Revision 1.0
SMV800 Modbus User's Guide
Page 201
Information
Sensor input bad
Temperature module
input bad. Input out
of range or may be
open
Use matching sensor
suitable for the
process range. Reset
the device, replace
the Temp Module if
issue persists
Bit - 6
120
Sensor/CJ Bad
Temperature Module
CJ measurement is
bad
Verify that the CJ
sensor within the
Temp sensor module
is not outside of the
operating temp limits
(-40 to 85 degC).
Reset the device,
replace the Temp
Module if issue
persists
Bit - 7
Sensor Input
Failure
Fault is set if
Temperature module
• input failue faulty
sensor,
• out of range
• input open
Replace the faulty
sensor if that is the
reason. Select
suitable sensor type
for the process. Reset
the device, replace
the Temperature
Module if issue
persists
Bit - 8
Low Supply
Temperature module
Supply is Low
Check supply voltage
is within specification.
If all are within
specification, replace
Temperature module
Bit - 9
Summary of Contents for SMV800
Page 82: ...Page 70 SMV800 Modbus User s Guide Revision 1 0 ...
Page 95: ...Revision 1 0 SMV800 Modbus User s Guide Page 83 2 5 4 Review ...
Page 99: ...Revision 1 0 SMV800 Modbus User s Guide Page 87 ...
Page 100: ...Page 88 SMV800 Modbus User s Guide Revision 1 0 ...
Page 101: ...Revision 1 0 SMV800 Modbus User s Guide Page 89 ...
Page 102: ...Page 90 SMV800 Modbus User s Guide Revision 1 0 ...
Page 103: ...Revision 1 0 SMV800 Modbus User s Guide Page 91 Maintenance Menu ...
Page 104: ...Page 92 SMV800 Modbus User s Guide Revision 1 0 2 7 1 Advanced Diagnotics Menu ...
Page 105: ...Revision 1 0 SMV800 Modbus User s Guide Page 93 2 7 2 Monitoring Menu ...
Page 112: ...Page 100 SMV800 Modbus User s Guide Revision 1 0 ...
Page 116: ......