Installation
18
UDC2300 Controller Product Manual
12/00
13
14
+
_
Auxiliary
Load
0 - 500
Ω
Connect shield
to ground at one
end only.
1
1 AuxOut , Digital Input and Communications are mutually exclusive.
Auxiliary Output
13
14
+
_
Contact
Input
Switch
Connect shield
to ground at one
end only.
Digital Inputs 1
1
13
14
D–
D+
COMMUNICATION MASTER
(A)
(RTN)
(B)
D+
SHLD
D–
120 OHMS
TO OTHER
COMMUNICATION
CONTROLLERS
D+
D–
120 OHMS ON LAST LEG
Connect shield wires together with
supplied crimp part number 30755381-001
1
2
Do not run these lines in the same conduit
as AC power.
1
2
Communications
Figure 2-16 External Interface Option Connections
Summary of Contents for UDC 2300
Page 1: ...UDC2300 Universal Digital Controller Product Manual 51 52 25 98 12 00 ...
Page 30: ...Installation 20 UDC2300 Controller Product Manual 12 00 ...
Page 62: ...Monitoring 52 UDC2300 Controller Product Manual 12 00 ...
Page 80: ...Operation 70 UDC2300 Controller Product Manual 12 00 ...
Page 92: ...Setpoint Rate Ramp Program Operation 82 UDC2300 Controller Product Manual 12 00 ...
Page 124: ...Troubleshooting Service 114 UDC2300 Controller Product Manual 12 00 ...
Page 170: ...Function Parameter Reference Guide 160 UDC2300 Controller Product Manual 12 00 ...
Page 176: ...Index 166 UDC2300 Controller Product Manual 12 00 ...
Page 177: ......
Page 178: ......
Page 180: ......
Page 181: ......
Page 182: ......
Page 183: ......
Page 184: ......