IDS2000 Dual-Row Aisle Containment
Installation Guide (Split-type Skylight, Old-Version
Sliding Door)
10 Cable Layout
Issue 02 (2015-06-30)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
212
Port
Function
Remarks
is reported over dry
contacts.
report low level alarms over
a dry contact.
LINK IN
Connects to other associated
skylight controllers,
controlling the opening of
the skylight.
Cascading port. This port
connects to no cable by
default. To connect multiple
skylight controllers to the
fire extinguishing system in
cascading mode, connect the
LINK IN port to the LINK
OUT port of next skylight
controller. Configuration on
the NetEco is not required.
LINK OUT
Connects to other associated
skylight controllers,
controlling the opening of
the skylight.
Cascading port. This port
connects to no cable by
default. To connect multiple
skylight controllers to the
fire extinguishing system in
cascading mode, connect the
LINK OUT port to the
LINK IN port of next
skylight controller.
Configuration on the
NetEco is not required.
describes the skylight controller DIP switch. Ensure that the two toggle switches
are both NO or NC.
Table 10-52
Skylight controller DIP switch
Position
Function
Scenario Example
NO
The toggle switches are both
NO by default. Set both
toggle switches to NO if you
need to open the skylight
after the skylight lock is
energized.
For a skylight lock with a
bolt, the 1 (+ –) to 14 (+ –)
ports of the skylight
controller do not supply
power to the bolt under
normal conditions. After
you press the skylight open
button or start remote open,
the 1 (+ –) to 14 (+ –) ports
supply power to the bolt.
Then the bolt draws in and
the skylight opens.
NC
Set both toggle switches to
NC if you need to open the
skylight after the skylight
lock is de-energized.
Take a skylight magnetic
lock for example. Normally,
the 1 (+ –) to 14 (+ –) ports
of the skylight controller
supply power to the
magnetic lock. After you
press the skylight open