Function Parameter Reference Guide
124
UDC2300 Controller Product Manual
12/00
12.2.13 AxSxTY
(ALARMx SETPOINTx TYPE - X = 1 OR 2)
This prompt is part of the Alarms Set up group.
Select what you want Setpoint x of Alarm x to represent. It can represent the Process
Variable, Deviation, Input 1, Input 2, Output, Remote Setpoint, PV rate of Change, Loop
Break, or Failsafe, and if you have a model with communications, you can configure the
controller to alarm on SHED. If you have setpoint programming, you can alarm when a
segment goes ON or OFF.
Selections
Definitions
NONE
Disables the alarms.
IN 1
Input 1
IN 2
Input 2
PV
Process Variable
DE
Deviation
OUT
Output (note 1)
SHED
Shed from Communications
EVON
Event ON (Setpoint Programmer)
EVOF
Event OFF (Setpoint Programmer)
MAN
Alarm on Manual mode (note 2)
RSP
Remote Setpoint
FSAF
Failsafe
PVRT
PV Rate of Change
DI
Alarm on Digital Input
DE II
Deviation Alarm based on deviation from 2
nd
Local Setpoint or Remote SP
regardless of which SP is active.
BRAK
Loop Break (note 3)
NOTE 1 When the controller is configured for Three Position Step Control, alarms set for Output
will not function.
NOTE 2 Not available if Timer is enabled because Alarm 1 is dedicated to Timer output.
NOTE 3 When enabled, the control output is checked for minimum and maximum limits. When
this occurs, a timer begins and, if the output has not caused the PV to be corrected by a
pre-determined amount and time, the alarm activates. For loop break alarms, the timer
value may be changed only for controllers configured for On-Off control.
Summary of Contents for UDC 2300
Page 1: ...UDC2300 Universal Digital Controller Product Manual 51 52 25 98 12 00 ...
Page 30: ...Installation 20 UDC2300 Controller Product Manual 12 00 ...
Page 62: ...Monitoring 52 UDC2300 Controller Product Manual 12 00 ...
Page 80: ...Operation 70 UDC2300 Controller Product Manual 12 00 ...
Page 92: ...Setpoint Rate Ramp Program Operation 82 UDC2300 Controller Product Manual 12 00 ...
Page 124: ...Troubleshooting Service 114 UDC2300 Controller Product Manual 12 00 ...
Page 170: ...Function Parameter Reference Guide 160 UDC2300 Controller Product Manual 12 00 ...
Page 176: ...Index 166 UDC2300 Controller Product Manual 12 00 ...
Page 177: ......
Page 178: ......
Page 180: ......
Page 181: ......
Page 182: ......
Page 183: ......
Page 184: ......