E3 Series Installation/Operation Manual
—
P/N 9000-0574:I 11/04/10
63
Cabinets
Installation
2.5.8.4 Cabinet C, E3-INX-C Plate, Installation
1.
Mount the ILI-MB-E3/ILI95-MB-E3/ANX over the standoffs on the E3-INX C plate and
secure with eight (8), standoffs, (3/16
” hex, #4-40 x 1”) in the eight-hole mounting pattern as
shown in Location 1 of Figure 2.5.8.4.2.
2.
Mount the DACT-E3 and the RPT-E3 on top of the ILI-MB-E3/ILI95-MB-E3/ANX and secure
with eight (8), screws (#4-40 x 1/4
”) into the eight (8), standoffs as shown in Location 2 of
Figure 2.5.8.4.2.
3.
Mount the PM-9/PM-9G over the standoffs on the E3-INX-C PLATE plate and secure with six
(6), standoffs (1/4
” hex, #4-40 x 2 1/4”) in the six-hole mounting pattern as shown in Location
3 of Figure 2.5.8.4.2.
4.
Mount the PM-9/PM-9G Adapter Plate on top of the PM-9/PM-9G and secure with six (6),
screws (#4-40 x 1/4
”) into the six (6), standoffs as shown in Location 4 of Figure 2.5.8.4.2.
5.
Mount the INI-VG on the PM-9/PM-9G Adapter Plate and secure with six (6), screws
(#4-40 x 1/4
”) as shown in Location 5 of Figure 2.5.8.4.2.
6.
Mount two (2), AM-50 Series amplifiers on the E3-INX-C plate and secure with eight (8),
standoffs (3/16
” #4-40 x 1 1/4”) in the two (2), four-hole mounting patterns as shown in
Location 6.
7.
Mount two (2), AM-50 Series amplifiers on top of the two (2), AM-50 Series amplifiers, and
secure eight (8), screws (#4-40 x 1/4
”) into the
eight (8), standoffs as shown in Location 7 of
Figure 2.5.8.4.2.
Figure 2.5.8.4.1 Cabinet C, E3-INX C Plate (Standard View)
PM-9/PM-9G
ILI-MB-E3/ILI95-MB-E3/ANX
INI-VG SERIES
DACT-E3
RPT-E3
AM-50 SERIES
AM-50 SERIES
AM-50 SERIES
PCB
AM-50 SERIES
AM-50 SERIES
AM-50 SERI
E
S
PCB