IDS2000 Dual-Row Aisle Containment
Installation Guide (Split-type Skylight, Old-Version
Sliding Door)
10 Cable Layout
Issue 02 (2015-06-30)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
226
You are familiar with the functions of all ports on the ECC collector by referring to
10.12.3 Port Description for the ECC Collector
Procedure
Step 1
Connect the monitoring cable to the collector.
If connected to a CCU collector, the monitoring cable should be connected by
performing the following steps.
a.
Cut off the crystal connector on the monitoring cable for the electronic door lock.
describes the core wires of the electronic door lock.
Table 10-62
Core wires of the electronic door lock
Color
Function
Red
Positive power terminal
Black
Negative power terminal
Blue
RS485+
Green
RS485-
Cut off the crystal connector from as near the connector as possible.
b.
Cut off one end of the network cable.
c.
Connect the core wires of the electronic door lock to the network core wires by
sequence specified in
Table 10-63
Matches by core wire colors
Electronic Door Lock
Network cable
Red
Green and white
Black
Brown
Blue
Orange-white, and blue
Green
Orange, and blue-white
d.
Connect the other end of the network cable to the RS485 port on the CCU collector.
If connected to an ECC collector, connect the RJ45 connector of the electronic door lock
cable to the RS485 port on the ECC collector.
----End