Page 34
SMV800 Modbus User's Guide
Revision 1.0
Background
You can set the LRV and URV for PT by either typing in the desired values on the MODBUS-
RTU host
Process Temperature Config tab
or applying the corresponding LRV and URV input
signals directly to the transmitter. The LRV and URV set the desired zero and span points for your
measurement range as shown the example in
Figure 2-2
.
Figure 2-2: RTD Range Configuration
•
The URV changes automatically to compensate for any changes in the LRV and maintain
the present span (URV – LRV). See
Figure 2-3
for an example.
•
If you must change both the LRV and URV, always change the LRV first. However, if the
change in the LRV would cause the URV to exceed the URL, you would have to change
the URV to narrow the span before you could change the LRV
Figure 2-3: Current Range Settings
Damping
Adjust the damping time constant for Process Temperature to reduce the output noise. Default
value of damping is 0.5 seconds. Damping can be configured from 0 to 102 seconds.
Summary of Contents for SMV800
Page 82: ...Page 70 SMV800 Modbus User s Guide Revision 1 0 ...
Page 95: ...Revision 1 0 SMV800 Modbus User s Guide Page 83 2 5 4 Review ...
Page 99: ...Revision 1 0 SMV800 Modbus User s Guide Page 87 ...
Page 100: ...Page 88 SMV800 Modbus User s Guide Revision 1 0 ...
Page 101: ...Revision 1 0 SMV800 Modbus User s Guide Page 89 ...
Page 102: ...Page 90 SMV800 Modbus User s Guide Revision 1 0 ...
Page 103: ...Revision 1 0 SMV800 Modbus User s Guide Page 91 Maintenance Menu ...
Page 104: ...Page 92 SMV800 Modbus User s Guide Revision 1 0 2 7 1 Advanced Diagnotics Menu ...
Page 105: ...Revision 1 0 SMV800 Modbus User s Guide Page 93 2 7 2 Monitoring Menu ...
Page 112: ...Page 100 SMV800 Modbus User s Guide Revision 1 0 ...
Page 116: ......