4.6 SP Ramp Set Up Group
Introduction
A single setpoint ramp [SPRAMP] can be configured to occur between the current local
setpoint and a final local setpoint over a time interval of from 1 to 255 minutes.
SPRATE lets you configure a specific rate of change for any local setpoint change.
You can also configure a 12-segment program from a Ramp/Soak profile.
You can start and stop the ramp/program using the
RUN/HOLD
key.
PV Hot Start is standard and means that at power up, the setpoint is set to the current PV
value and the Ramp or Rate or Program then starts from this value.
Function Prompts
Table 4-5 SPRAMP Group (Numeric Code 300) Function Prompts
Prompt
Selection or Range of Setting
English
Numeric
Code
Description
Numeric
Code
English
Factory
Setting
Reference
Guide
Page
SP RAMP
301
Single Setpoint
Ramp
0
1
DIS
ENAB
Rate and Program must
be disabled
DIS
154
TI MIN
302
Single Setpoint
Ramp Time
0 to 255 minutes
3
156
FINLSP
303
Setpoint Ramp
Final Setpoint
Enter a value within the
setpoint limits
1000
134
SPRATE
304
Setpoint Rate
0
1
DIS
ENAB
Ramp and Program must
be disabled
DIS
154
EUHRUP
305
Rate Up
0 to 9999 in Engineering
units per hour
0
133
EUHRDN
306
Rate Down
0 to 9999 in Engineering
units per hour
0
133
SPPROG
307
Setpoint
Ramp/Soak
Programming
0
1
DIS
ENAB
Rate and Ramp must be
disabled
DIS
154
STRSEG
308
Start Segment
Number
1 to 11
- - -
156
ENDSEG
309
End Segment
Number
2
4
6
8
10
12
2 to 12 (always end in a
soak segment 2, 4, … 12)
SOK 2
SOK 4
SOK 6
SOK 8
SOK 10
SOK 12
- - -
133
Summary of Contents for UDC 2300
Page 1: ...UDC2300 Universal Digital Controller Product Manual 51 52 25 98 12 00 ...
Page 30: ...Installation 20 UDC2300 Controller Product Manual 12 00 ...
Page 62: ...Monitoring 52 UDC2300 Controller Product Manual 12 00 ...
Page 80: ...Operation 70 UDC2300 Controller Product Manual 12 00 ...
Page 92: ...Setpoint Rate Ramp Program Operation 82 UDC2300 Controller Product Manual 12 00 ...
Page 124: ...Troubleshooting Service 114 UDC2300 Controller Product Manual 12 00 ...
Page 170: ...Function Parameter Reference Guide 160 UDC2300 Controller Product Manual 12 00 ...
Page 176: ...Index 166 UDC2300 Controller Product Manual 12 00 ...
Page 177: ......
Page 178: ......
Page 180: ......
Page 181: ......
Page 182: ......
Page 183: ......
Page 184: ......