Function Parameter Reference Guide
12/00
UDC2300 Controller Product Manual
155
12.2.96 SP
SEL
(SETPOINT SELECT FUNCTION LOCKOUT)
This prompt is part of the Tuning Set up group.
This selection allows you to disable/enable the Setpoint Select function.
“LOCK” must be set to “NONE”.
Selections
Definitions
DIS
Disables the Setpoint Select Function.
ENAB
Enables the Setpoint Select Function.
12.2.97 SP
TRK
(SETPOINT TRACKING)
This prompt is part of the Control Set up group.
The local setpoint can be configured to track either PV or RSP as listed below.
ATTENTION
For selections other than NONE, LSP is stored in nonvolatile memory only when there is a mode change;
i.e., when switching from RSP to LSP or from Manual to Automatic. If power is lost, then the current LSP
value is also lost.
Selections
Definitions
NONE
NO TRACKING—If local setpoint tracking is not configured, the LSP will
not be altered when transfer from RSP to LSP is made.
PV
PROCESS VARIABLE—Local setpoint tracks the PV when in manual.
RSP
REMOTE SETPOINT—Local setpoint tracks remote setpoint when in
automatic. When the controller transfers out of remote setpoint, the last
value of the remote setpoint (RSP) is inserted into the local setpoint.
12.2.98 START
(TIMER START SELECTION)
This prompt is part of the Timer Set up group. This selection allows you to select
whether the Timer starts with the keyboard
RUN/HOLD
key or Alarm 2.
Selections
Definitions
KEY
Starts with
RUN/HOLD
key.
AL2
Starts on Alarm 2.
12.2.99 STATE
(PROGRAM STATE AT PROGRAM END)
This prompt is part of the Setpoint Ramp/Program Set up group.
The program state selection determines the program state after completion.
Selections
Definitions
DIS
Program disabled at program end.
HOLD
Program held at program end.
Summary of Contents for UDC 2300
Page 1: ...UDC2300 Universal Digital Controller Product Manual 51 52 25 98 12 00 ...
Page 30: ...Installation 20 UDC2300 Controller Product Manual 12 00 ...
Page 62: ...Monitoring 52 UDC2300 Controller Product Manual 12 00 ...
Page 80: ...Operation 70 UDC2300 Controller Product Manual 12 00 ...
Page 92: ...Setpoint Rate Ramp Program Operation 82 UDC2300 Controller Product Manual 12 00 ...
Page 124: ...Troubleshooting Service 114 UDC2300 Controller Product Manual 12 00 ...
Page 170: ...Function Parameter Reference Guide 160 UDC2300 Controller Product Manual 12 00 ...
Page 176: ...Index 166 UDC2300 Controller Product Manual 12 00 ...
Page 177: ......
Page 178: ......
Page 180: ......
Page 181: ......
Page 182: ......
Page 183: ......
Page 184: ......