2.4 Operating Environment Specifications
Environmental Specifications
Table 2-3 Environmental specifications
Item
Specifications
Indoor unit
operating
temperature
18–32°C, temperature adjustment precision: ±1°C
Indoor unit
operating
humidity
20%–80% RH, humidity adjustment precision: ±5% RH
Storage
temperature
● –40°C to +70°C (indoor unit)
● –40°C to +70°C (outdoor unit without refrigerant)
● –40°C to +45°C (outdoor unit with refrigerant)
Storage
humidity
5%–95% RH (non-condensing)
Outdoor unit
operating
temperature
–20°C to +45°C
Altitude
0–4000 m, When the altitude exceeds 1000 m, the power
should be derated.
Installation Requirements
Table 2-4 Installation requirements
Item
Specifications
Equipm
ent
room
door
Width ≥ 1.2 m; height ≥ 2.3 m
Floor
Bearing capacity ≥ 350 kg/m
2
NetCol8000-A013 In-room Air Cooled Smart Cooling
Product
User Manual (600 mm Width)
2 Product Description
Issue 02 (2020-11-09)
Copyright © Huawei Technologies Co., Ltd.
21