IDS2000 Dual-Row Aisle Containment
Installation Guide (Split-type Skylight, Old-Version
Sliding Door)
2 Installing Cabinets
Issue 02 (2015-06-30)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
12
When positioning a NetCol5000-C, ensure that its front frame is aligned with that of the adjacent
cabinet.
If a double-swing door is installed, check that the doorheads are 1200 mm away from each other.
Step 3
Mark the position of the other array cabinet.
Step 4
Use the PDU8000 as the reference and place cabinets one by one according to the engineering
layout drawing.
Use the PVC pipe for the control skylight (BOM number: 21500918 or 21500944) to check the aisle
width.
If the aisle width is not 1200 mm, adjust the cabinet positions to ensure a 1200 mm wide aisle.
The distance checked by the PVC pipe is the distance between the two front doors of the cabinets on
both sides of the aisle.
Do not throw away the PVC pipe after use. You need to use it when installing skylights.
Figure 2-9
Checking the aisle width (unit: mm)
----End
2.3 Installing Adaptive Frames
2.3.1 Overview of Adaptive Frames
provides information about adaptive frames.
Table 2-1
Adaptive frames
Adaptive Frame
BOM No.
Description
NetCol5000-C enclosure
frame
21500710
Configured if the number of
NetCol5000-Cs is odd. The
item is used to increase the