Page 198
SMV800 Modbus User's Guide
Revision 1.0
Warni
ng
Flow Calculation
Fault
During setup and
configuration of the
flow
algorithm
parameters,
insufficient
configuration
or invalid parameter
values have been
entered
which are causing a
division by zero math
error
in the flow calculation
Carefully review the
flow algorithm
parameter
values that have been
configured. Correct
any errors. When the
flow is showing a
good value and this
status is cleared,
reset the device to
clear any Critical
Status that may have
been generated due
to the bad flow
calculation.
Parameters to check:
For Primary Elements
/ Algorithms other
than Pitot Tube
(Algorithm Option =
ASME 1989
Algorithms) and for
any Elements
(including Average
Pitot Tube, Algorithm
Option = Advanced
Algorithms)
Pipe Diameter D
cannot be equal to
Bore Diameter d
d must be > 0
D must be > 0
d < D
For primary element /
algorithm = Pitot Tube
(applicable to
Algorithm Option =
ASME 1989
Algorithms only)
Pipe Diameter D must
be equal to Bore
Diameter d
alpha_D must be
equal to alpha_d
D = d and alpha_D =
alpha_d
D and d must be > 0
alpha_D and alpha_d
must be > 0
Primary Element =
Wedge
Segment Height H <
D H and D > 0
Viscosity and Density
Coefficeints (as
applicable)
Make sure at least
one of the Viscosity
coefficients > 0
Make sure at least
one of the Density
coefficients > 0
Bit - 5
119
Summary of Contents for SMV800
Page 82: ...Page 70 SMV800 Modbus User s Guide Revision 1 0 ...
Page 95: ...Revision 1 0 SMV800 Modbus User s Guide Page 83 2 5 4 Review ...
Page 99: ...Revision 1 0 SMV800 Modbus User s Guide Page 87 ...
Page 100: ...Page 88 SMV800 Modbus User s Guide Revision 1 0 ...
Page 101: ...Revision 1 0 SMV800 Modbus User s Guide Page 89 ...
Page 102: ...Page 90 SMV800 Modbus User s Guide Revision 1 0 ...
Page 103: ...Revision 1 0 SMV800 Modbus User s Guide Page 91 Maintenance Menu ...
Page 104: ...Page 92 SMV800 Modbus User s Guide Revision 1 0 2 7 1 Advanced Diagnotics Menu ...
Page 105: ...Revision 1 0 SMV800 Modbus User s Guide Page 93 2 7 2 Monitoring Menu ...
Page 112: ...Page 100 SMV800 Modbus User s Guide Revision 1 0 ...
Page 116: ......