Troubleshooting/Service
112
UDC2300 Controller Product Manual
12/00
Procedure #5
Table 10-9 explains how to troubleshoot Alarm Relay Output failure.
Table 10-9 Troubleshooting Alarm Relay Output Failure
Step
What to do
How to do it
1
Check the alarm configuration
data. If it is correct, check the
field wiring.
Reconfigure if necessary.
Refer to Section 4 - Configuration for
details.
2
Check that the applicable alarm
relay actuates properly
depending on what you have set
at prompt AxSxTYPE.
If it does, check the field wiring.
If the alarm type is set for PV, place the
controller in manual mode. Vary the input
to raise and lower the PV around the
setpoint. Listen for a click from the relay
as the PV moves in either direction and
note that the proper ALM1 or ALM2 is lit.
EXAMPLE: If the alarm is set for MAN,
put the controller into manual mode. The
alarm light is ON. Put the controller into
automatic mode and the alarm light is
OFF.
3
Check the contacts.
Make sure the NO or NC contact wiring is
correct.
Refer to Section 2 - Installation for relay
jumper placement and relay contact
information.
4
Change Main board.
Installation instructions supplied with new
board.
Summary of Contents for UDC 2300
Page 1: ...UDC2300 Universal Digital Controller Product Manual 51 52 25 98 12 00 ...
Page 30: ...Installation 20 UDC2300 Controller Product Manual 12 00 ...
Page 62: ...Monitoring 52 UDC2300 Controller Product Manual 12 00 ...
Page 80: ...Operation 70 UDC2300 Controller Product Manual 12 00 ...
Page 92: ...Setpoint Rate Ramp Program Operation 82 UDC2300 Controller Product Manual 12 00 ...
Page 124: ...Troubleshooting Service 114 UDC2300 Controller Product Manual 12 00 ...
Page 170: ...Function Parameter Reference Guide 160 UDC2300 Controller Product Manual 12 00 ...
Page 176: ...Index 166 UDC2300 Controller Product Manual 12 00 ...
Page 177: ......
Page 178: ......
Page 180: ......
Page 181: ......
Page 182: ......
Page 183: ......
Page 184: ......