Page 20
SMV800 Modbus User's Guide
Revision 1.0
Static Pressure
LRV
The Lower Range Value for the Static
Pressure input (which represents 0%
output) in user selected engineering
units. This value may be configured to
any value within the range SP LTL to
SP UTL.
Static Pressure
URV
The Upper Range Value for the Static
Pressure input (which represents 100%
output) in user selected engineering
units. This value may be configured to
any value within the range SP LTL to
SP UTL.
Static Pressure Damping
Damping value for the Static Pressure
output. Entries may be any value from
0.00 to 32.00 seconds.
Static Pressure URL
The Upper Range Limit for the Static
Pressure input
Static Pressure LRL
The Lower Range Limit for the Static
Pressure input
Static Pressure UTL
The Upper Transducer Limit for the
Static Pressure input
Static Pressure LTL
The Lower Transducer Limit for the
Static Pressure input
Write SP Range Values
SP LRV
SP URV
Write a new Lower Range Value and
Upper Range Value for the Static
Pressure
Sensor Type
Shows type of pressure sensor.
Absolute Pressure Sensor and Gauge
Pressure sensor
Summary of Contents for SMV800
Page 82: ...Page 70 SMV800 Modbus User s Guide Revision 1 0 ...
Page 95: ...Revision 1 0 SMV800 Modbus User s Guide Page 83 2 5 4 Review ...
Page 99: ...Revision 1 0 SMV800 Modbus User s Guide Page 87 ...
Page 100: ...Page 88 SMV800 Modbus User s Guide Revision 1 0 ...
Page 101: ...Revision 1 0 SMV800 Modbus User s Guide Page 89 ...
Page 102: ...Page 90 SMV800 Modbus User s Guide Revision 1 0 ...
Page 103: ...Revision 1 0 SMV800 Modbus User s Guide Page 91 Maintenance Menu ...
Page 104: ...Page 92 SMV800 Modbus User s Guide Revision 1 0 2 7 1 Advanced Diagnotics Menu ...
Page 105: ...Revision 1 0 SMV800 Modbus User s Guide Page 93 2 7 2 Monitoring Menu ...
Page 112: ...Page 100 SMV800 Modbus User s Guide Revision 1 0 ...
Page 116: ......