Revision 1.0
SMV800 Modbus User's Guide
Page 51
Continued ..
Reverse Flow
ON
OFF
With Reverse flow OFF, flow value will
be zero flow when Flow is negative
(when Differential Pressure is < 0) for
Algorithm Options = Advanced
Algorithms or 1989 Algorithms
With Reverse flow ON, flow value will
be negative when Differential Pressure
is < 0 for Algorithm Options =
Advanced Algorithms
With Reverse flow ON or OFF, flow
value will be 0 when Differential
Pressure is < 0 for Algorithm Options =
ASME 1989 Algorithms
So, if Reverse flow is expected, select
Algorithm Options = Advanced
Algorithms, set Reverse Flow
Calculation parameter: ON
Example:
When Reverse flow is ON, PV4 is
calculated considering the absolute
value of DP (when Differential Pressure
is < 0) and resulting Flwo value will be
negative.
Example When Reverse Flow OFF:
DP = -100 inH20
SP = 14.45 psi.
PV4 (Flow) = 0
Example When Reverse Flow ON:
DP = -100 inH20 (-3.612 psi)
SP = 14.45 psi.
PV4 calculation will consider 100in H20
in calculation.
SP value, SP=SP-DP.
SP = 14.45-(-3.612)=18.062 psi will be
Summary of Contents for SMV800
Page 82: ...Page 70 SMV800 Modbus User s Guide Revision 1 0 ...
Page 95: ...Revision 1 0 SMV800 Modbus User s Guide Page 83 2 5 4 Review ...
Page 99: ...Revision 1 0 SMV800 Modbus User s Guide Page 87 ...
Page 100: ...Page 88 SMV800 Modbus User s Guide Revision 1 0 ...
Page 101: ...Revision 1 0 SMV800 Modbus User s Guide Page 89 ...
Page 102: ...Page 90 SMV800 Modbus User s Guide Revision 1 0 ...
Page 103: ...Revision 1 0 SMV800 Modbus User s Guide Page 91 Maintenance Menu ...
Page 104: ...Page 92 SMV800 Modbus User s Guide Revision 1 0 2 7 1 Advanced Diagnotics Menu ...
Page 105: ...Revision 1 0 SMV800 Modbus User s Guide Page 93 2 7 2 Monitoring Menu ...
Page 112: ...Page 100 SMV800 Modbus User s Guide Revision 1 0 ...
Page 116: ......