12.2.18 BLOCK
(ALARM BLOCKING)
This prompt is part of the Alarms Set up group.
Prevent nuisance alarms when the controller is first powered up. The alarm is suppressed
until the parameter gets to the non-alarm limit or band. Alarm blocking affects both alarm
setpoints.
ATTENTION
When enabled on power up or initial enabling via configuration, the alarm will not activate unless
it has not been in alarm for one cycle (167 ms).
Selections
Definitions
DIS
Disable Blocking
BK1
Blocks Alarm 1 only
BK2
Blocks Alarm 2 only
BK12
Blocks Alarm 1 and Alarm 2
12.2.19 BRNOUT
(BURNOUT PROTECTION - SENSOR BREAK)
This prompt is part of the Input 1 Set up group.
BURNOUT PROTECTION (SENSOR BREAK) provides most input types with upscale
or downscale protection if the input fails. 1-5V, 0-10V, or 4-20 mA inputs require no
burnout or NONE selection.
Selections
Definitions
NONE
NO BURNOUT—Pre-configured Failsafe output applied if failed input is
detected (does not apply for an input out of range). Error message IN 1 FAIL
is flashed on the lower display intermittently every 10 seconds.
UP
UPSCALE BURNOUT —will make the PV signal increase to full scale,
+10 %, when a sensor fails, and flash IN 1 FAIL on the lower display
intermittently every 10 seconds.
The controller remains in Automatic control mode and adjusts the controller
output signal in response to the full scale PV signal developed by the
Burnout circuitry.
DOWN
DOWNSCALE BURNOUT —will make the PV signal decrease to the
lower range value, -10 %, when a sensor fails, and flash INPUT 1 FAIL on
the lower display intermittently every 10 seconds.
The controller remains in Automatic control mode and adjusts the controller
output signal in response to the zero percent PV signal developed by the
Burnout circuitry.
NOFS
NO FAILSAFE —This selection does not provide input failure detection
and should only be used when an absolute accuracy is the most important
criteria. (For this selection, no burnout signal went to the sensor.)
Summary of Contents for UDC 2300
Page 1: ...UDC2300 Universal Digital Controller Product Manual 51 52 25 98 12 00 ...
Page 30: ...Installation 20 UDC2300 Controller Product Manual 12 00 ...
Page 62: ...Monitoring 52 UDC2300 Controller Product Manual 12 00 ...
Page 80: ...Operation 70 UDC2300 Controller Product Manual 12 00 ...
Page 92: ...Setpoint Rate Ramp Program Operation 82 UDC2300 Controller Product Manual 12 00 ...
Page 124: ...Troubleshooting Service 114 UDC2300 Controller Product Manual 12 00 ...
Page 170: ...Function Parameter Reference Guide 160 UDC2300 Controller Product Manual 12 00 ...
Page 176: ...Index 166 UDC2300 Controller Product Manual 12 00 ...
Page 177: ......
Page 178: ......
Page 180: ......
Page 181: ......
Page 182: ......
Page 183: ......
Page 184: ......