Configuration 16
Configuration 16 applies to the scenario where the actual total power is greater than 24 kW
but no greater than 36 kW, and the backup time is 30 minutes. The following table describes
battery cabinet configuration.
Table 10-17
Battery cabinet configuration 16
Component
Configuration
Configuration Number
Battery
Rechargeable Battery 288
V-150 Ah Battery
A string of 24 batteries
Battery tray
Battery tray for 4 batteries
12 PCS
Circuit breaker
Circuit breaker, 690 V AC,
250 A, 3P, 36 kA/415 V
AC, 105
(W)*150(D)*102(H)
1 PCS
Battery cable
Battery Accessory, SD-288
V 150 Ah/12 V-PX-35
(OT), Battery Cabinet
Installation, 600 mm
(W)*1100 mm (D)*2000
mm (H), Top out, Cables for
battery group SHOTO
6-GFM-150 embedded in
battery cabinet of IDC (35
mm
2
), IDC special
1 PCS
Figure 10-41
Conceptual diagram of battery cable connections