IDS2000 Dual-Row Aisle Containment
Installation Guide (Split-type Skylight, Old-Version
Sliding Door)
10 Cable Layout
Issue 02 (2015-06-30)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
215
Device cables not mentioned in the document do not need to be connected onsite and should
be insulated only.
----End
10.12.12 Connecting a Monitoring Cable to a Door Status Sensor
Prerequisites
A required monitoring cable is prepared.
You are familiar with the functions of all ports on the CCU collector by referring to
10.12.2 Port Description for the CCU Collector
You are familiar with the functions of all ports on the ECC collector by referring to
10.12.3 Port Description for the ECC Collector
Context
When connecting the door status sensor to an ECC collector, you need to perform the
following steps to prepare a special monitoring cable.
Procedure
Step 1
Disassemble the door status sensor and connect a cable to it.
1.
Prepare an RJ45 connector on one end of the network cable by following the instruction
in
10.12.1 Preparing a Monitoring Cable
2.
Prepare cord end terminals on the sixth core wire (green) and seventh core wire
(brown-and-white) at the other end of the network cable, and then put the two terminals
under the door status sensor washer, as shown in
Figure 10-53
Connecting a monitoring cable to a door status sensor
Step 2
Install a door status sensor in a reverse order of
Step 3
Connect a monitoring cable to the collector.