Installation
12/00
UDC2300 Controller Product Manual
17
9
10
5+
4-
Control Relay #2
Motor
Power
Supply
Close (CCW)
Open (CW)
Control
Relay #1
24864
Alarm #2 is not available with Three Position Step Control.
1
2 amp Fast Blo
1
See Figure 2-15 for Alarm and Duplex Output Connections.
Figure 2-14 Three Position Step Control Connections
9
10
11
12
1
2
Load
Supply
Power
Control or Alarm
Relay #2 Load
Alarm
Relay #1 Load
Load
Supply
Power
5 amp fast Blo
5 amp Fast Blo
24867
Control relays 1 and 2 are configured N.O. as shipped. Alarm relays 1
and 2 are configured N.C. as shipped. N.O. or N.C. configurations are
selectable by jumpers on main printed wiring boards. See “Preliminary
Checks” in this sections of the Product Manual for details. Each SPST
relay is rated at 5 A, 120 Vac and 24 Vdc, 2.5 A, 240 Vac.
Alarm #2 not available for Time Proportional Duplex or Three Position
Step Control.
1
1
2
Figure 2-15 Alarm and Duplex Output Connections
Summary of Contents for UDC 2300
Page 1: ...UDC2300 Universal Digital Controller Product Manual 51 52 25 98 12 00 ...
Page 30: ...Installation 20 UDC2300 Controller Product Manual 12 00 ...
Page 62: ...Monitoring 52 UDC2300 Controller Product Manual 12 00 ...
Page 80: ...Operation 70 UDC2300 Controller Product Manual 12 00 ...
Page 92: ...Setpoint Rate Ramp Program Operation 82 UDC2300 Controller Product Manual 12 00 ...
Page 124: ...Troubleshooting Service 114 UDC2300 Controller Product Manual 12 00 ...
Page 170: ...Function Parameter Reference Guide 160 UDC2300 Controller Product Manual 12 00 ...
Page 176: ...Index 166 UDC2300 Controller Product Manual 12 00 ...
Page 177: ......
Page 178: ......
Page 180: ......
Page 181: ......
Page 182: ......
Page 183: ......
Page 184: ......