Alarm
ID
Alarm Name
System
Action
Possible Causes
Solution
702
Suction Press
Sensor Fault
The
compressor
shuts down.
1. The pressure sensor
cable is not properly
connected.
2. The pressure sensor
is faulty.
1. Check the cable
connection to the
pressure sensor.
2. Maintain or replace
the pressure sensor.
703
Suction Temp
Sensor Fault
The
compressor
shuts down.
1. The temperature
sensor cable is not
properly connected.
2. The temperature
sensor is faulty.
1. Check the cable
connection to the
temperature sensor.
2. Maintain or replace
the temperature
sensor.
704
Discharge Temp
Sensor Fault
--
1. The temperature
sensor cable is not
properly connected.
2. The temperature
sensor is faulty.
1. Check the cable
connection to the
temperature sensor.
2. Maintain or replace
the temperature
sensor.
705
Outdoor Temp
Sensor Fault
The
compressor
shuts down.
(705 and 706
are triggered
at the same
time.)
1. The temperature
sensor cable is not
properly connected.
2. The temperature
sensor is faulty.
1. Check the cable
connection to the
temperature sensor.
2. Maintain or replace
the temperature
sensor.
706
Inverter Temp
Sensor Fault
The
compressor
shuts down.
(705 and 706
are triggered
at the same
time.)
1. The temperature
sensor cable is not
properly connected.
2. The temperature
sensor is faulty.
1. Check the cable
connection to the
temperature sensor.
2. Maintain or replace
the temperature
sensor.