IDS2000 Dual-Row Aisle Containment
Installation Guide (Split-type Skylight, Old-Version
Sliding Door)
A Appendix
Issue 02 (2015-06-30)
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
262
Figure A-13
Adjusting the screws
A.4 (Optional) Connecting Linkage Cables Between the
Gas Extinguishing Controller and ATS
Context
After linkage cables are connected between the gas extinguishing controller and ATS, the ATS
disconnects non-fire power supply and stops supplying power to precision air conditioners in
the data center when the gas extinguishing controller generates a fire signal.
Linkage cables can be connected between the gas extinguishing controller and ATS in the
following two ways:
Link the fire alarm bell and ATS. When the fire alarm bell rings, the ATS is triggered to
disconnect non-fire power supply.
Link the audible and visual alarm and ATS. When an alarm occurs on the audible and
visual alarm device, the ATS is triggered to disconnect non-fire power supply.
This section describes how to connect linkage cables between the JB-QBL-QM200 gas
extinguishing controller and ATS.
Procedure
Connect linkage cables between the drive output ports for the fire alarm bell on the gas
extinguishing controller and the non-fire power disconnection ports on the ATS, as
shown in