Function Parameter Reference Guide
12/00
UDC2300 Controller Product Manual
139
12.2.50 IN2
HI
(INPUT 2 HIGH RANGE VALUE)
This prompt is part of the Input2 Set up group.
This selection lets you the Input2 high range value in engineering units.
Linear or Square Root Inputs only.
Scale the #2 input signal to the display value you want for 100 %.
EXAMPLE:
Actuation (Input) = 4 to 20 mA
Process Variable = Flow
Range of Flow = 0 to 250 Gal/Min
High Range display value = 250
Then 20 mA = 250 Gal/Min
The control setpoint will be limited by the range of units selected here.
Range of Setting: -999 to 9999 (floating) in Engineering Units
12.2.51 IN2
LO
(INPUT 2 LOW RANGE VALUE)
This prompt is part of the Input2 Set up group.
This selection lets you the Input 2 Low range value in engineering units.
Linear or Square Root Inputs only.
Scale the #2 input signal to the display value you want for 0 %.
EXAMPLE:
Actuation (Input) = 4 to 20 mA
Process Variable = Flow
Range of Flow = 0 to 250 Gal/Min
Low Range display value = 0
Then 4 mA = 0 Gal/Min
The control setpoint will be limited by the range of units selected here.
Range of Setting: -999 to 9999 (floating) in Engineering Units
Summary of Contents for UDC 2300
Page 1: ...UDC2300 Universal Digital Controller Product Manual 51 52 25 98 12 00 ...
Page 30: ...Installation 20 UDC2300 Controller Product Manual 12 00 ...
Page 62: ...Monitoring 52 UDC2300 Controller Product Manual 12 00 ...
Page 80: ...Operation 70 UDC2300 Controller Product Manual 12 00 ...
Page 92: ...Setpoint Rate Ramp Program Operation 82 UDC2300 Controller Product Manual 12 00 ...
Page 124: ...Troubleshooting Service 114 UDC2300 Controller Product Manual 12 00 ...
Page 170: ...Function Parameter Reference Guide 160 UDC2300 Controller Product Manual 12 00 ...
Page 176: ...Index 166 UDC2300 Controller Product Manual 12 00 ...
Page 177: ......
Page 178: ......
Page 180: ......
Page 181: ......
Page 182: ......
Page 183: ......
Page 184: ......