Page 32
SMV800 Modbus User's Guide
Revision 1.0
Sensor Type
Identify and select the type of sensor that is connected to the transmitter as its input for process
temperature. This will set the appropriate LRL and URL data in the transmitter automatically.
Table 2-6
shows the pre-programmed temperature sensor types and the rated measurement range
limits for a given sensor selection.
Table 2-6: Sensor Types for Process Temperature Input
Input
Type
Maximum Range Limits
RTD
(2,3,4 wire)
° C
° F
Pt254
-200 to 850
-328 to 1562
Pt100
-200 to 850
-328 to 1562
Pt2004
-200 to 850
-328 to 1562
Pt5004
-200 to 850
-328 to 1562
Pt10004
-200 to 500
-328 to 932
Thermocouples
° C
° F
B4
200 to 1820
392 to 3308
E
-200 to 1000
-328 to 1832
J
-200 to 1200
-328 to 2192
K
-200 to 1370
-328 to 2498
N4
-200 to 1300
-328 to 2372
R4
-50 to 1760
-58 to 3200
S4
-50 to 1760
-58 to 3200
T
-250 to 400
-418 to 752
ATTENTION:
Whenever you connect a different sensor as the
transmitter’s input, you must also change the sensor type
configuration to agree. Otherwise, range setting errors may result.
Summary of Contents for SMV800
Page 82: ...Page 70 SMV800 Modbus User s Guide Revision 1 0 ...
Page 95: ...Revision 1 0 SMV800 Modbus User s Guide Page 83 2 5 4 Review ...
Page 99: ...Revision 1 0 SMV800 Modbus User s Guide Page 87 ...
Page 100: ...Page 88 SMV800 Modbus User s Guide Revision 1 0 ...
Page 101: ...Revision 1 0 SMV800 Modbus User s Guide Page 89 ...
Page 102: ...Page 90 SMV800 Modbus User s Guide Revision 1 0 ...
Page 103: ...Revision 1 0 SMV800 Modbus User s Guide Page 91 Maintenance Menu ...
Page 104: ...Page 92 SMV800 Modbus User s Guide Revision 1 0 2 7 1 Advanced Diagnotics Menu ...
Page 105: ...Revision 1 0 SMV800 Modbus User s Guide Page 93 2 7 2 Monitoring Menu ...
Page 112: ...Page 100 SMV800 Modbus User s Guide Revision 1 0 ...
Page 116: ......