Revision 1.0
SMV800 Modbus User's Guide
Page 149
Fluid Type
289
Shows currently selected
fluid Type.This is user
configurable parameter
Note:
Saturated Steam-SP : use
Static Pressure to
calculate the Density for
Saturated steam).
Saturated Steam-PT : use
Process Temperature to
calculate the Density for
Saturated steam)
R/W
uint8
(Byte 0 :-> Bit 0 to 3 )
0 = Gas
1 = Liquid
2 = Steam
3 = Saturated Steam-SP
4 = Saturated Steam-PT
5-15 = Reserved
VCone Y
Method
Shows currently selected
VCone Y Method.This is
user configurable parameter.
(Byte 0 :-> Bit 4 )
0 = Use McCrometer
Method
1 = Use ASME Method
VCone
Simplified
Liquid
Shows currently selected
VCone Simplified Liquid.This
is user configurable
parameter.
(Byte 0 :-> Bit 5 )
0 = Off
1 = ON
Use Wedge
Fixed Flow
Coefficient
Shows currently selected
Use Wedge Fixed Flow
Coefficient.This is user
configurable parameter.
(Byte 0 :-> Bit 6 )
0 = Off
1 = ON
(Byte 0 :-> Bit 7 )
Reserved
Algorithm
Type
290
Shows if the Algorithm is
Advanced Algorithms
type or ASME 1989
Algorithms.
When Algorithm Options is
ON, Algorithm is ASME
1989 Algorithms type. When
OFF, it is Advanced
Algorithms type.
R/W
uint8
0 = Advanced Algorithms
1 = ASME1989 Algorithms
Summary of Contents for SMV800
Page 82: ...Page 70 SMV800 Modbus User s Guide Revision 1 0 ...
Page 95: ...Revision 1 0 SMV800 Modbus User s Guide Page 83 2 5 4 Review ...
Page 99: ...Revision 1 0 SMV800 Modbus User s Guide Page 87 ...
Page 100: ...Page 88 SMV800 Modbus User s Guide Revision 1 0 ...
Page 101: ...Revision 1 0 SMV800 Modbus User s Guide Page 89 ...
Page 102: ...Page 90 SMV800 Modbus User s Guide Revision 1 0 ...
Page 103: ...Revision 1 0 SMV800 Modbus User s Guide Page 91 Maintenance Menu ...
Page 104: ...Page 92 SMV800 Modbus User s Guide Revision 1 0 2 7 1 Advanced Diagnotics Menu ...
Page 105: ...Revision 1 0 SMV800 Modbus User s Guide Page 93 2 7 2 Monitoring Menu ...
Page 112: ...Page 100 SMV800 Modbus User s Guide Revision 1 0 ...
Page 116: ......