Page 128
SMV800 Modbus User's Guide
Revision 1.0
3.2.12.
Transmitter register maps
This section contains three register maps for SMV800 Modbus Device. These maps
include Coils, Holding register and Floating point register.
Table 3-8: SMV800 Modbus Coils
Name
Coil
Address
Function
Codes
Description
Access
Type
Soft Reset
1
5
Perform device soft reset
W
Differential Pressure Calib
HiPt
2
5
Perform differential pressure calibration at high point
W
Differential Pressure Calib
LowPt
3
5
Perform differential pressure calibration at low point
W
Static Pressure Calib_HiPt
4
5
Perform static pressure calibration at high point
W
Static Pressure Calib
LowPt
5
5
Perform static pressure calibration at low point
W
Differential Pressure Zero
Correct
6
5
Perform differential pressure zero correct
W
Static Pressure Zero
Correct
7
5
Perform static pressure zero correct
W
Differential Pressure Reset
Correct
8
5
Perform differential pressure reset correct
W
Static Pressure Reset
Correct
9
5
Perform static pressure reset correct
W
Process Temperature
Reset Correct
10
5
Perform process temperature reset corrects
W
Process Temperature
Calib HiPt
11
5
Perform process temperature calibration at high point
W
Process Temperature
Calib LowPt
12
5
Perform process temperature calibration at low point
W
Critical Alarm
49
1
Device critical alarm status
R
Warning Alarm
50
1
Device non-critical alarm status
R
Differential Pressure
Above Upper Limit
54
1
Status of differential pressure above upper limit
R
Differential Pressure
Below Lower Limit
55
1
Status of differential pressure below lower limit
R
Static Pressure Above
Upper Limit
60
1
Status of Static pressure above upper limit
R
Static Pressure Below
Lower Limit
61
1
Status of Static pressure below lower limit
R
Process Temperature
Above Upper Limit
68
1
Status of process temperature above upper limit
R
Process Temperature
Below Lower Limit
69
1
Status of process temperature below lower limit
R
MBT Above Upper Limit
75
1
Status of meter body temperature above Upper limit
R
MBT Below Lower Limit
76
1
Status of meter body temperature below lower limit
R
Sensor Module Failure
79
1
Status of pressure or temperature sensor Module failure
R
Sensor Communication
Failure
81
1
Status of pressure or temperature sensor communication
failure
R
DP Simulation Enabled
88
1
Status of differential pressure simulation enabled
R
SP Simulation Enabled
89
1
Status of static pressure simulation enabled
R
PT Simulation Enabled
93
1
Status of process temperature simulation enabled
R
Flow Simulation Enabled
94
1
Status of flow simulation enabled
R
WP Enabled
95
1
Status of write protect enabled
R
Summary of Contents for SMV800
Page 82: ...Page 70 SMV800 Modbus User s Guide Revision 1 0 ...
Page 95: ...Revision 1 0 SMV800 Modbus User s Guide Page 83 2 5 4 Review ...
Page 99: ...Revision 1 0 SMV800 Modbus User s Guide Page 87 ...
Page 100: ...Page 88 SMV800 Modbus User s Guide Revision 1 0 ...
Page 101: ...Revision 1 0 SMV800 Modbus User s Guide Page 89 ...
Page 102: ...Page 90 SMV800 Modbus User s Guide Revision 1 0 ...
Page 103: ...Revision 1 0 SMV800 Modbus User s Guide Page 91 Maintenance Menu ...
Page 104: ...Page 92 SMV800 Modbus User s Guide Revision 1 0 2 7 1 Advanced Diagnotics Menu ...
Page 105: ...Revision 1 0 SMV800 Modbus User s Guide Page 93 2 7 2 Monitoring Menu ...
Page 112: ...Page 100 SMV800 Modbus User s Guide Revision 1 0 ...
Page 116: ......