Item
Specifications
Equivale
nt
length
of the
one-
way
pipe
≤ 60 m
Height
differen
ce
betwee
n the
indoor
and
outdoor
units
● If the outdoor unit is placed higher than the indoor unit, the
maximum vertical distance between them is 20 meters.
● If the indoor unit is placed higher than the outdoor unit, the
maximum vertical distance between them is 5 meters.
Water
supply
The inlet water pressure should be 0.1–0.7 MPa, and the temperature
should be in the range of 1°C–40°C.
The wet film humidifier should use tap water that meets the
following requirements:
● Non-freezing, Nephelometric Turbidity Units (NTU) < 3
● No visible substances
● 6.5 ≤ pH value ≤ 8.5
● Total hardness (in CaCO
3
) ≤ 450 mg/L
For details, refer to the
GB 5749-2006 Standards for Drinking Water
Quality
.
Power
require
ments
Earth leakage circuit breakers are not recommended for mains. If
earth leakage circuit breakers are required by the customer or
according to local regulations, use the residual current circuit breaker
(RCCB) that is not sensitive to the single-phase DC pulse and
transient current pulse.
Note: If the requirements are not met, contact Huawei technical support for an
optimized plan.
2.5 Technical Specifications
All models (indoor and outdoor units) of this product meet the environmental
protection requirements. The environmental protection mark is as follows.
NetCol8000-A013 In-room Air Cooled Smart Cooling
Product
User Manual (600 mm Width)
2 Product Description
Issue 02 (2020-11-09)
Copyright © Huawei Technologies Co., Ltd.
22