Function Parameter Reference Guide
12/00
UDC2300 Controller Product Manual
131
12.2.29 DI
COM
(DIGITAL INPUT COMBINATIONS)
This prompt is part of the Options Set Up Group
There are five selections available for combination with any digital input selection.
Selections
Definitions
DIS
DISABLE-Disables combination function.
+PD2
Any Digital Input Selection PLUS PID2-Contact closure selects PID Set 2.
+DIR
Any Digital Input Selection PLUS DIRECT ACTION – Contact closure
selects direct controller action.
+SP2
Any Digital Input Selection PLUS SETPOINT 2 – Contact closure puts the
controller into setpoint 2.
+SP1
Any Digital Input Selection PLUS SETPOINT 1 – Contact closure puts the
controller into setpoint 1.
+RUN
Any Digital Input Selection PLUS RUN SETPOINT PROGRAM/RAMP –
Contact closure starts SP Program/Ramp if enabled.
12.2.30 DIG
IN
(DIGITAL INPUT)
This prompt is part of the Options Set Up Group
This selection allows remote selection of various parameters.
Selections
Definitions
NONE
NO DIGITAL INPUT SELECTIONS
MAN
TO MANUAL – Contact closure puts the affected loop into manual mode.
Contact open returns controller to former mode.
LSP
TO LOCAL SETPOINT – When a remote setpoint is configured, contact
closure puts the controller into local setpoint 1. When contact opens, the
controller returns to former operation – local or remote setpoint – unless
SETPOINT SELECT
key is pressed while digital input is active. If this
happens, the controller will stay in the local setpoint mode when contact
opens.
SP2
TO LOCAL SETPOINT TWO - Contact closure puts the controller into
local setpoint 2.
DIR
TO DIRECT ACTION - Contact closure selects direct controller action.
HOLD
TO HOLD – Contact closure suspends Setpoint Program or Setpoint Ramp.
When contact reopens, the controller starts from the Hold point of the
Ramp/Program unless the Ramp/Program was not previously started via the
RUN/HOLD
key.
This selection applies to either loop.
PID2
TO PID2 – Contact closure selects PID Set 2.
Summary of Contents for UDC 2300
Page 1: ...UDC2300 Universal Digital Controller Product Manual 51 52 25 98 12 00 ...
Page 30: ...Installation 20 UDC2300 Controller Product Manual 12 00 ...
Page 62: ...Monitoring 52 UDC2300 Controller Product Manual 12 00 ...
Page 80: ...Operation 70 UDC2300 Controller Product Manual 12 00 ...
Page 92: ...Setpoint Rate Ramp Program Operation 82 UDC2300 Controller Product Manual 12 00 ...
Page 124: ...Troubleshooting Service 114 UDC2300 Controller Product Manual 12 00 ...
Page 170: ...Function Parameter Reference Guide 160 UDC2300 Controller Product Manual 12 00 ...
Page 176: ...Index 166 UDC2300 Controller Product Manual 12 00 ...
Page 177: ......
Page 178: ......
Page 180: ......
Page 181: ......
Page 182: ......
Page 183: ......
Page 184: ......