Page 120
SMV800 Modbus User's Guide
Revision 1.0
Warning
118
Bit - 8
meter_comm
_timeout
Display communication
failure
Secure Display
connections and recheck.
If problem persists, reset
the device. If the problem
still persists, replace the
Display module.
Bit - 9
meter_nvm
_corrupt
Communication screen
configuration module is
reporting corruption
of the Non-Volatile Memory
data (NVM) related to
display
Power cycle the device. If
the problem is not seen,
verify the parameters for
configuration changes
made. If the problem still
persists then NVM might
be damaged so need to
replace Communication
board.
Bit - 10
Comm VCC
Fault
The voltage supply to the
Communication
Module
processor is outside the
operational range of 2.8 to
3.2volts
Power cycle the device. If
problem persist, Check the
terminal voltage to be
within limits. If problem
continues replace the
Communication module
Bit - 11
Device VCC
Fault
Power Supply failure
Power cycle the device. If
problem persist, Check the
terminal voltage to be
within limits. If still problem
persists, replace the
Terminal block assembly. If
problem continues replace
the Communication module
Bit 12-
15
Unused
NA
NA
Summary of Contents for SMV800
Page 82: ...Page 70 SMV800 Modbus User s Guide Revision 1 0 ...
Page 95: ...Revision 1 0 SMV800 Modbus User s Guide Page 83 2 5 4 Review ...
Page 99: ...Revision 1 0 SMV800 Modbus User s Guide Page 87 ...
Page 100: ...Page 88 SMV800 Modbus User s Guide Revision 1 0 ...
Page 101: ...Revision 1 0 SMV800 Modbus User s Guide Page 89 ...
Page 102: ...Page 90 SMV800 Modbus User s Guide Revision 1 0 ...
Page 103: ...Revision 1 0 SMV800 Modbus User s Guide Page 91 Maintenance Menu ...
Page 104: ...Page 92 SMV800 Modbus User s Guide Revision 1 0 2 7 1 Advanced Diagnotics Menu ...
Page 105: ...Revision 1 0 SMV800 Modbus User s Guide Page 93 2 7 2 Monitoring Menu ...
Page 112: ...Page 100 SMV800 Modbus User s Guide Revision 1 0 ...
Page 116: ......