E3 Series Installation/Operation Manual
—
P/N 9000-0574:I 11/04/10
169
Standby Battery Calculations
E3 Series System Connections
3.15 Standby Battery Calculations
To determine the standby battery calculations, refer to Table 3.15.1.
Qty
Module
Description
Supv.
Current
Alarm
Current
Total
Supv.
Current
Total
Alarm
Current
ANX
Addressable Node Expander
0.065 A
0.065 A
ILI-MB-E3
Intelligent Loop Interface, Main Board 0.081 A
0.150 A
ILI95-MB-E3
Intelligent Loop Interface, Main Board-95 0.050 A
0.091 A
ILI-S-E3
Intelligent Loop Interface, Expansion
Board, 95 two additional SLCs
0.118 A
0.119 A
ILI95-S-E3
Intelligent Loop Interface, Expansion
Board, two additional SLCs
0.109 A
0.11 A
LCD-E3
LCD display/Switch Control
0.024 A
0.028 A
RPT-E3
ARCNet Repeater
0.013 A
0.013 A
DACT-E3
Digital Communicator
0.018 A
0.018 A
ASM-16
Auxiliary Switch Sub-Assembly
0.011 A
†
(See Note 4)
0.011 A
†
(See Note 4)
ANU-48
Remote LED Driver
011 A
‡
(
See Note 5)
0.011 A
‡
See Note 5)
PM-9
(See Notes 6 & 7)
Power Supply
0.050 A
0.050 A
PM-9G
(See Notes 6 & 7)
Power Supply
0.027 A
0.050A
LCD-7100
Remote Display Module
0.012 A
0.023 A
NGA
LCD Annunciator
0.200 A
£
(
See Note 3)
0.200 A
£
(
See Note 3)
Smoke and heat sensors
Notification Appliances
Auxiliary Power Devices
Miscellaneous devices
TOTALS
A
Total Supervisory Current (See Note 6)
B
Enter number of standby hours required** (See Note 1)
C
Multiply Line A times hours in Line B
—enter
D
Total alarm current from above
E
Enter alarm sounding period in hours.
F
Multiply Line D times Line E
–enter
G
Total of Lines C & F
—enter
H
Multiply Line G by 1.2 --- enter (Total ampere/hours required***) (See Note 2)
NOTES:
NOTE 1: ** 24 hrs for NFPA 72 protected premises or Central Station signaling, or Auxiliary, or Remote Supervising
Station Fire Alarm Systems.
NOTE 2: *** Use the next size battery with a capacity greater than required. (Use only Gamewell-FCI Models: B-1,
B-7R, B-17R, B-55R, BAT-1270, BAT-12120, BAT-12260, or BAT-12550 batteries). The maximum standby current for
60 hours when using 55 A/H batteries is .560 A. The system batteries must be replaced as a set.
NOTE 3:
£ Normal operating current. During power failure, current
drops to 0.045 amp since back light is extinguished.
NOTE 4:
† Add .003 amp for any LED to be lit
for any condition when powered internally.
NOTE 5:
‡ Add .003 amp for any LED to be lit for any condition when powered internally. When powered externally, a
max. output current of .050/point is available for a maximum total output of 2.4 amp/ANU-48.
NOTE 6: Continuous standby loads in excess of .560 Amps up to 5 Amps may require Generator Backup or load
shedding during an AC power failure.
Note 7: Continuous standby loads in excess of .560 Amps up to 4 Amps may require a Generator Backup or load
shedding during an AC power failure.
Table 3.15.1 Battery Standby Chart