Maintenance Item
Expected Result
Troubleshooting
Check that the electrical components
and control components of the
outdoor unit are free of dust.
Check that the surfaces of the
control board are not aged.
Replace the abnormal board.
Check that the electric heater
contactor works properly.
Replace the electric heating
contactor if it is faulty.
Cable
Check that no cable is aged.
Replace aged cables.
Outdoor unit
Check that the outdoor unit is
secured to the floor.
Tighten the screws that secure the
rack to the floor.
5.2 Troubleshooting
CA UTION
Do not maintain or replace outdoor units during thunderstorms. Otherwise, your
personal safety will be in danger.
NO TICE
● You are not advised to maintain or replace outdoor units in rainy days. If
unavoidable, take protective measures to prevent water from entering the
outdoor unit.
● When opening the electric control box cover, clear water from the cover.
● Certain circuits in the smart cooling product have lethal voltages. Only
professional technicians are allowed to perform maintenance.
● Exercise caution during troubleshooting with power on.
● If jumpers are used for troubleshooting, always remove them after
troubleshooting. Connected jumpers may affect control functions and damage
equipment.
Table 5-4 Troubleshooting
Cate
gory
Sympto
m
Possible Cause
Measure
Indo
or
unit
The
indoor
unit fails
to start.
The indoor fan is damaged. Replace the indoor fan.
The drive board of the
indoor fan is damaged.
Replace the drive board of the indoor fan.
NetCol8000-A013 In-room Air Cooled Smart Cooling
Product
User Manual (600 mm Width)
5 System Operation and Maintenance
Issue 02 (2020-11-09)
Copyright © Huawei Technologies Co., Ltd.
80