Circuit Breaker
The marked electrical for the server is 7.2 amps. The recommended circuit breaker size is 12 amps per line
cord (2 maximum) for North America. For countries outside North America, consult the local electrical
authority that has jurisdiction for the recommended circuit breaker size.
System Power Specifications
Available power (output) is the maximum dc power that the power supply can supply to the system.
Maximum input power is what the power supply requires from the ac line to deliver the maximum dc output
(given worst case efficiency and max loading).
Maximum input current is the worst case or highest current given the lowest input voltage and the maximum
input power.
Table 2-4 lists the system power specifications.
If an overload triggers the power supply overload protection, the system is immediately powered off. To reset
the power supply unit, follow these steps:
1. Disconnect the power cord.
2. Determine what caused the overload by contacting a HP support representative.
3. Reconnect the power cord, then reboot the system.
If an overload occurs twice, there is an undetected short circuit somewhere.
When you use the front panel’s power button to power off the server, power consumption falls below the low
power consumption, but doesn’t reach zero. To reach zero power consumption in “off ” mode, either unplug the
server or use a power block with a switch.
Table 2-4
System Power Specifications
Parameter
Total Rating
Peak
(15 sec)
Max. per PCI-X Sockets
64-bit, 133 MHz
Input voltage
100 – 240 VAC
Off
Off
Input current (max)
7.2A at 115 VAC or
3.6A at 220 VAC
Off
Off
Input frequency
50 to 60 Hz
Off
Off
Measured input power
560W
Off
Off
Available power (output)
650W
Off
85W total for PCI sockets
Maximum current at +12V
49A
0.5A
Off
Maximum current at –12V
0.35A
Off
0.1A
Maximum current at +3.3V
34A
Off
4.6A
Maximum current at +5V
18A
31A
3A
Maximum current at +3.3V
standby
3.5A
Off
Off
Summary of Contents for 9000 rp3410
Page 8: ...Contents 8 ...
Page 128: ...Installing the System Troubleshooting Chapter 3 128 ...
Page 130: ...Installing the System Troubleshooting Chapter 3 130 ...
Page 146: ...Chapter 5 Troubleshooting Cleaning Procedures 146 ...
Page 240: ...Appendix A Replacement Parts Replaceable Parts List 240 ...
Page 248: ...Appendix B Utilities iLO MP 248 ...
Page 250: ...Physical and Environmental Specifications Appendix C 250 ...