IDS2000 Dual-Row Aisle Containment
Installation Guide (Split-type Skylight, Old-Version
Sliding Door)
10 Cable Layout
Issue 02 (2015-06-30)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
186
Component
Configuration
Configuration Number
of IDC (25 mm
2
), IDC
special
Figure 10-38
Conceptual diagram of battery cable connections
Configuration 14
Configuration 14 applies to the following scenarios:
12 kW < actual total power ≤ 24 kW; backup time: 30 minutes
24 kW < actual total power ≤ 36 kW; backup time: 15 minutes
36 kW < actual total power ≤ 48 kW; backup time: 15 minutes
The following table describes battery cabinet configuration.
Table 10-15
Battery cabinet configuration 14
Component
Configuration
Configuration Number
Battery
Rechargeable Battery 288
V-100 Ah Battery
A string of 24 batteries
Battery tray
Battery tray for 4 batteries
6 PCS
Circuit breaker
Circuit breaker, 690 V AC,
250 A, 3P, 36 kA/415 V
AC, 105