If connected to a CCU collector, the two monitoring cables should connect to the GATA
port or one of the IN0 to IN4 ports.
If connected to an ECC collector, the RJ45 connector of the network cable to the AI/DI
port of the ECC collector.
----End
10.12.13 Connecting a Monitoring Cable for the SD-09A-HWA
Current-Type Smoke Sensor
Prerequisites
A monitoring cable required is prepared.
You are familiar with the functions of all ports on the CCU collector by referring to
10.12.2 Port Description for the CCU Collector
You are familiar with the functions of all ports on the ECC collector by referring to
10.12.3 Port Description for the ECC Collector
Context
Before connecting an SD-09A-HWA current type smoke sensor and the ECC collector, you
need to perform the following steps to prepare a special monitoring cable.
Procedure
Step 1
Connect the monitoring cable to the collector.
If connected to a CCU collector, the monitoring cable should be connected by
performing the following steps.
a.
Install the converter delivered with the smoke sensor on the smoke sensor.
b.
Connect the cord end terminal on one end of the monitoring cable to the converter
on the smoke sensor.
c.
Connect the cord end terminal on the other end of the monitoring cable to the dry
contact wiring terminal on the CCU collector.
If connected to an ECC collector, the monitoring cable should be connected by
performing the following steps.
a.
Prepare an RJ45 connector on one end of the network cable by following to the
instruction in
10.12.1 Preparing a Monitoring Cable
b.
Short-circuit core wires 1, 5, and 8 on the other end of the network cable.
c.
Use core wires 3 and 6 of the cable as two cord end terminals.
d.
Install the converter delivered with the smoke sensor on the smoke sensor.
e.
Connect the two cord end terminals to the converter on the smoke sensor, regardless
of polarities.
f.
Connect one end of the RJ45 network cable to the AI/DI port on the ECC collector.
----End