Information
Sensor RAM DB
Failure
Pressure module is
reporting corruption
in the database in the
Random Access
Memory (RAM)
Power cycle the
device. If the problem
persists, replace the
Meter Body
Bit - 4
121
Press No Fact
Calib
Factory Calibration
for the Pressure
module is missing.
Accuracy will be
compromised.
Return the device for
Factory Calibration
Bit - 5
Pressure Module
Unreliable
Communication
Internal
communication
quality between the
Communication
Module and Pressure
Sensor is degrading.
Either the transmitter
is installed in a noisy
environment or
internal
communication
quality between the
Communication
Module and Pressure
Sensor module is
degrading.
Verify the connector
for bent pins.If
cable/connector is not
the problem, replace
the Communication
module.If problem still
persists, replace the
Terminal board.
Bit - 6
Press Sensor
Over
Temperature
The Meter Body
temperature is too
high. Accuracy and
life span may
decrease if it remains
high.
Verify the
environmental
temperature is within
specification. Take
steps to insulate the
Temperature module
from the temperature
source.
Bit - 7
Summary of Contents for SMV800
Page 82: ...Page 70 SMV800 Modbus User s Guide Revision 1 0 ...
Page 95: ...Revision 1 0 SMV800 Modbus User s Guide Page 83 2 5 4 Review ...
Page 99: ...Revision 1 0 SMV800 Modbus User s Guide Page 87 ...
Page 100: ...Page 88 SMV800 Modbus User s Guide Revision 1 0 ...
Page 101: ...Revision 1 0 SMV800 Modbus User s Guide Page 89 ...
Page 102: ...Page 90 SMV800 Modbus User s Guide Revision 1 0 ...
Page 103: ...Revision 1 0 SMV800 Modbus User s Guide Page 91 Maintenance Menu ...
Page 104: ...Page 92 SMV800 Modbus User s Guide Revision 1 0 2 7 1 Advanced Diagnotics Menu ...
Page 105: ...Revision 1 0 SMV800 Modbus User s Guide Page 93 2 7 2 Monitoring Menu ...
Page 112: ...Page 100 SMV800 Modbus User s Guide Revision 1 0 ...
Page 116: ......