background image

NetCol8000-A013 In-room Air Cooled Smart

Cooling Product

User Manual (600 mm Width)

Issue

02

Date

2020-11-09

HUAWEI TECHNOLOGIES CO., LTD.

Summary of Contents for NetCol8000-A013

Page 1: ...NetCol8000 A013 In room Air Cooled Smart Cooling Product User Manual 600 mm Width Issue 02 Date 2020 11 09 HUAWEI TECHNOLOGIES CO LTD ...

Page 2: ...cribed in this document may not be within the purchase scope or the usage scope Unless otherwise specified in the contract all statements information and recommendations in this document are provided AS IS without warranties guarantees or representations of any kind either express or implied The information in this document is subject to change without notice Every effort has been made in the prep...

Page 3: ...gineers Data configuration engineers Maintenance personnel Symbol Conventions The symbols that may be found in this document are defined as follows Symbol Description Indicates a hazard with a high level of risk which if not avoided will result in death or serious injury Indicates a hazard with a medium level of risk which if not avoided could result in death or serious injury Indicates a hazard w...

Page 4: ...text NOTE is used to address information not related to personal injury equipment damage and environment deterioration Change History Changes between document issues are cumulative The latest document issue contains all the changes made in earlier issues Issue 02 2020 11 09 Updated the safety information Issue 01 2019 09 18 This issue is the first official release NetCol8000 A013 In room Air Coole...

Page 5: ...utdoor Unit 17 2 2 2 3 Controller 18 2 2 2 4 Monitoring System 19 2 3 Physical Ports 20 2 4 Operating Environment Specifications 21 2 5 Technical Specifications 22 3 Installation Guide 26 3 1 Tools 26 3 2 Materials 28 3 2 1 Optional Refrigerant R410A 29 3 2 2 Optional Refrigerant Oil RB75EA 30 3 2 3 Pipes 30 3 2 4 Pipe Support 33 3 2 5 Cables 33 3 3 Space Requirements 34 3 3 1 Indoor Unit Space Re...

Page 6: ...ation 59 4 Power On Commissioning 60 4 1 Controller Description 60 4 2 Equipment Power On 62 4 3 Setting Temperature and Humidity Values 67 4 4 Optional Setting Teamwork Parameters 69 4 5 Optional Setting Monitor Parameters 72 4 6 Commissioning Procedure 73 4 7 Checking After Commissioning 76 5 System Operation and Maintenance 77 5 1 Routine Maintenance 77 5 1 1 Routine Maintenance Overview 77 5 1...

Page 7: ...word 131 6 8 How Do I Set Alarm Parameters 133 6 9 How Do I Restore Default Settings 137 6 10 How Do I Set a New Administrator Password 140 6 11 How Do I Clear Total Runtime of a Device 143 6 12 How Do I Calibrate a Sensor 145 6 13 How Do I Upgrade Versions 147 6 14 How Do I Import and Export Data 150 6 15 How Do I Set a New Maintenance Password 153 6 16 How Do I View the Current Versions 155 A Co...

Page 8: ...w local laws and regulations when installing operating or maintaining the equipment The safety instructions in this document are only supplements to local laws and regulations Huawei will not be liable for any consequences of the following circumstances Operation beyond the conditions specified in this document Installation or use in environments which are not specified in relevant international o...

Page 9: ...n operation and maintenance Before handling a conductor surface or terminal measure the contact point voltage and ensure that there is no risk of electric shock After installing the equipment remove idle packing materials such as cartons foam plastics and cable ties from the equipment area In the case of a fire immediately leave the building or the equipment area and turn on the fire alarm bell or...

Page 10: ...ring equipment transportation or installation in a timely manner Equipment with scratches cannot be exposed to an outdoor environment for a long period of time Before operations ensure that the equipment is firmly secured to the floor or other solid objects such as a wall or an installation rack Do not use water to clean electrical components inside or outside of a cabinet Do not change the struct...

Page 11: ...onals personnel who are trained or experienced in equipment operations and are clear of the sources and degree of various potential hazards in equipment installation operation maintenance Trained personnel personnel who are technically trained have required experience are aware of possible hazards on themselves in certain operations and are able to take protective measures to minimize the hazards ...

Page 12: ...ties must be performed by qualified personnel Cabling When routing cables ensure that a distance of at least 30 mm exists between the cables and heat generating components or areas This prevents damage to the insulation layer of the cables Do not route cables behind the air intake and exhaust vents of the equipment Ensure that cables meet the VW 1 or ZB flame spread rating requirements or higher B...

Page 13: ...ing materials before storing or transporting them Figure 1 1 Wearing an ESD wrist strap Neutral Ground Voltage It is recommended that the three phase loads be equalized and the neutral ground voltage be kept at less than 2 V to meet power distribution requirements 1 4 Installation Environment Requirements To prevent fire due to high temperature ensure that the ventilation vents or heat dissipation...

Page 14: ...ear personal protective equipment such as the safety helmet and safety belt or waist rope and fasten it to a solid structure Do not mount it on an insecure moveable object or metal object with sharp edges Make sure that the hooks will not slide off Set a restricted area and eye catching signs for working at heights to warn away irrelevant personnel Carry the operation machinery and tools properly ...

Page 15: ...erglass ladders when you need to perform live working at heights When a step ladder is used ensure that the pull ropes are secured and the ladder is held firm Before using a ladder check that it is intact and confirm its load bearing capacity Do not overload it Ensure that the ladder is securely positioned The recommended angle for a ladder against the floor is 75 degrees as shown in the following...

Page 16: ...inside Metal shavings from drilling may short circuit boards inside the equipment Obtain the consent from the customer and subcontractor before drilling Wear goggles and protective gloves when drilling holes When drilling holes protect the equipment from shavings After drilling clean up any shavings that have accumulated inside or outside the equipment Moving Heavy Objects DANGER When removing a h...

Page 17: ... Safety Welding At least two persons are required on a welding site A welder must have a work permit A welding site must be free from inflammables Ensure that a fire extinguisher wet wiper and water container are available A burning welding torch must not be placed on a component or on the floor and must not be placed in a metal container with acetylene and oxygen Otherwise the gas may leak and ca...

Page 18: ...her wastes that have a shell in European Union EU areas To avoid environment pollution and harm to human health wastes must be classified and recycled This also promotes resource reuse When recycling a device fill in the device information in the recycling collection system or contact your dealer for help The dealer can help you recycle devices in a safe and environment friendly way 1 7 Others Exe...

Page 19: ... following product models NetCol8000 A013U4WE0 NetCol8000 A013U40E0 Figure 2 1 Model number Table 2 1 Model number description No Meaning Description 1 Data center smart cooling product NetCol data center smart cooling product 2 Series 8000 in room smart cooling product 3 Cooling mode A air cooled 4 Model code 013 model code 013 5 Airflow mode U Upflow NetCol8000 A013 In room Air Cooled Smart Cool...

Page 20: ...Model number No Meaning Description 1 Data center smart cooling product NetCol data center smart cooling product 2 Series 500 outdoor unit 3 Cooling mode A air cooled 4 Model code 018 model code 018 5 Power system 6 220 240 V 1 Ph 50 60 Hz 6 Climate type C Common non corrosive environment 7 Fan type 3 DC fan 8 Packaging type E Package for international markets 9 Special identifier for orders 0 Non...

Page 21: ...that then moves to the evaporator with heat transmitted to the refrigerant The refrigerant is discharged to the condenser using the compressor releasing heat to the outdoor environment The indoor unit and outdoor condenser are connected and circulate using refrigerant in a sealing manner Figure 2 3 Components 2 2 2 Main Components NetCol8000 A013 In room Air Cooled Smart Cooling Product User Manua...

Page 22: ...ance and Dimensions Figure 2 4 Appearance and dimensions unit mm NetCol8000 A013 In room Air Cooled Smart Cooling Product User Manual 600 mm Width 2 Product Description Issue 02 2020 11 09 Copyright Huawei Technologies Co Ltd 15 ...

Page 23: ...EV electric heater optional wet film humidifier optional and stop valve DC fan The DC centrifugal fan is used which supports stepless speed adjustment Evaporator The evaporator adopts the inner threaded copper pipe and blue hydrophilic aluminum foil to prevent water blowing due to condensate water accumulation and improve heat exchange performance The evaporator uses the I type design reducing the...

Page 24: ...difier The wet film humidifier has low water quality requirements and high environment adaptability It has a simple structure and is easy to remove clean and maintain It consumes less power saving more than 95 of energy compared with a traditional electrode humidifier The humidifier complies with China Compulsory Certification Stop valve The stop valve connecting the inner and outer pipes can be c...

Page 25: ...ility It is installed in the outdoor unit and easy to maintain Fan The DC axial fan is used which supports stepless speed adjustment 2 2 2 3 Controller Appearance The controller uses an LCD with a white backlight to display the working status sensor data and running status and runtime of the key components for the smart cooling product The user friendly interface is protected by multiple levels of...

Page 26: ...oling product enters the active mode one by one periodically balancing the service life of each smart cooling product On demand operation The number of operating smart cooling products varies with thermal loads in the equipment room to save energy A mechanism is adopted to prevent the smart cooling products in the same equipment room from operating in opposite status such as humidification and deh...

Page 27: ...ling stop valve for the end face Humidifier water inlet pipe Optional G 3 4 inch Drainpipe G 3 4 inch Outdoor unit Refrigerant liquid pipe Outer diameter 3 8 inch 9 52 mm sealing stop valve for the end face Refrigerant gas pipe Outer diameter 3 4 inch 19 05 mm sealing stop valve for the end face NetCol8000 A013 In room Air Cooled Smart Cooling Product User Manual 600 mm Width 2 Product Description...

Page 28: ... without refrigerant 40 C to 45 C outdoor unit with refrigerant Storage humidity 5 95 RH non condensing Outdoor unit operating temperature 20 C to 45 C Altitude 0 4000 m When the altitude exceeds 1000 m the power should be derated Installation Requirements Table 2 4 Installation requirements Item Specifications Equipm ent room door Width 1 2 m height 2 3 m Floor Bearing capacity 350 kg m2 NetCol80...

Page 29: ...al hardness in CaCO3 450 mg L For details refer to the GB 5749 2006 Standards for Drinking Water Quality Power require ments Earth leakage circuit breakers are not recommended for mains If earth leakage circuit breakers are required by the customer or according to local regulations use the residual current circuit breaker RCCB that is not sensitive to the single phase DC pulse and transient curren...

Page 30: ... Refrigerant R410A Cooling capacitya 12 5 kW Air supply mode Upflow Air volume 3100 m3 h Pipe routing Bottom left and right pipe routing Cabling mode Bottom left and right cabling IP rating IP20 Dimensions H x W x D 2000 mm x 600 mm x 600 mm Heating function No Yes Humidification function No Yes Reheating capacity 4 kW Humidifying capacity 2 kg h NetCol8000 A013 In room Air Cooled Smart Cooling Pr...

Page 31: ...60 Hz 1 Ph N PE Voltage tolerance 15 to 10 frequency tolerance 3 Hz Max current 30 A Net Gross weight 90 kg 108 kg Protection level IPX4 Environment class Class B Altitude 0 4000 m derating at above 1000 m Certification CE CQC CCC third party performance certification CRAA SASO TUV Environmental protection RoHS Reach WEEE Outdoor unit installation environments are classified as follows based on th...

Page 32: ...ts with simple shielding measures within 1 2 km from a pollution source Class D marine environment environments within 500 m from the coast NetCol8000 A013 In room Air Cooled Smart Cooling Product User Manual 600 mm Width 2 Product Description Issue 02 2020 11 09 Copyright Huawei Technologies Co Ltd 25 ...

Page 33: ...tep ladder 2 m Adjustable wrench 6 Phillips screwdriver M4 and M6 Flat head screwdriver 2 5 mm Torque wrench Right angle Socket wrench M6 M8 and M12 Hex key 5 mm Pipe bender NetCol8000 A013 In room Air Cooled Smart Cooling Product User Manual 600 mm Width 3 Installation Guide Issue 02 2020 11 09 Copyright Huawei Technologies Co Ltd 26 ...

Page 34: ... Hammer drill Pallet truck Table 3 2 Special tools Name Specifications and Appearance Antifreeze gloves Electric balance Welding torch 5 silver solder Oxygen Acetylene Hot melt device Clamp meter NetCol8000 A013 In room Air Cooled Smart Cooling Product User Manual 600 mm Width 3 Installation Guide Issue 02 2020 11 09 Copyright Huawei Technologies Co Ltd 27 ...

Page 35: ...alve must be installed on the head of the nitrogen cylinder and the reducing valve range 4 0 MPa d Vacuum pump airflow 2 4 L s absolute vacuum 60 Pa e For equipment with humidifiers ensure that the following requirements are met Applicable to all pipe materials Anaerobic metal pipe thread sealant with PTEF as the padding Maximum gap 0 5 mm Pressure resistance above 1 6 MPa Compliant with the indus...

Page 36: ...e that corresponds to the measured external surface temperature according to Table 3 3 and calculate the deviation from the measured internal pressure If the deviation is more than 0 2 MPa the refrigerant is not qualified and should be replaced Figure 3 1 Checking refrigerant Table 3 3 Mapping between temperatures and R410A saturation pressures Temperatur e C Saturation Pressure Surface Pressure M...

Page 37: ... refrigerant oil has been filled in the indoor compressor before delivery to ensure the reliable running of a 60 m long pipe Additional refrigerant oil is not required during onsite installation When the compressor is damaged refrigerant oil has been filled in the compressor before the compressor is replaced Additional refrigerant oil is not required during replacement Add refrigerant oil based on...

Page 38: ...e 3 8 inch 9 52 mm wall thickness 0 75 mm pressure withstanding capacity 4 5 MPa Gas pipe 3 4 inch 19 05 mm wall thickness 1 0 mm pressure withstanding capacity 4 5 MPa Thermal insulation foam 13 mm Water Pipe Figure 3 3 shows how to connect a drainpipe NetCol8000 A013 In room Air Cooled Smart Cooling Product User Manual 600 mm Width 3 Installation Guide Issue 02 2020 11 09 Copyright Huawei Techno...

Page 39: ...ier water inlet pipe 1 Connector with outer screw thread G 3 4 inch 2 Rigid pipe conversion adapter G 3 4 inch connected to a rigid pipe with inner screw threads 3 Active connector G 3 4 inch inner thread PP R 4 Rigid pipe made of PP R or other material 5 Elbow made of PP R or other materials NOTE The object shown in the broken line box is reserved port of the smart cooling product The hose clamp ...

Page 40: ... steel Install a support every 1500 mm for the straight sections of pipes and 500 mm away from each bending point in turning sections 3 2 5 Cables NOTICE The site ground resistance must be less than 0 1 ohm The fireproof level of the cables must be at least VB The signal cables of indoor and outdoor units must be shielded cables and the shielding layer must be reliably grounded Table 3 5 lists the...

Page 41: ...WG black three core wires 10 A shielded outdoor cable UL The length is determined by site survey Naked crimping terminal single wire cord end terminal 1 5 mm2 16 A Red Delivered with the fittings 3 3 Space Requirements 3 3 1 Indoor Unit Space Requirements Equipment Room Requirements To ensure that the environment control system in the smart cooling product room works properly take moisture proof a...

Page 42: ...hortened the supply and return air will mix up and air noise will be caused To ensure good ventilation do not place the smart cooling product in the corner of a room or at the end of a long and narrow room To facilitate the normal maintenance of the indoor unit do not install other devices above the indoor unit Figure 3 6 Space requirements side pipe routing Figure 3 7 Space requirements bottom pi...

Page 43: ...nstalled against a wall or the local outdoor temperature may be below 5 C place an air baffle at the air intake side of the outdoor unit based on Figure 3 9 Figure 3 9 Space requirements for installing an air baffle Installing an outdoor unit on a wall as shown in Figure 3 10 NetCol8000 A013 In room Air Cooled Smart Cooling Product User Manual 600 mm Width 3 Installation Guide Issue 02 2020 11 09 ...

Page 44: ... a wall or the local outdoor temperature may be below 5 C place an air baffle at the air intake side of each outdoor unit Figure 3 11 Space requirements for installing multiple outdoor units 3 4 Layout Principles The layout principles are as follows If the outdoor unit is placed higher than the indoor unit the maximum height deviation between them should be less than or equal to 20 meters Install ...

Page 45: ...hat the scale of the pipe tilting is 1 200 The pipe tilting direction should be consistent with the hypotenuse of the right triangle Figure 3 12 Layout of sideward piping 1 Oil trap 2 Tilted gas pipe 3 Tilted liquid pipe NetCol8000 A013 In room Air Cooled Smart Cooling Product User Manual 600 mm Width 3 Installation Guide Issue 02 2020 11 09 Copyright Huawei Technologies Co Ltd 38 ...

Page 46: ...Humidifier water inlet pipe hole 4 Drainpipe hole 5 Gas pipe hole 6 Liquid pipe hole Figure 3 14 Holes dimensions unit mm NetCol8000 A013 In room Air Cooled Smart Cooling Product User Manual 600 mm Width 3 Installation Guide Issue 02 2020 11 09 Copyright Huawei Technologies Co Ltd 39 ...

Page 47: ...of the needle valve bonnets shown in Figure 3 16 is missing by turns 1 If they do not exist contact Huawei technical support 2 If they exist remove each valve bonnet and press the valve plugs in turn If nitrogen is exhausted the system is working properly If no nitrogen is exhausted contact Huawei technical support NetCol8000 A013 In room Air Cooled Smart Cooling Product User Manual 600 mm Width 3...

Page 48: ... base or floor mounting holes according to the following figure Figure 3 17 Mounting hole sizes Step 3 Move the smart cooling product to the installation position Step 4 Secure the indoor unit to the base or floor using a torque wrench NetCol8000 A013 In room Air Cooled Smart Cooling Product User Manual 600 mm Width 3 Installation Guide Issue 02 2020 11 09 Copyright Huawei Technologies Co Ltd 41 ...

Page 49: ...are recommended to stand the outdoor unit during transportation If tilt is not avoidable the tilt degree cannot exceed 15 Do not hold the fan guard on the shell Otherwise it will be deformed Do not touch the blades using hand or any other object After installing the outdoor unit remove the protective cardboard of condenser fin NetCol8000 A013 In room Air Cooled Smart Cooling Product User Manual 60...

Page 50: ...d secure the outdoor unit to the concrete base using four M10 expansion bolts as shown in Figure 3 19 Figure 3 19 Installing an outdoor unit End 3 9 Connecting Refrigerant Pipes Context Tools adjustable wrench 250 mm x 30 mm hex key 5 mm torque wrench 17 19 27 30 36 NetCol8000 A013 In room Air Cooled Smart Cooling Product User Manual 600 mm Width 3 Installation Guide Issue 02 2020 11 09 Copyright ...

Page 51: ...impurities Avoid elbows and ensure that the connection between the indoor and outdoor units is the shortest The refrigerant pipes should be wrapped with thermal insulation foam Procedure Step 1 Weld pipes in the medium segment by referring to Figure 3 21 NOTICE Exercise caution during welding to avoid burning components such as rubber rings inside the cabinet During the welding charge a little nit...

Page 52: ...of the active connector nut are free of impurities and scratches Clean up impurities using alcohol or a wet cloth For any scratch contact Huawei technical support for replacement 3 Keep the adapter nut and the stop valve screw thread on the same center line Secure the adapter to the stop valve with the other hand and tighten the nut using a torque wrench NOTICE Tighten the liquid pipe stop valve u...

Page 53: ...sure that you tighten the nut to the specified torque The failure torque for the pipe nut of the liquid pipe stop valve is 70 N m and that for the pipe nut of the gas pipe stop valve is 100 N m The torque greater than the failure torque will damage the screw thread NetCol8000 A013 In room Air Cooled Smart Cooling Product User Manual 600 mm Width 3 Installation Guide Issue 02 2020 11 09 Copyright H...

Page 54: ...on and the straight section of the engineering pipe outside the cabinet Open the pipe nut of the stop valve and tighten the welded pipe to the stop valve by the torque wrench Figure 3 24 Side pipe routing Bottom pipe routing Open the rubber hole on the bottom plate Weld the gas liquid connection and gas liquid pipe outside the cabinet Open the pipe nut of stop valve and tighten the welded pipe com...

Page 55: ...gid pipe conversion adapter to the water inlet pipe connector Step 2 Route the external water inlet pipe into the cabinet through the side plate or bottom plate Connect the external water inlet pipe to the rigid pipe conversion adapter Figure 3 26 Connecting the water inlet pipe Step 3 Secure water pipes using cable ties and seal the pipe hole using firestop putty End NetCol8000 A013 In room Air C...

Page 56: ... rigid pipe conversion adapter to the drainpipe connector Step 2 Route the external drainpipe into the cabinet through the side plate or bottom plate Connect the external drainpipe to the rigid pipe conversion adapter Figure 3 27 Bottom pipe routing Figure 3 28 Side pipe routing NetCol8000 A013 In room Air Cooled Smart Cooling Product User Manual 600 mm Width 3 Installation Guide Issue 02 2020 11 ...

Page 57: ...bles control cables and ground cables must comply with the local electrical code and the cable specifications should comply with the local cabling specifications For details about the currents in full load see the NetCol8000 A nameplate The cable dimensions must comply with the local cabling rules Primary power supply requirements 380 415 V 3 phase 50 60 Hz see the indoor unit nameplate Only train...

Page 58: ...figured by the customer The general power cable of the indoor unit must be reliably secured by a cable clip Figure 3 30 shows how to connect the indoor unit power cable Figure 3 30 Connecting the indoor unit power cable 3 11 3 Optional Connecting the Indoor Unit Signal Cables Figure 3 31 Signal terminals NetCol8000 A013 In room Air Cooled Smart Cooling Product User Manual 600 mm Width 3 Installati...

Page 59: ...nd the Signal Cable Between Indoor and Outdoor Units Connect the L N and GND wires of the outdoor unit to the L N and GND terminals of the indoor unit Connect the P Q and E wires of the outdoor unit to the X2 1 X2 2 and X2 3 terminals of the indoor unit NOTE The signal cables of indoor and outdoor units must be shielded cables and the shielding layer must be reliably grounded Figure 3 32 Connectin...

Page 60: ...UP RS485 D Pin8 GROUP RS485 D NOTE The cables must be shielded cables and the shielding layer must be reliably grounded Connecting Teamwork Cables NetCol8000 A013 supports teamwork networking hand in hand In networking a maximum of 32 smart cooling products can be teamworked After power on choose Setting User Menu Teamwork Setting and set Enable Teamwork Resistor for the controllers of the first a...

Page 61: ... port on the first smart cooling product in the teamwork networking to the monitoring device An 32 Considering the monitoring speed it is recommended that An be less than or equal to 8 Figure 3 34 Connecting RS485 monitoring cables 3 11 6 Cable Routes The bottom routing for power cables and the signal cable between indoor and outdoor units is shown in the figure NetCol8000 A013 In room Air Cooled ...

Page 62: ...greater than or equal to 4 0 MPa and the tolerance range of the leather hose must be greater than or equal to 4 5 MPa During the pressure preservation process do not remove the leather hose and pressure gauge otherwise nitrogen may leak Procedure Step 1 Open the stop valves for the gas pipe and liquid pipe of the indoor unit NOTICE Before opening the indoor unit stop valves ensure that the stop va...

Page 63: ...g ambient temperature conditions If there is considerable temperature change and the pressure changes perform the test again Step 4 If welding defects exist locate and repair the leak point If the pressure does not change exhaust the nitrogen through the injection needle valves End 3 13 Vacuumization Prerequisites Check that all pipe connectors are correct and the refrigerant pipe tilts and has su...

Page 64: ...oling system Step 3 After 20 minutes the pressure gauge pointer should be in the negative area and the vacuum pump makes small noises Close and open the pressure gauge alternatively for several times The position of the pressure gauge pointer and the noises made by the vacuum pump do not change Otherwise the cooling system may not be sealed properly Step 4 Check that the time for vacuuming is 80 m...

Page 65: ...nt from spraying out After the vacuumization and before removing the rubber hose ensure that there is positive pressure inside the refrigerant pipe of the indoor unit For detailed operations see step 1 3 in section Commissioning Components Step 7 Remove the hose pressure gauge and vacuum pump Step 8 Install needle valve nut and rear cover nut of indoor unit and outdoor unit Step 9 Wrap the gas pip...

Page 66: ...ed specifications of the upstream switch meet the maximum current requirement Passed Failed Cabinet The cabinet is installed properly without any tilt The cabinet is secured The foreign matter inside the cabinet such as cable ties and cable cuts is cleaned up Passed Failed Wet film humidifier The humidifier water inlet pipe is properly connected and secured Passed Failed Water pan The foreign matt...

Page 67: ... sound is generated press this key to mute the sound until the next different alarm is raised If an alarm needs to be cleared manually press and hold this key for 3 seconds to generate a prompt tone prompting that it has been eliminated NetCol8000 A013 In room Air Cooled Smart Cooling Product User Manual 600 mm Width 4 Power On Commissioning Issue 02 2020 11 09 Copyright Huawei Technologies Co Ltd...

Page 68: ... the next level menu screen On the bottom level submenu screen press this key to make the configurable parameter where the cursor is located enter the modification status When modifying a parameter press this key to complete parameter modification Press and hold for 3 seconds to unlock the keys 6 Up On a menu screen press this key to move the cursor up When modifying a parameter if the cursor is l...

Page 69: ...ssword are also restored to the default password 000001 4 2 Equipment Power On Prerequisites Check that the cables to the indoor and outdoor units are correctly connected and that the input voltage meets requirements Ensure that the smart cooling product circuit breaker in the upstream PDB is OFF Context NOTICE The parameters under the administrator menu must be modified by certified technical per...

Page 70: ... only to access the user menu and cannot be used to access the administrator menu or maintenance menu Procedure Step 1 Switch on the circuit breaker for the indoor unit on the upstream PDB NOTICE Before turning on the circuit breaker of indoor unit ensure that no one operates the outdoor unit If the outdoor unit does not take the electricity from indoor unit switch on the circuit breakers for the ...

Page 71: ...quences Step 3 After the startup screen ends the screen for the initial startup password is automatically displayed Figure 4 3 Initial startup screen Step 4 Obtain the 8 digit startup password for this model through the Service Expert app based on the model barcode and verification code 1 Open the Service Expert app 2 Tap StartUp on the home screen of the app NetCol8000 A013 In room Air Cooled Sma...

Page 72: ...nd the screen shown in the following figure Figure 4 5 Generating a startup password NetCol8000 A013 In room Air Cooled Smart Cooling Product User Manual 600 mm Width 4 Power On Commissioning Issue 02 2020 11 09 Copyright Huawei Technologies Co Ltd 65 ...

Page 73: ...pp again unless a new indoor unit is installed Step 5 After the initial startup the display panel displays the home screen Figure 4 6 Home screen Table 4 3 Icon description No Icon Name Description 1 Indoor fan rotational speed percentage Current rotational speed of the indoor fan Maximum rotational speed x 100 2 Compresso r rotational speed percentage Current rotational speed of the compressor Ma...

Page 74: ... lock icon appears again To access the setting or maintenance menu you need to re enter the correct password 7 Monitoring icon If the unit is in monitoring mode this icon exists Otherwise this icon does not exist 8 Teamwork icon If the unit is in teamwork mode this icon exists Otherwise this icon does not exist 9 Alarm icon If the unit has raised an alarm this icon blinks Otherwise this icon does ...

Page 75: ...umid Setting and set Return Air Temp Set and Return Air Humid Set as required NOTE After selecting the parameters you want to set by and press to set up and then press to confirm when you are finished Figure 4 8 Temperature and humidity setting Step 4 After the setting is complete tap to return to the user menu End NetCol8000 A013 In room Air Cooled Smart Cooling Product User Manual 600 mm Width 4...

Page 76: ...ddress is set to 1 master unit the menus on the last two screens are viewable and configurable Otherwise the last two screens are not displayed Step 3 Set Teamwork Function to Enable Step 4 Set the Unit Address of the master unit to 1 and the Unit Address of the slave unit to an integer other than 1 Step 5 Set other parameters based on the following table NetCol8000 A013 In room Air Cooled Smart C...

Page 77: ...nits in the group Set the planned unit address Enable Teamwork Resistor Indicates the build out resistor status of each smart cooling product in a teamwork group Set this parameter to No for non teamwork scenarios For teamwork scenarios set this parameter to Yes for the first and last smart cooling products in a teamwork group and set it to No for other smart cooling products Units in Group Indica...

Page 78: ...en the load power is even Disable Rotation Type Can be set to Address or hour You are advised not to change the value Address Rotation Cycle Indicates the interval between rotations The value ranges from 1 to 30 1D Rotation Time Indicates the time when rotation takes place The value can be any hour in a day 0 23 00 00 High Temp Start All When it is enabled if the return air temperature is higher t...

Page 79: ...ange the value 13 C Step 6 After the setting is complete tap to return to the user menu End 4 5 Optional Setting Monitor Parameters Procedure Step 1 Choose Comm Setting from the user menu and tap to access the communication setting screen Figure 4 10 Communication settings Step 2 Set Baud Rate Comm Address and Enable Monitoring Resistor based on site requirements NetCol8000 A013 In room Air Cooled...

Page 80: ...rocedures for such components NOTICE The outdoor unit has been charged R410A refrigerant for 5 kg before delivery The indoor unit has been charged no refrigerant If the R410A refrigerant is provided by Huawei put the refrigerant cylinder upside down when charging the refrigerant If the refrigerant is not provided by Huawei check with the refrigerant provider whether the cylinder has a siphon If th...

Page 81: ...ter a period of time the electric heater runs properly In this case tap Off for the electric heater and change the input of the indoor fans to 0 Step 6 Commission the compressor by setting the compressor rotational speed to 3000 rpm 1 According to the one way pipe length determine whether it is need to fill the refrigerant If you need to fill refrigerant fill refrigerant through the needle valve o...

Page 82: ... Suction Superheat Degree Supercool Below 15 C 1 5 2 5 MPa 0 7 1 2 MPa 4 10 C 3 5 C 15 35 C 1 5 3 1 MPa 35 45 C 2 5 3 8 MPa Above 45 C 3 1 4 15 MPa 3 On the diagnostic mode screen change the compressor input to 0 rpm Step 7 Commission the humidifier 1 Confirm that the upstream inlet valve of the wet film humidifier is open 2 In diagnostic mode start the wet film humidifier 3 Check that the water i...

Page 83: ...e needle valve plug is secured torque of 0 45 0 05 N m and the valve bonnet is tightened Passed Failed The foreign matter inside the water pan and bottom plate is cleaned up Passed Failed The air filter is correctly installed Passed Failed NetCol8000 A013 In room Air Cooled Smart Cooling Product User Manual 600 mm Width 4 Power On Commissioning Issue 02 2020 11 09 Copyright Huawei Technologies Co ...

Page 84: ...e NOTICE CAUTION WARNING and DANGER statements in this document do not represent all safety instructions They are only supplements to the safety instructions Personnel who will install operate and maintain Huawei equipment must receive thorough training understand all necessary safety precautions and be able to correctly perform all operations Pay attention to the safety symbols on the equipment a...

Page 85: ...t blocked Clean the air filter with water recommended Check that the return air filter is not damaged or distorted If it is damaged replace the air filter Wet film humidifier Check that the valve on the water inlet pipe is open Open the valve on the water inlet pipe Check that the wet film is clean and have no scale If there is much water scale replace the wet film humidifier Check that no operati...

Page 86: ...eck that the fan runs properly without abnormal noise or vibration and the blades rotate properly Replace the outdoor fan Yearly Preventive Maintenance Table Table 5 3 Yearly preventive maintenance table on the basis of quarterly preventive maintenance Maintenance Item Expected Result Troubleshooting Monitoring unit Export smart cooling product logs alarms temperature humidity the operating status...

Page 87: ...y days If unavoidable take protective measures to prevent water from entering the outdoor unit When opening the electric control box cover clear water from the cover Certain circuits in the smart cooling product have lethal voltages Only professional technicians are allowed to perform maintenance Exercise caution during troubleshooting with power on If jumpers are used for troubleshooting always r...

Page 88: ...has exceeded the maximum operating time Replace the wet film humidifier Water supply fails Check and maintain the water supply source and pipe Water overflows The drainpipe is not connected or the drainpipe does not meet the gradient requirements Ensure that the drainpipe is connected to the pump correctly and the gradient of the drainpipe meets the requirements The condensate water pump is faulty...

Page 89: ...uirements Install outdoor units in the right positions based on the installation requirements Air enters the refrigerant loop Check the discharge temperature and pressure Eliminate and retrieve refrigerant Refill refrigerant Heat dissipation is poor because the condenser is dirty or blocked Clean the condenser fins using a fin brush The outdoor fan fails Check whether the outdoor fan works properl...

Page 90: ...rature is too low Increase the temperature setting The air filter is dirty or blocked Replace the air filter The electronic expansion valve coil is faulty Replace the electronic expansion valve coil Refrigerant has been charged too much Reclaim part of refrigerant The compress or generates too much operating noise It is common that the compress or generates much noise when it shuts down Liquid is ...

Page 91: ... A power failure occurs and the equipment is restarted within a short period of time 1 Check that the indoor fan is not blocked 2 Check that the air vent of the indoor unit is not blocked 3 Check the fan cable connections 4 Replace the fan drive or indoor fan 5 Do not power on and restart the equipment immediately after a power failure occurs 103 InFan Comm Interrupt Alarm Turn off all 1 Cables to...

Page 92: ...nsor is faulty 5 The refrigerant is overfilled 6 The outdoor unit is not properly installed 1 Clean the condenser fins 2 Maintain or replace the outdoor fan drive or outdoor fan 3 Check the cable connections to the high pressure sensor 4 Maintain or replace the high pressure sensor 5 Decrease certain amount of refrigerant 6 Reinstall the outdoor unit 202 Comp Discharge HP Lock Alarm The compressor...

Page 93: ...e the indoor fan drive or indoor fan 4 Check the cable connections to the low pressure sensor 5 Maintain or replace the low pressure sensor 6 Identify and repair the leaking points and refill refrigerant after maintenance 7 Reinstall the indoor unit 8 Check and fully open the stop valve 9 Check and replace the connecting pipe 10 Maintain or replace the EEV coil or EEV 204 Comp Suction LP Lock Alar...

Page 94: ...the outdoor fan drive or outdoor fan 3 Check the cable connections to the high pressure switch 4 Maintain or replace the high pressure switch 5 Decrease certain amount of refrigerant 6 Reinstall the outdoor unit 206 Comp HP Switch Lock Alarm The compressor shuts down The alarm needs to be manually cleared The Comp HP Switch Alarm is triggered multiple times within a specified period of time Refer ...

Page 95: ...cable connections to the low pressure switch 4 Maintain or replace the low pressure switch 5 Identify and repair the leaking points and refill refrigerant after maintenance 6 Reinstall the indoor unit 7 Maintain or replace the EEV coil or EEV 8 Check and fully open the stop valve 9 Check and replace the filter 10 Check that the selected model is correct 11 Check and replace the connecting pipe 208...

Page 96: ...aintain or replace the solenoid valve coil or the solenoid valve 5 Identify and repair the leaking points and refill refrigerant after maintenance 6 Reinstall the outdoor unit 7 Maintain or replace the EEV coil or EEV 8 Check and fully open the stop valve 9 Check and replace the filter 10 Check and replace the connecting pipe 210 Comp Discharge HT Lock Alarm The compressor shuts down The alarm nee...

Page 97: ...he compressor fails to start 2 At least two cables between the compressor and the drive board are not connected 3 The output of the inverter module of the compressor drive board is faulty 1 Check the refrigerant of the compressor 2 Check the cables between the compressor and the drive board 3 Replace the compressor drive board 213 Comp Start Fail Alarm The compressor shuts down The difference betw...

Page 98: ...he compressor drive board if it is faulty 215 Comp Drive DC Undervolt Alarm The compressor shuts down The input voltage of the compressor drive board is lower than the preset threshold 1 Check whether the input power is within the normal range 2 Use an oscilloscope to check whether the waveform of the power grid is within the normal range 3 Replace the compressor drive board if it is faulty NetCol...

Page 99: ...e outdoor unit is poor and whether the outdoor unit is blocked 4 Check whether the fins of the outdoor unit are polluted which causes the air intake volume of the outdoor unit to be small 217 Comp Drive Alarm The compressor shuts down The compressor drive board of the outdoor unit is faulty 1 Check the compressor status 2 Check the connection status of the compressor and the drive board 3 Check th...

Page 100: ...ware Fault and Comp Start Fail Alarm is raised six times within one hour 1 Check the compressor status 2 Check the connection status of the compressor and the drive board 3 Check the status of the compressor drive board 4 Replace the compressor drive board or compressor 220 Comp Preheating Alarm The compressor shuts down The compressor preheating function is started and the preheating is not compl...

Page 101: ... 3 Calibrate or replace the suction pressure sensor 4 Maintain or replace the filter 5 Maintain or replace the EEV 6 Check that the air vent of the indoor unit is not blocked 7 Check the cable connections to the indoor fan 222 Comp Run Timeout Alarm The runtime of the compressor exceeds the preset threshold Replace the compressor and clear the cumulative runtime 223 Comp Type Unmatched Alarm The c...

Page 102: ...e alarm needs to be manually cleared The EEV Low Superheat Alarm is triggered multiple times within a specified period of time Refer to the solution to the EEV Low Superheat Alarm 303 EEV Drive Alarm The compressor shuts down 1 The EEV is not connected 2 The EEV coil is short circuited 3 The EEV drive circuit of the indoor unit main control board is faulty 1 Check the cables to the EEV 2 Check whe...

Page 103: ...hold Replace the electric heater and clear the cumulative runtime 502 Wet Film Humid Replace Alarm The runtime of the humidifier wet film exceeds the preset threshold Replace the humidifier wet film and clear the cumulative runtime 504 Humid Power Abnormal Alarm The humidification system is shut down 1 The power module of the humidifier is faulty 2 The humidifier power cable is not properly connec...

Page 104: ...tdoor unit is in the strong wind state 3 Outdoor fan 1 is faulty 1 Reinstall the outdoor unit 2 Add air baffles 3 Replace outdoor fan 1 609 OutUnit High Temp Alarm The compressor shuts down 1 The ambient temperature is higher than the upper threshold 2 There is strong radiation on the monitoring point resulting in high temperature 3 The temp displayed is different from the actual temp 1 Measure th...

Page 105: ...ulty 1 Check the cable connection to the temperature sensor 2 Maintain or replace the temperature sensor 705 Outdoor Temp Sensor Fault The compressor shuts down 705 and 706 are triggered at the same time 1 The temperature sensor cable is not properly connected 2 The temperature sensor is faulty 1 Check the cable connection to the temperature sensor 2 Maintain or replace the temperature sensor 706 ...

Page 106: ... the outdoor unit and the compressor drive board is faulty 1 Check whether the power supply to the compressor drive board is normal 2 Replace the compressor drive board if it is damaged 709 OutUnit Mainboard Fault The E square of the main control board of the outdoor unit is faulty Replace the main control board of the outdoor unit 710 OutUnit Power Hardware Fault The compressor shuts down The com...

Page 107: ...ly voltage of the indoor unit is too low 2 The power supply voltage of the outdoor unit is too low 1 Increase the power supply voltage of the indoor unit 2 Increase the power supply voltage of the outdoor unit 714 Power Overvolt Alarm Turn off all 1 The power supply voltage of the indoor unit is too high 2 The power supply voltage of the outdoor unit is too high 1 Decrease the power supply voltage...

Page 108: ...t is faulty Replace the main control board of the indoor unit 720 InUnit Flash Alarm The compressor shuts down The flash memory of the main control board of the indoor unit is faulty Replace the main control board of the indoor unit 721 InUnit Clock Abnormal Alarm The clock circuit of the main control board of the indoor unit is faulty Replace the main control board of the indoor unit 722 Smoke Se...

Page 109: ...ling products 2 Check whether other causes exist if the alarm is not cleared in a long time after startup 3 Check the ambient temperature 4 Adjust the return air high temperature alarm threshold 5 Calibrate or replace the temperature sensor 802 Return Air Low Temp Alarm 1 The heat load is low or the cooling capacity is too high 2 The ambient temperature is too low 3 The return air low temperature ...

Page 110: ...air low humidity alarm threshold is inappropriate for the working conditions 4 The humidity displayed by the humidity sensor is different from the actual humidity 1 Replace the unit with one that has heating and humidification functions 2 Start the humidification function 3 Adjust the return air low humidity alarm threshold 4 Calibrate or replace the humidity sensor 805 Smoke Sensor Alarm Turn off...

Page 111: ...n 2 The air conditioner is remotely shut down 3 The air conditioner is shut down over the LCD 1 Start the air conditioner 2 Start the air conditioner remotely 3 Start the air conditioner over the LCD 5 4 Parts Replacement After replacing any part verify that the new part works properly 5 4 1 Replacing Indoor Unit Components 5 4 1 1 Replacing an Air Filter Prerequisites An air filter needs to be re...

Page 112: ... down on the home screen Tap Yes on the shutdown confirmation screen displayed Step 2 Open the front door and turn off the indoor unit circuit breaker and circuit breaker in the power distribution cabinet Step 3 Use a Phillips screwdriver to remove the six screws that secure the fan cover and remove the fan cover as shown by 1 in Figure 5 2 Step 4 Use diagonal pliers to cut off the cable tie that ...

Page 113: ...heater in the sequence from Step 7 to 3 Step 9 Power on the equipment choose Maintain Performance Maintain on the home screen and clear the total runtime of the electric heater Step 10 Tap on the home screen and tap Yes on the start confirmation screen displayed Ensure that the smart cooling product is running normally without any alarms End 5 4 1 3 Optional Replacing a Wet Film Humidifier Prerequ...

Page 114: ...re 5 3 Step 5 Use a Phillips screwdriver to remove the screw that secures the wet film humidifier and pull out the humidifier as shown by 3 and 4 in Figure 5 3 Step 6 Install the new wet film humidifier in the sequence from Step 5 to Step 3 Step 7 Power on the equipment choose Maintain Performance Maintain on the home screen and clear the total runtime of the wet film humidifier Step 8 Tap on the ...

Page 115: ...cover as shown by 1 in Figure 5 4 Step 4 Remove the baffle plate from the electric control box Use diagonal pliers to cut off the cable ties that secure the fan cable remove the fan terminal CN4 from the fan drive board and pull out the cable to the near of the fan Step 5 Remove the air supply temperature sensor and move the sensor cable under the fan Step 6 Use a Phillips screwdriver to remove th...

Page 116: ...en and tap Yes on the start confirmation screen displayed Ensure that the smart cooling product is running normally without any alarms End 5 4 1 5 Replacing a Main Control Board Prerequisites A main control board needs to be replaced A spare main control board of the same model is available and functional Context Tool Phillips screwdriver Preparation Power off the indoor unit The following figure ...

Page 117: ...t you know how to bind the cable ties and install the cable terminals later Step 4 Remove the eight screws that secure the main control board and remove the main control board Step 5 Install the new main control board in reverse order Step 6 Tap on the home screen and tap Yes on the start confirmation screen displayed Ensure that the smart cooling product is running normally without any alarms End...

Page 118: ...ve the nine screws that secure the baffle plate of the electric control box and remove the baffle plate from the electric control box Step 3 Remove the cable terminals from the fan drive board NOTE Take a photo before performing this step so that you know how to bind the cable ties and install the cable terminals later Step 4 Remove the six screws that secure the fan drive board and remove the fan...

Page 119: ...s screwdriver Procedure Step 1 Open the front door Step 2 Remove the cables from the LCD Step 3 Use a Phillips screwdriver to remove the four screws from the rear of the LCD Step 4 Remove the LCD and backplane Step 5 Install the new LCD and backplane in reverse order Step 6 Install the LCD cables Step 7 Choose Maintenance USB Wizard Configuration Import to import historical data Step 8 After the c...

Page 120: ...gerant Step 5 Pry the EEV coil off using a flat head screwdriver as shown in Figure 5 8 Step 6 Weld the two ends of the EEV using a welding torch as shown in Figure 5 8 Then remove the EEV Figure 5 8 Removing the EEV Step 7 Weld a new EEV and install the coil for the EEV NOTICE Protect the surrounding components during the welding process Step 8 Inject nitrogen and preserve the pressure After chec...

Page 121: ...MPa Step 12 Enter the diagnostic mode and set the compressor rotational speed to 0 rpm Exit the diagnostic mode Step 13 Power on the equipment choose Maintain Performance Maintain on the home screen and clear the total runtime of the EEV End 5 4 2 Replacing Outdoor Unit Components 5 4 2 1 Replacing an Outdoor Fan Prerequisites An outdoor fan needs to be replaced A spare outdoor fan of the same mod...

Page 122: ...he top cover and front upper panel using a Phillips screwdriver 2 Use a flat head screwdriver to remove the red clip of the fan terminal CN17 of the control board and then remove the interconnection terminal 3 Pull out the cable from the fan side 4 Use a socket wrench to remove the four screws that secure the motor mounting plate and take out the motor and cable Step 5 Install the new outdoor fan ...

Page 123: ...e control board of the same model is available and functional Context Tools Phillips screwdriver diagonal pliers and cable tie Preparation Power off the outdoor unit Procedure Step 1 Turn off the indoor unit circuit breaker and circuit breaker in the power distribution cabinet NOTICE If the outdoor unit does not take the electricity from indoor unit turn off the circuit breaker for the outdoor uni...

Page 124: ...e terminals later Step 4 Remove the cover of the middle liquid cooling cold plate using a Phillips screwdriver Step 5 Use a Phillips screwdriver to remove the bolts that secure the control board and Pull out the control board upwards Figure 5 12 Removing the control board 1 Liquid cooling cold plate Step 6 Install a new control board and tighten the bolts to secure it NetCol8000 A013 In room Air C...

Page 125: ...rvation tool vacuumization tool refrigerant injection tool adjustable wrench and sealant Preparation Power off the outdoor unit Procedure Step 1 Turn off the indoor unit circuit breaker and circuit breaker in the power distribution cabinet NOTICE If the outdoor unit does not take the electricity from indoor unit turn off the circuit breaker for the outdoor unit Step 2 Reclaim all the refrigerant f...

Page 126: ... product does not leak vacuumize the smart cooling product and charge refrigerant Step 10 Reinstall all the panels Step 11 Power on the smart cooling product and startup it Choose Maintain Diagnostic Mode and set the compressor rotational speed to 3000 rpm 1 After the compressor speed stabilizes at 3000 rmp for about 10 minutes choose Run Device Run State to view the Suction Pressure Discharge Pre...

Page 127: ...actly as standard charge required Refrigerant charging too much would result in high discharge pressure Refrigerant charging too little would result in low suction pressure low discharge pressure and high suction overheating degree 2 The air inlet and outlet of outdoor unit are without block The air inlet and outlet blockage would result in high discharge pressure 2 On the diagnostic mode screen c...

Page 128: ...ure 6 1 Menu screen Step 2 Move the cursor to Run by pressing the or key Step 3 Press the key to access the run submenu screen Step 4 Move the cursor to Temp Humid Param by pressing the or key NetCol8000 A013 In room Air Cooled Smart Cooling Product User Manual 600 mm Width 6 FAQ Issue 02 2020 11 09 Copyright Huawei Technologies Co Ltd 121 ...

Page 129: ...enu Step 6 Query all contents under this submenu by pressing the and keys End 6 2 How Do I Check Device Running State Procedure Step 1 On the home screen press the key to access the menu screen Figure 6 4 Menu screen NetCol8000 A013 In room Air Cooled Smart Cooling Product User Manual 600 mm Width 6 FAQ Issue 02 2020 11 09 Copyright Huawei Technologies Co Ltd 122 ...

Page 130: ... key to access the device run state submenu screen Figure 6 6 Device run state submenu Step 6 Query all contents under this submenu by pressing the and keys End 6 3 How Do I Check Teamwork State Procedure Step 1 On the home screen press the key to access the menu screen NetCol8000 A013 In room Air Cooled Smart Cooling Product User Manual 600 mm Width 6 FAQ Issue 02 2020 11 09 Copyright Huawei Tech...

Page 131: ...by pressing the or key Figure 6 8 Moving the cursor Step 5 Press the key to access the teamwork state submenu screen Figure 6 9 Teamwork state submenu Step 6 Query all contents under this submenu by pressing the and keys End NetCol8000 A013 In room Air Cooled Smart Cooling Product User Manual 600 mm Width 6 FAQ Issue 02 2020 11 09 Copyright Huawei Technologies Co Ltd 124 ...

Page 132: ... by pressing the or key Step 3 Press the key to access the run submenu screen Figure 6 11 Run submenu Step 4 Move the cursor to Runtime by pressing the or key Step 5 Press the key to access the runtime submenu screen NetCol8000 A013 In room Air Cooled Smart Cooling Product User Manual 600 mm Width 6 FAQ Issue 02 2020 11 09 Copyright Huawei Technologies Co Ltd 125 ...

Page 133: ...e key to access the menu screen 2 On the menu screen move the cursor to Alarm by pressing the or key 3 Press the key to access the alarm submenu screen Figure 6 13 Accessing the alarm submenu NetCol8000 A013 In room Air Cooled Smart Cooling Product User Manual 600 mm Width 6 FAQ Issue 02 2020 11 09 Copyright Huawei Technologies Co Ltd 126 ...

Page 134: ...name and generation time of all active alarms by pressing the or key The alarms are sorted by generation time in descending order NOTE On any screen other than the screen for querying active alarms press the key to access the screen for querying active alarms End NetCol8000 A013 In room Air Cooled Smart Cooling Product User Manual 600 mm Width 6 FAQ Issue 02 2020 11 09 Copyright Huawei Technologie...

Page 135: ... alarms Step 2 Query the name and generation time of all historical alarms by pressing the or key The alarms are sorted by generation time in descending order End 6 6 How Do I Perform User Settings Procedure Step 1 Press the key to access the menu screen NetCol8000 A013 In room Air Cooled Smart Cooling Product User Manual 600 mm Width 6 FAQ Issue 02 2020 11 09 Copyright Huawei Technologies Co Ltd ...

Page 136: ...ess the key to access the screen for entering the password for the user menu Step 4 On the screen for entering the password for the user menu enter the password digits by using the and keys and adjust the position of the digit to be entered by using the and keys Then press the key Figure 6 18 Entering a password NetCol8000 A013 In room Air Cooled Smart Cooling Product User Manual 600 mm Width 6 FA...

Page 137: ...d Step 5 On the user menu screen move the cursor to User Setting by pressing the or key Then press the key to access the user setting submenu screen Step 6 Set parameters for the user setting submenu by pressing the and keys Figure 6 21 User settings End NetCol8000 A013 In room Air Cooled Smart Cooling Product User Manual 600 mm Width 6 FAQ Issue 02 2020 11 09 Copyright Huawei Technologies Co Ltd ...

Page 138: ...en move the cursor to User Menu by pressing the or key Then press the key to access the screen for entering the password for the user menu Step 4 On the screen for entering the password for the user menu enter the password digits by using the and keys and adjust the position of the digit to be entered by using the and keys Then press the key NetCol8000 A013 In room Air Cooled Smart Cooling Product...

Page 139: ...orrect the user menu screen is displayed Figure 6 26 Correct password Step 5 On the user menu screen move the cursor to Password Setting by pressing the or key Then press the key to access the password setting screen NetCol8000 A013 In room Air Cooled Smart Cooling Product User Manual 600 mm Width 6 FAQ Issue 02 2020 11 09 Copyright Huawei Technologies Co Ltd 132 ...

Page 140: ...8 Password setting Figure 6 29 Confirming the new password End 6 8 How Do I Set Alarm Parameters Procedure Step 1 Press the key to access the menu screen NetCol8000 A013 In room Air Cooled Smart Cooling Product User Manual 600 mm Width 6 FAQ Issue 02 2020 11 09 Copyright Huawei Technologies Co Ltd 133 ...

Page 141: ...key to access the screen for entering the password for the administrator menu Step 4 On the screen for entering the password for the administrator menu enter the password digits by using the and keys and adjust the position of the digit to be entered by using the and keys Then press the key Figure 6 32 Entering a password NetCol8000 A013 In room Air Cooled Smart Cooling Product User Manual 600 mm ...

Page 142: ... Figure 6 34 Correct password Step 5 On the administrator menu screen move the cursor to Alarm Setting by pressing the or key Then press the key to access the alarm setting submenu screen Figure 6 35 Accessing the alarm setting submenu NetCol8000 A013 In room Air Cooled Smart Cooling Product User Manual 600 mm Width 6 FAQ Issue 02 2020 11 09 Copyright Huawei Technologies Co Ltd 135 ...

Page 143: ...re 6 36 Temperature and humidity sensor Access the Compressor submenu screen and set parameters for the compressor by pressing the and keys Figure 6 37 Compressor Access the Delete Historical Alarms submenu screen and confirm whether to delete all historical alarms by pressing the and NetCol8000 A013 In room Air Cooled Smart Cooling Product User Manual 600 mm Width 6 FAQ Issue 02 2020 11 09 Copyri...

Page 144: ...9 How Do I Restore Default Settings Procedure Step 1 Press the key to access the menu screen Figure 6 39 Menu screen Step 2 Move the cursor to Setting by pressing the or key Then press the key to access the setting submenu screen NetCol8000 A013 In room Air Cooled Smart Cooling Product User Manual 600 mm Width 6 FAQ Issue 02 2020 11 09 Copyright Huawei Technologies Co Ltd 137 ...

Page 145: ...e password digits by using the and keys and adjust the position of the digit to be entered by using the and keys Then press the key Figure 6 41 Entering a password If the password is incorrect the message Wrong Password Enter Again is displayed Figure 6 42 Incorrect password If the password is correct the administrator menu screen is displayed NetCol8000 A013 In room Air Cooled Smart Cooling Produ...

Page 146: ...ord to access the screen for confirming restoration of default settings Choose Yes or No by pressing the or key If you choose Yes all configurable parameters will be restored to default settings If you choose No the previous menu will be displayed Press the key to confirm the operation Figure 6 45 Restoring default settings End NetCol8000 A013 In room Air Cooled Smart Cooling Product User Manual 6...

Page 147: ...move the cursor to Admin Menu by pressing the or key Then press the key to access the screen for entering the password for the administrator menu Step 4 On the screen for entering the password for the administrator menu enter the password digits by using the and keys and adjust the position of the digit to be entered by using the and keys Then press the key NetCol8000 A013 In room Air Cooled Smart...

Page 148: ...e administrator menu screen is displayed Figure 6 50 Correct password Step 5 On the administrator menu screen move the cursor to Password Setting by pressing the or key Then press the key to access the password setting screen NetCol8000 A013 In room Air Cooled Smart Cooling Product User Manual 600 mm Width 6 FAQ Issue 02 2020 11 09 Copyright Huawei Technologies Co Ltd 141 ...

Page 149: ... The level of the administrator password is higher than that of the user password The administrator password can be used to log in to the user menu but the user password cannot be used to log in to the administrator menu End NetCol8000 A013 In room Air Cooled Smart Cooling Product User Manual 600 mm Width 6 FAQ Issue 02 2020 11 09 Copyright Huawei Technologies Co Ltd 142 ...

Page 150: ...u Step 3 On the screen for entering the password for the maintenance menu enter the password digits by using the and keys and adjust the position of the digit to be entered by using the and keys Then press the key Figure 6 55 Entering a password If the password is incorrect the message Wrong Password Enter Again is displayed NetCol8000 A013 In room Air Cooled Smart Cooling Product User Manual 600 ...

Page 151: ...ess the key to access the performance maintenance submenu screen Figure 6 58 Performance maintenance Step 5 Clear the total runtime of each device by pressing the and keys NOTE The first maintenance time is The last maintenance time is displayed only after the total runtime is cleared End NetCol8000 A013 In room Air Cooled Smart Cooling Product User Manual 600 mm Width 6 FAQ Issue 02 2020 11 09 Co...

Page 152: ... 3 On the screen for entering the password for the maintenance menu enter the password digits by using the and keys and adjust the position of the digit to be entered by using the and keys Then press the key Figure 6 60 Entering a password If the password is incorrect the message Wrong Password Enter Again is displayed NetCol8000 A013 In room Air Cooled Smart Cooling Product User Manual 600 mm Wid...

Page 153: ...the cursor to Sensor Calibration by pressing the or key Then press the key to access the sensor calibration submenu screen Figure 6 63 Sensor calibration Step 5 Set sensor calibration parameters by pressing the and keys End NetCol8000 A013 In room Air Cooled Smart Cooling Product User Manual 600 mm Width 6 FAQ Issue 02 2020 11 09 Copyright Huawei Technologies Co Ltd 146 ...

Page 154: ...p 2 Move the cursor to Maintain by pressing the or key Then press the key to access the screen for entering the password for the maintenance menu Step 3 On the screen for entering the password for the maintenance menu enter the password digits by using the and keys and adjust the position of the digit to be entered by using the and keys Then press the key Figure 6 65 Entering a password NetCol8000...

Page 155: ...ce menu move the cursor to USB Wizard by pressing the or key Then press the key to access the USB wizard submenu screen Figure 6 68 USB wizard Step 5 On the USB wizard menu move the cursor to Version Upgrade by pressing the or key Then press the key to access the version upgrade screen NetCol8000 A013 In room Air Cooled Smart Cooling Product User Manual 600 mm Width 6 FAQ Issue 02 2020 11 09 Copyr...

Page 156: ...B flash drive the system starts upgrading the indoor unit program and the upgrade progress bar is displayed After the upgrade is complete Upgrade Done is displayed If the indoor unit upgrade program in the USB flash drive is consistent with the running program version of the indoor unit No Need Upgrade is displayed If no USB flash drive is inserted U Disk No Detect is displayed 15 seconds after yo...

Page 157: ...p 1 Press the key to access the menu screen Figure 6 70 Menu screen Step 2 Move the cursor to Maintain by pressing the or key Then press the key to access the screen for entering the password for the maintenance menu Step 3 On the screen for entering the password for the maintenance menu enter the password digits by using the and keys and adjust the position of the digit to be entered by using the...

Page 158: ...rrect the maintenance menu screen is displayed Figure 6 73 Correct password Step 4 On the maintenance menu move the cursor to USB Wizard by pressing the or key Then press the key to access the USB wizard submenu screen NetCol8000 A013 In room Air Cooled Smart Cooling Product User Manual 600 mm Width 6 FAQ Issue 02 2020 11 09 Copyright Huawei Technologies Co Ltd 151 ...

Page 159: ...6 75 Export Step 6 On the USB wizard menu move the cursor to Config Import by pressing the or key and press the key to perform the operation After the import is complete Import Done is displayed in the lower part of the screen If no USB flash drive is inserted U Disk No Detect is displayed 15 seconds after you press the key If the USB flash drive inserted does not contain the configuration file AC...

Page 160: ... access the screen for entering the password for the maintenance menu Step 3 On the screen for entering the password for the maintenance menu enter the password digits by using the and keys and adjust the position of the digit to be entered by using the and keys Then press the key NetCol8000 A013 In room Air Cooled Smart Cooling Product User Manual 600 mm Width 6 FAQ Issue 02 2020 11 09 Copyright ...

Page 161: ...nce menu screen is displayed Figure 6 80 Correct password Step 4 On the maintenance menu move the cursor to Password Setting by pressing the or key Then press the key to access the password setting screen Figure 6 81 Entering a password NetCol8000 A013 In room Air Cooled Smart Cooling Product User Manual 600 mm Width 6 FAQ Issue 02 2020 11 09 Copyright Huawei Technologies Co Ltd 154 ...

Page 162: ... administrator password and maintenance password are at the same level End 6 16 How Do I View the Current Versions Procedure Step 1 Press the key to access the menu screen Figure 6 84 Menu screen NetCol8000 A013 In room Air Cooled Smart Cooling Product User Manual 600 mm Width 6 FAQ Issue 02 2020 11 09 Copyright Huawei Technologies Co Ltd 155 ...

Page 163: ...ursor by pressing the or key and press the key Then you can view the e label of the current model as well as the current version of the display panel indoor unit and outdoor unit Figure 6 85 About End NetCol8000 A013 In room Air Cooled Smart Cooling Product User Manual 600 mm Width 6 FAQ Issue 02 2020 11 09 Copyright Huawei Technologies Co Ltd 156 ...

Page 164: ...op valve 11 Indoor unit liquid pipe stop valve 12 Strainer 13 Electronic expansion valve 14 Evaporator coils temperature sensor 15 Evaporator 16 Indoor unit gas pipe stop valve 17 Outdoor unit gas pipe stop valve 18 Suction temperature sensor 19 Low pressure sensor 20 Gas liquid separator 21 Low pressure switch NetCol8000 A013 In room Air Cooled Smart Cooling Product User Manual 600 mm Width A Coo...

Page 165: ...se of an indoor unit unit mm Figure B 2 Base of an outdoor unit unit mm NetCol8000 A013 In room Air Cooled Smart Cooling Product User Manual 600 mm Width B Base Dimensions Issue 02 2020 11 09 Copyright Huawei Technologies Co Ltd 158 ...

Page 166: ...or channel steel Width of 50 mm and thickness of 4 to 5 mm are recommended 3 Control the welding process and avoid excessive error NetCol8000 A013 In room Air Cooled Smart Cooling Product User Manual 600 mm Width B Base Dimensions Issue 02 2020 11 09 Copyright Huawei Technologies Co Ltd 159 ...

Page 167: ... for wall mounting brackets unit mm 1 Wall 2 Outdoor unit 3 Guardrail 4 Support NetCol8000 A013 In room Air Cooled Smart Cooling Product User Manual 600 mm Width C Bracket Drawings Issue 02 2020 11 09 Copyright Huawei Technologies Co Ltd 160 ...

Page 168: ...s need to fasten the safety belt during the maintenance Do not lean against the protection railing on three sides of the support Figure C 2 Drawings 2 for wall mounting brackets unit mm NOTE Select the 50 mm x 50 mm x 5 mm stainless angle steel NetCol8000 A013 In room Air Cooled Smart Cooling Product User Manual 600 mm Width C Bracket Drawings Issue 02 2020 11 09 Copyright Huawei Technologies Co L...

Page 169: ...ectrical Conceptual Diagrams NetCol8000 A013 In room Air Cooled Smart Cooling Product User Manual 600 mm Width D Electrical Conceptual Diagrams Issue 02 2020 11 09 Copyright Huawei Technologies Co Ltd 162 ...

Page 170: ... 1 Indoor unit electrical diagram NetCol8000 A013 In room Air Cooled Smart Cooling Product User Manual 600 mm Width D Electrical Conceptual Diagrams Issue 02 2020 11 09 Copyright Huawei Technologies Co Ltd 163 ...

Page 171: ... 2 Outdoor unit electrical diagram NetCol8000 A013 In room Air Cooled Smart Cooling Product User Manual 600 mm Width D Electrical Conceptual Diagrams Issue 02 2020 11 09 Copyright Huawei Technologies Co Ltd 164 ...

Page 172: ...p Curve Humidity Curve Run Device Run State Compressor EEV Indoor Fan Outdoor Fan1 Suction Pressure Suction Temp EEV Suct Superheat Discharge Pressure Discharge Temp EEV Discharge Superheat Compressor Phase Cur Outdoor Temp NetCol8000 A013 In room Air Cooled Smart Cooling Product User Manual 600 mm Width E Controller Menu Issue 02 2020 11 09 Copyright Huawei Technologies Co Ltd 165 ...

Page 173: ...egree Remote Off Compressor Heat Tape State HP Switch LP Switch Water Inlet Solenoid Valve Humidifier Water Pump Electric Heater Low Liquid Detect High Liquid Detect Run Teamwork State Current State M S Unit State Unit Address Rotation Mode High Temp Start All Low Temp Start All NetCol8000 A013 In room Air Cooled Smart Cooling Product User Manual 600 mm Width E Controller Menu Issue 02 2020 11 09 ...

Page 174: ...work Setting Teamwork Function Disable Enable Disable Unit Address or 1 1 to 32 Enable Teamwork Resistor or No Yes No Units in Group Hide or 1 1 to 32 Active Units in Group Hide or 1 1 to 32 Rotation Function Hide or Disable Enable Disable Rotation Type Hide or Address Address Hour Rotation Cycle Hide or 1D 1D to 30D Rotation Time Hide or 00 00 24 hours High Temp Start All Hide or Disable Enable D...

Page 175: ... No Setting User Menu Password Setting 000001 Six digit number Setting Admin Menu Alarm Setting Temp Humid Sensor Return Air HT Alarm Enable Enable Disable Return Air HT Thres 32 0 C 25 C to 40 0 C Return Air LT Alarm Enable Enable Disable Return Air LT Thres 12 0 C 5 C to 24 0 C High Humid Alarm Enable Enable Disable High Humid Thres 85 0 RH 65 0 RH to 95 0 RH Low Humid Alarm Enable Enable Disabl...

Page 176: ...Freq Thres 47 Hz 47 Hz to 49 Hz Air Filter RT out Alarm Enable Enable Disable Air Filter RT out Alarm 4320 h 2160 h to 6480 h Smoke Sensor Alarm Enable Enable Disable Floor Water Alarm Enable Enable Disable Fire Alarm Enable Enable Disable Setting Admin Menu Alarm Setting Electric Heater Run Time out Alarm Enable Enable Disable Run Time out Thres 30000 h 20000 h to 40000 h Setting Admin Menu Alarm...

Page 177: ...50 Dehum Comp Off Demand 50 0 to 100 Setting Admin Menu System Setting Temp Humid Sensor Max Temp Set 32 0 18 C to 35 C Min Temp Set 18 0 18 C to 35 C Max Humid Set 90 0 RH 20 0 RH to 100 0 RH Min Humid Set 30 0 RH 20 0 RH to 70 0 RH Temp P band 3 0 C 0 5 C to 20 0 C Temp Deadzone 1 0 C 0 1 C to 20 0 C Dehum P band 5 0 1 0 to 90 0 Dehum Dead zone 1 0 0 5 to 90 0 Humid P band 5 0 1 0 to 90 0 Humid ...

Page 178: ...Stop Vacuum Pressure 0 48 MPa 0 to 1 5 MPa Comp Preheating On The default value is On for the first startup and the value is Off after preheatin g is complete On Off Dis HT Rise Limit Temp 97 0 C 90 C to 115 C Dis HT Drop Temp 107 0 C 90 C to 115 C Setting Admin Menu System Setting Indoor Fan Min Speed 30 30 to 100 Max Speed 100 30 to 100 NetCol8000 A013 In room Air Cooled Smart Cooling Product Us...

Page 179: ...00 40 to 100 Min Run Pressure 2 10 MPa 1 0 MPa to 3 5 MPa Start Pressure 2 26 MPa 1 0 MPa to 3 5 MPa Max Run Pressure 2 80 MPa 2 5 MPa to 4 0 MPa Setting Admin Menu System Setting EEV Min Open 52 step 0 to 480 step Max Open 480 step 0 to 480 step Standby Open 300 step Min Open to Max Open Suct Super Heat Set point 6 0 C 2 0 C to 20 0 C Suct Super Heat Dead zone 2 0 C 0 to 5 0 C Adjust Cycle 10s 5s...

Page 180: ...x Open Low Press Ini Open 150 step Min Open to Max Open Medium Press Ini Open 120 step Min Open to Max Open High Press Ini Open 120 step Min Open to Max Open NetCol8000 A013 In room Air Cooled Smart Cooling Product User Manual 600 mm Width E Controller Menu Issue 02 2020 11 09 Copyright Huawei Technologies Co Ltd 173 ...

Page 181: ...ic expansion valve L LCD liquid crystal display P PTC positive temperature coefficient R RCCB residual current circuit breaker U USB Universal Serial Bus NetCol8000 A013 In room Air Cooled Smart Cooling Product User Manual 600 mm Width F Acronyms and Abbreviations Issue 02 2020 11 09 Copyright Huawei Technologies Co Ltd 174 ...