Function Parameter Reference Guide
12/00
UDC2300 Controller Product Manual
129
“corrected” each time the controller drives the motor to one of its stops (0 %
or 100 %). It avoids all the control problems associated with the feedback
slidewire (wear, dirt, noise). When operating in this algorithm, the estimated
“OUT” display is shown to the nearest percent (that is, no decimal).
Other prompts affected: D BAND
12.2.24 CSRATO
(COMPUTER SETPOINT RATIO)
This prompt is part of the Communications Set up group.
RATIO—Computer setpoint ratio
Range of Setting: -20.0 to 20.0
12.2.25
CYC T1 or CT1 X3
(CYCLE TIME - HEAT)
This prompt is part of the Tuning Set up group.
CYCLE TIME (HEAT) determines the length of one time proportional output relay cycle.
Defined as “HEAT” Cycle time for Heat/Cool applications.
CYC TI—Electromechanical relays (seconds)
CTIX3—Solid state relays (1/3 seconds)
Cycle times are in either second or 1/3-second increments depending upon the
configuration of RLY TY in the Output Algorithm Set Up group.
Range of Setting: 1 to 120
ATTENTION
If 1/3 second increments are used, 1 = .33 seconds and 120 = 40 seconds.
Summary of Contents for UDC 2300
Page 1: ...UDC2300 Universal Digital Controller Product Manual 51 52 25 98 12 00 ...
Page 30: ...Installation 20 UDC2300 Controller Product Manual 12 00 ...
Page 62: ...Monitoring 52 UDC2300 Controller Product Manual 12 00 ...
Page 80: ...Operation 70 UDC2300 Controller Product Manual 12 00 ...
Page 92: ...Setpoint Rate Ramp Program Operation 82 UDC2300 Controller Product Manual 12 00 ...
Page 124: ...Troubleshooting Service 114 UDC2300 Controller Product Manual 12 00 ...
Page 170: ...Function Parameter Reference Guide 160 UDC2300 Controller Product Manual 12 00 ...
Page 176: ...Index 166 UDC2300 Controller Product Manual 12 00 ...
Page 177: ......
Page 178: ......
Page 180: ......
Page 181: ......
Page 182: ......
Page 183: ......
Page 184: ......