.