Setpoint Rate/Ramp/Program Operation
80
UDC2300 Controller Product Manual
12/00
Run/Monitor the program
Prior to running the program, make sure all the “SP PROG” function prompts under the
Set Up group “SP RAMP” have been configured with the required data.
“HOLD” appears periodically in the upper display indicating that the program is in the
HOLD state.
ATTENTION
SP Programmer parameter cannot be changed during RUN state (must be
in HOLD state).
Run/Monitor functions
Table 7-3 lists all the functions required to run and monitor the program.
Table 7-3 Run/Monitor Functions
Function
Press
Result
Set the Local
Setpoint
DISPLAY
Upper Display = PV value
Lower Display = SP
or
To set the Local Setpoint value to where you
want the program to start out.
Run State
RUN/HOLD
Initiates the setpoint program.
“RUN” appears in the upper display indicating
that the program is running.
Hold State
RUN/HOLD
Holds the setpoint program.
“HOLD” appears in the upper display indicating
that the program is in the HOLD state.
The setpoint holds at the current setpoint.
External Hold
If Remote Switching (Digital Input Option) is
present on your controller, contact closure
places the controller in the HOLD state, if the
setpoint program is running.
The “HOLD” in the upper display will be
displayed periodically in lower case.
ATTENTION The keyboard takes priority
over the external switch for the RUN/HOLD
function.
Contact reopening runs program.
Viewing the present
ramp or soak
segment number
and time
DISPLAY
until you see
Upper Display = PV value
Lower Display = XXHH.MM
Time remaining in the SEGMENT in hours and
minutes. XX = 1 to 12
continued
Summary of Contents for UDC 2300
Page 1: ...UDC2300 Universal Digital Controller Product Manual 51 52 25 98 12 00 ...
Page 30: ...Installation 20 UDC2300 Controller Product Manual 12 00 ...
Page 62: ...Monitoring 52 UDC2300 Controller Product Manual 12 00 ...
Page 80: ...Operation 70 UDC2300 Controller Product Manual 12 00 ...
Page 92: ...Setpoint Rate Ramp Program Operation 82 UDC2300 Controller Product Manual 12 00 ...
Page 124: ...Troubleshooting Service 114 UDC2300 Controller Product Manual 12 00 ...
Page 170: ...Function Parameter Reference Guide 160 UDC2300 Controller Product Manual 12 00 ...
Page 176: ...Index 166 UDC2300 Controller Product Manual 12 00 ...
Page 177: ......
Page 178: ......
Page 180: ......
Page 181: ......
Page 182: ......
Page 183: ......
Page 184: ......