Revision 1.0
SMV800 Modbus User's Guide
Page 113
3.2.11.
Diagnostics
The SMV800 Modbus device features several diagnostics status bits that gives
information about the status of the transmitter. A complete listing of the
diagnostics status bits is shown in
Table 3-7
. The status bits can be read as coils, or
holding registers.
Table 3-7: Transmitter Status amd Diagnostic Registers
Category
Modbus
Holding
Register
#
Bit
details
Name of fault
Description
Resolution
Critical
115
Bit - 0
comm_section_f
ailure
This is a roll-up status bit
that is set when any of the
following critical status
conditions are present,
RAM, ROM or program
execution (flow) of
communication module.
Power cycle the device. If
the problem persists after
power cycle then board
might be damaged so need
to replace Communication
module.
Bit -1
comm_section_r
am_corrupt
Communication board
RAM Corruption/
Failure.
Power cycle the device. If
the problem persists after
power cycle, then board
might be damaged so need
to replace Communication
module.
Bit - 2
comm_section_r
om_corrupt
Communication board
ROM Corruption/
Failure.
Power cycle the device. If
the problem persists after
power cycle, then board
might be damaged so need
to replace Communication
module.
Bit - 3
comm_section_f
low_failure
Communication module
firmware Program Flow
Failure. This fault will get
set if any of the critical part
of the code is not executed
after expected duration.
Check the connection
between communication
and meterbody (Housing).
Power cycle the device and
if problem persists replace
the Communication
module.
Bit - 4
configuration_co
rrupt
This is a roll-up status bit
that is set when any of the
following status of register
122/123 are set.
- Common DB Corrupt
- Vital DB Corrupt
- General Config DB
Corrupt
- Totalizer Config DB
Corrupt
- Totalizer Value DB
Corrupt
Power cycle the device. If
the problem is not seen,
verify the parameters for
configuration changes. If
the problem persists then
NVM might be damaged so
need to replace
Communication board.
Summary of Contents for SMV800
Page 82: ...Page 70 SMV800 Modbus User s Guide Revision 1 0 ...
Page 95: ...Revision 1 0 SMV800 Modbus User s Guide Page 83 2 5 4 Review ...
Page 99: ...Revision 1 0 SMV800 Modbus User s Guide Page 87 ...
Page 100: ...Page 88 SMV800 Modbus User s Guide Revision 1 0 ...
Page 101: ...Revision 1 0 SMV800 Modbus User s Guide Page 89 ...
Page 102: ...Page 90 SMV800 Modbus User s Guide Revision 1 0 ...
Page 103: ...Revision 1 0 SMV800 Modbus User s Guide Page 91 Maintenance Menu ...
Page 104: ...Page 92 SMV800 Modbus User s Guide Revision 1 0 2 7 1 Advanced Diagnotics Menu ...
Page 105: ...Revision 1 0 SMV800 Modbus User s Guide Page 93 2 7 2 Monitoring Menu ...
Page 112: ...Page 100 SMV800 Modbus User s Guide Revision 1 0 ...
Page 116: ......