Operation
12/00
UDC2300 Controller Product Manual
57
6.4 Control Modes
ATTENTION
After changing a Local Setpoint value, if no other key is pressed, it then takes a minimum of thirty (30)
seconds elapsed time before the new value is stored in non-volatile memory. If controller power is
removed before this time, the new setpoint value is lost and the previous setpoint value is used at
power-up. If, after changing the LSP value, another key is pressed, then the value is stored immediately.
6.4.1 Mode Definitions
Table 6-3 Control Mode Definitions
Control Mode
Definition
AUTOMATIC with
LOCAL
SETPOINT
In automatic local mode, the controller operates from the local setpoints and
automatically adjusts the output to maintain the PV at the desired value.
In this mode you can adjust the setpoint.
See Subsection 6.5 - Setpoints.
AUTOMATIC with
REMOTE
SETPOINT
In automatic remote mode, the controller operates from the setpoint measured at the
remote setpoint input. Adjustments are available to ratio this input and add a
constant bias before it is applied to the control equation.
See Subsection 4.9 or 4.10, Input 1 or Input 2.
MANUAL
In the manual mode, the operator directly controls the controller output level. The
process variable and the percent output are displayed. The configured High and Low
Output Limits are disregarded and the operator can change the output value, using
the increment and decrement keys, to the limits allowed by the output type (0 % to
100 % for a time proportioning output or –5 % to 105 % for a current output).
Manual not available with Single Display model.
Summary of Contents for UDC 2300
Page 1: ...UDC2300 Universal Digital Controller Product Manual 51 52 25 98 12 00 ...
Page 30: ...Installation 20 UDC2300 Controller Product Manual 12 00 ...
Page 62: ...Monitoring 52 UDC2300 Controller Product Manual 12 00 ...
Page 80: ...Operation 70 UDC2300 Controller Product Manual 12 00 ...
Page 92: ...Setpoint Rate Ramp Program Operation 82 UDC2300 Controller Product Manual 12 00 ...
Page 124: ...Troubleshooting Service 114 UDC2300 Controller Product Manual 12 00 ...
Page 170: ...Function Parameter Reference Guide 160 UDC2300 Controller Product Manual 12 00 ...
Page 176: ...Index 166 UDC2300 Controller Product Manual 12 00 ...