IDS2000 Dual-Row Aisle Containment
Installation Guide (Split-type Skylight, Old-Version
Sliding Door)
10 Cable Layout
Issue 02 (2015-06-30)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
219
Table 10-57
Connecting humidity and temperature sensors in series
Port on the Ambient Temperature and
Humidity Sensor 1
Connect to Humidity and Temperature
Sensor 2 Port
+
+
A
A
B
B
-
-
Step 4
After installing the ambient temperature and humidity sensor, connect the RJ45 connector of
the monitoring cable to the RS485 port on ECC collector that supplies 12 V power to the
RS485 port.
----End
10.12.16 Connecting a Cable to the WLDS900 Water Sensor
Prerequisites
A monitoring cable required has been prepared.
You are familiar with the functions of all ports on the CCU collector by referring to
10.12.2 Port Description for the CCU Collector
You are familiar with the functions of all ports on the ECC collector by referring to
10.12.3 Port Description for the ECC Collector
Context
When connecting the water sensor and the CCU collector, you need to perform the following
steps to prepare a special monitoring cable.
Procedure
Step 1
Connect a monitoring cable to the collector.
If connected to a CCU, the monitoring cable should be connected by performing the
following steps:
a.
Prepare an RJ45 connector on one end of the network cable by following the
instructions in
10.12.1 Preparing a Monitoring Cable
to the Ethernet port on the water sensor.
b.
Prepare cord end terminals for core wires 3, 6, 7, and 8 on the other end of the
network cable and connect them to the ALM_IN port on the CCU collector, as
described in
Table 10-58
Connecting a cable to the water sensor
Wiring Terminal in the ALM_IN Port
Core Wire in the Cord End Terminal
12V
Core wire 3 (green-white)