background image

E3 Series Installation/Operation Manual 

 P/N 9000-0574:I  11/04/10

169

Standby Battery Calculations

E3 Series System Connections

3.15  Standby Battery Calculations

To determine the standby battery calculations, refer to Table 3.15.1.

Qty     

Module 

Description 

Supv. 

Current   

Alarm 

Current

Total

Supv.

Current   

Total 

Alarm

Current 

ANX

Addressable Node Expander

0.065 A

0.065 A

ILI-MB-E3 

Intelligent Loop Interface, Main Board       0.081 A 

0.150 A 

ILI95-MB-E3 

Intelligent Loop Interface, Main Board-95 0.050 A

0.091 A

ILI-S-E3 

Intelligent Loop Interface, Expansion   
Board, 95 two additional SLCs  

0.118 A

0.119 A

ILI95-S-E3 

Intelligent Loop Interface, Expansion 
Board, two additional SLCs 

0.109 A

0.11 A

LCD-E3 

LCD display/Switch Control 

0.024 A 

0.028 A 

RPT-E3 

ARCNet Repeater 

0.013 A 

0.013 A 

DACT-E3 

Digital Communicator 

0.018 A 

0.018 A 

ASM-16 

Auxiliary Switch Sub-Assembly 

0.011 A

† 

(See Note 4)

0.011 A

† 

(See Note 4) 

ANU-48 

Remote LED Driver 

011 A

‡ 

(

See Note 5) 

0.011 A

‡ 

See Note 5) 

PM-9

(See Notes 6 & 7)

Power Supply

0.050 A

0.050 A

PM-9G

(See Notes 6 & 7)

Power Supply 

0.027 A 

0.050A 

LCD-7100 

Remote Display Module 

0.012 A 

0.023 A 

NGA 

LCD Annunciator 

0.200 A

£   

(

See Note 3)

 0.200 A

£

(

See Note 3)

Smoke and heat sensors 

Notification Appliances 

Auxiliary Power Devices 

Miscellaneous devices 

TOTALS 

A

Total Supervisory Current (See Note 6)

Enter number of standby hours required** (See Note 1)

Multiply Line A times hours in Line B

—enter 

Total alarm current from above 

Enter alarm sounding period in hours. 

Multiply Line D times Line E 

–enter 

Total of Lines C & F

—enter 

Multiply Line G by 1.2 --- enter (Total ampere/hours required***) (See Note 2)

NOTES:

NOTE 1: ** 24 hrs for NFPA 72 protected premises or Central Station signaling, or Auxiliary, or Remote Supervising 
Station Fire Alarm Systems. 

NOTE 2: *** Use the next size battery with a capacity greater than required. (Use only Gamewell-FCI Models: B-1, 
B-7R, B-17R, B-55R, BAT-1270, BAT-12120, BAT-12260, or BAT-12550 batteries). The maximum standby current for 
60 hours when using 55 A/H batteries is .560 A. The system batteries must be replaced as a set.

NOTE 3: 

£ Normal operating current. During power failure, current

 drops to 0.045 amp since back light is extinguished. 

NOTE 4: 

† Add .003 amp for any LED to be lit 

for any condition when powered internally. 

NOTE 5: 

‡ Add .003 amp for any LED to be lit for any condition when powered internally. When powered externally, a 

max. output current of .050/point is available for a maximum total output of 2.4 amp/ANU-48. 

NOTE 6: Continuous standby loads in excess of .560 Amps up to 5 Amps may require Generator Backup or load 
shedding during an AC power failure. 

Note 7: Continuous standby loads in excess of .560 Amps up to 4 Amps may require a Generator Backup or load 
shedding during an AC power failure.

Table 3.15.1  Battery Standby Chart 

Summary of Contents for Gamewell-FCI E3 Series

Page 1: ...aso Texas 79925 Ph 915 778 6061 Fax 915 778 7046 Fire Alarm and Mass Notification O M Manual TACTICAL EQUIPMENT MAINTENANCE FACILITY TEMF FT BLISS EQUIPMENT MAINTENANCE FACILITIES EMF FORT BLISS TEXAS Gamewell FCI Fire Alarm Mass Notification System ...

Page 2: ...I P N 9000 0574 I ECN 10 116 Document 9000 0574 11 04 10 Rev E3 Series Expandable Emergency Evacuation System Installation Operation Manual ...

Page 3: ...ther type of detector is necessarily best and a given type of detector may not provide adequate warning of a fire Smoke detectors cannot be expected to provide adequate warning of fires caused by arson children playing with matches especially in bedrooms smoking in bed and violent explosions caused by escaping gas improper storage of flammable materials etc Heat detectors do not sense particles of...

Page 4: ...maged when subjected to lightning induced transients Although no system is completely immune from lightning transients and interference proper grounding will reduce susceptibility Overhead or outside aerial wiring is not recommended due to an increased susceptibility to nearby lightning strikes Consult with the Technical Services Department if any problems are anticipated or encountered Disconnect...

Page 5: ...e appropriate version for a specific application Documentation Feedback Your feedback helps us keep out documentation up to date and accurate If you have any comments or suggestions about our online Help or printed manuals you can email us Please include the following information Product name and version number if applicable Printed manual or online Help Topic Title for online Help Page number for...

Page 6: ...LI95 E3 Series 16 1 5 3 Notification Appliance Circuits ILI MB E3 or ILI95 MB E3 17 1 5 4 Alarm Dry Contacts ILI MB E3 or ILI95 MB E3 17 1 5 5 Trouble Dry Contacts ILI MB E3 or ILI95 MB E3 17 1 5 6 Supervisory Dry Contacts ILI MB E3 or ILI95 MB E3 17 1 5 7 Earth Ground Connection ILI MB E3 or ILI95 MB E3 17 1 5 8 24 VDC Power System ILI MB E3 or ILI95 MB E3 17 1 5 9 RS 232 Port 17 1 5 10 Battery C...

Page 7: ...t C E3 INX C Plate Installation Instructions 59 2 5 8 1 Cabinet C Backbox Installation 60 2 5 8 2 Cabinet C Trim Rings Installation Optional Accessory 61 2 5 8 3 Cabinet C E3 INX C Plate Outer Door Installation 62 2 5 8 4 Cabinet C E3 INX C Plate Installation 63 2 5 8 5 Cabinet C E3 INX C Sub Assemblies Plate to the Backbox Installation 65 2 5 9 Cabinet C E3 INCC C Plate Installation Instructions ...

Page 8: ... 111 3 5 3 Intelligent Loop Interface XP95 Slave Wiring Connections 112 3 5 4 ILI95 S E3 Wiring Diagram 113 3 6 ILI E3 and ILI95 E3 Series Programming Address Switch Settings 114 3 7 Addressable Node Expander ANX Connections 115 3 7 1 ANX Specifications 115 3 7 2 Minimum Configuration 115 3 7 3 ANX Wiring Requirements 116 3 7 4 FocalPoint Gateway 3 Wiring 116 3 7 5 License 116 3 7 5 1 From uIP 116...

Page 9: ...ecifications 158 3 12 2 ANU 48 Sub Assembly 159 3 12 3 ANU 48 Wiring Connections 160 3 12 4 ANU 48 Wiring Diagram 161 3 12 5 ANU 48 Programming Address Switch Settings 162 3 13 LCD E3 Panel Display Connections 163 3 13 1 Specifications 163 3 13 2 LCD E3 Sub Assembly 164 3 13 3 LCD E3 Wiring Connections 165 3 13 4 LCD E3 Wiring Diagram 166 3 14 LCD 7100 Remote Display Connections 167 3 14 1 Mountin...

Page 10: ...neral 179 6 2 To Set the System Time 179 6 3 Automatic Configuration 179 Section 7 Test and Maintenance 180 7 1 Test 180 7 2 Maintenance 180 Section 8 Power Limited Non Power Limited Wiring 181 8 1 E3 Series Control Panel Circuit Wiring Requirements 182 8 2 E3 Series Power Limited and Non Power Limited Diagram 183 Index 185 ...

Page 11: ...re Alarm Systems 1 2 Standard Features Two 2 Class A Style 6 7 or Class B Style 4 Signaling Line Circuits Two 2 Class A Style Z or Class B Style Y Notification Appliance Circuits 2 0 amp each Alarm Trouble and Supervisory dry contacts Accommodates 159 Gamewell FCI Approved UL Listed compatible analog sensors per signaling line circuit ILI MB E3 or ILI S E3 only Accommodates 159 Gamewell FCI Approv...

Page 12: ...ouble Acknowledge Signal Silence System Reset Lamp test Programming buttons Menu Back Back Space Edit OK 12 button keypad Figure 1 3 1 1 Switch Control Panel The ILI MB E3 or ILI95 MB E3 can support up to six 6 LCD E3 sub assemblies any or all of which may be remotely located via the local RS 485 serial interface LED Indicators AC Power On green Power Fault yellow Alarm red Ground Fault yellow Sup...

Page 13: ...emblies The units occupy one node on the Broadband network Alarm signals lock in The Supervisory Signals can be either locked in or not locked in depending on the CAMWorks Trouble signals do not lock in The following sensors and modules are used with each unit The ILI95 MB E3 accommodates the Apollo Series of sensors and modules For a comprehensive list refer to the Compatibility Addendum to Gamew...

Page 14: ...The RPT E3 sub assembly provides a remote interface between the ILI MB E3 ILI95 MB E3 and or ANX and the Broadband Network The unit can be used with unshielded twisted pair wire or fiber optic cable as the Model RPT E3 FO The Model RPT E3 UTP is used with only twisted pair 1 4 4 Intelligent Loop Interface Slave Board ILI S E3 These sub assemblies provide two 2 additional signaling line circuits Th...

Page 15: ...Graphic Annunciator NGA The NGA mounts in the E3 Series enclosure or it may be remotely located It provides an LCD display of system events together with system status indicating LEDs and touch screen switches for Alarm Acknowledge Trouble Acknowledge Signal Silence and System Reset The NGA occupies one node on the Broadband network The background display can be programmed to display Command Cente...

Page 16: ...ve up to 50 watts The following describe each AM 50 Series amplifier AM 50 25 The AM 50 25 amplifier is a 50 watt Class D switching type audio output amplifier with a standard voltage for audio output of 25VRMS AM 50 70 The AM 50 70 amplifier is a 50 watt Class D switching audio output amplifier with a standard voltage for audio output of 70 7VRMS The AM 50 Series amplifiers may be installed in an...

Page 17: ...Hz 2 4 amps max Output Voltage 24 VDC FWR 24 VDC FWR Output Current 9 amperes Alarm max continuous 9 amperes Alarm max continuous Output Current 5 amperes max continuous Standby when the PM 9 is used with the ILI E3 or the ILI95 E3 Series See Note 1 5 amperes max continuous Standby when the PM 9G is used with the ILI E3 or the ILI95 E3 Series See Note 1 Output Current 4 amperes max continuous Stan...

Page 18: ...2 0 amp maximum per each circuit 2 5 amp maximum combined Unsupervised Power limited 1 5 9 RS 232 Port The RS 232 port consists of the Terminal Block TB6 which provides a standard serial port for the connection to a Listed output device for a supplementary type service Typical examples of such devices include any UL Listed EDP device remote printer or video terminal any UL Listed Signaling Device ...

Page 19: ...er to the Compatibility Addendum to Gamewell FCI Manuals P N 9000 0427 Section 3 for a list of UL Listed compatible releasing solenoids Voltage 24 VDC Nominal FWR Supervisory Current 0018 amp Alarm Current 510 amp max Box Trip Coil Resistance 14 5 Ohms max Line Resistance 35 Ohms max Supervised against Opens and Grounds Non Power limited Voltage 24 VDC nominal FWR Supervisory Current 012 amp Alarm...

Page 20: ...on field wiring shall be in compliance with local and national codes 2 3 Unpacking and Inspecting Components Remove all sub assemblies and accessories from their shipping cartons to access the enclosure Remove and inspect the enclosure for shipping damage Inspect all electronic sub assemblies for damage without removing them from their anti static protective bags If any pieces are found damaged no...

Page 21: ...t options Cabinets A1 and A2 Cabinet A remote Cabinet B Cabinet C Cabinet D B Slim Cabinet E3 Inner Door Bonding Strap 2 5 1 Cabinet A1 Installation Instructions The E3 Series Cabinet A1 assembly typically includes the following Backbox Cabinet A1 Trim Rings Optional Accessory Outer Door Inner Door unit Hardware Kit Figure 2 5 1 1 Cabinet A1 Standard View NOTE Electrical continuity for grounding o...

Page 22: ... and 2 of the figure below 3 Set the backbox over the top two hole mounting pattern and hang the backbox over the two screw heads 4 Insert and secure two 2 10 screws in the two hole mounting pattern as shown in Locations 3 and 4 of the figure below Figure 2 5 1 1 1 Cabinet A1 Backbox Installation NOTE If the fasteners are anchored to wallboard use 10 wall anchors Mountings to concrete walls should...

Page 23: ...low 5 Insert the Cabinet A1 trim left ring on the left side of the two hole mounting pattern 6 Secure with two 2 6 Hex Kep nuts in the two hole mounting pattern on the left side of the backbox as shown in Locations 5 and 6 of the figure below 7 Insert the Cabinet A1 trim right ring on the right side of the two hole mounting pattern 8 Secure with two 2 6 Hex Kep nuts in the two hole mounting patter...

Page 24: ...tallation 1 Mount the outer door on the backbox 2 Secure with three 3 6 32 nuts in the three hole mounting pattern on the left side of the backbox as shown in Locations 1 2 and 3 of the figure below Figure 2 5 1 3 1 Cabinet A1 Outer Door Installation CABINET A1 BACKBOX CABINET A1 OUTER DOOR NUT HEX 6 32 3 PLACES 3 2 1 3 2 1 ...

Page 25: ...tom hinge pin hole on top of the nylon spacer and secure using the 8 x 5 screw as shown in Location 2 of the figure below 5 After the inner door is secured in place attach the one end of the bonding wire to the top hinge pin using the 8 x 5 screw as shown in Location 3 of the figure below Figure 2 5 1 4 1 Cabinet A1 Inner Door to the Backbox Installation NOTE For information on the installation of...

Page 26: ...e the opposite end of the bonding wire to the welded 6 stud on the inner side of the inner door using the 6 nut as shown in Location 2 of the figure below 3 After the panel is wired use the thumbscrews to secure the inner door to the backbox as shown in Location 3 of the figure below Figure 2 5 1 5 1 Cabinet A1 Inner Door Installation 2 2 1 1 1 1 1 3 3 CABINET A1 INNER DOOR THUMBSCREWS TO SECURE T...

Page 27: ...Installation Cabinets 2 5 2 Cabinet A2 Installation Instructions The E3 Series Cabinet A2 assembly typically includes the following Backbox Cabinet A2 Trim Rings Optional Accessory Outer Door Inner Door LCD E3 Keypad Hardware Kit Figure 2 5 2 1 Cabinet A2 Standard View ...

Page 28: ...nd 2 of the figure below 3 Set the backbox over the top two hole mounting pattern and hang the backbox over the two screw heads 4 Insert and secure two 2 10 screws in the two hole mounting pattern as shown in Locations 3 and 4 of the figure below Figure 2 5 2 1 1 Cabinet A2 Backbox Installation NOTE If the fasteners are anchored to wallboard use 10 wall anchors Mountings to concrete walls should b...

Page 29: ...he two hole mounting pattern 6 Secure with two 2 6 Hex Kep nuts in the two hole mounting pattern on the left side of the backbox as shown in Locations 5 and 6 of the figure below 7 Insert the Cabinet A2 trim right ring on the right side of the two hole mounting pattern 8 Secure with two 2 6 Hex Kep nuts in the two hole mounting pattern on the right side of the backbox as shown in Locations 7 and 8...

Page 30: ...tallation 1 Mount the outer door on the backbox 2 Secure with three 3 6 32 nuts in the three hole mounting pattern on the left side of the backbox as shown in Locations 1 2 and 3 of the figure below Figure 2 5 2 3 1 Cabinet A2 Outer Door Installation CABINET A2 BACKBOX CABINET A2 OUTER DOOR NUT HEX 6 32 3 PLACES 3 2 1 3 2 1 ...

Page 31: ...tom hinge pin hole on top of the nylon spacer and secure using the 8 x 5 screw as shown in Location 2 of the figure below 5 After the inner door is secured in place attach the one end of the bonding wire to the top hinge pin using the 8 x 5 screw as shown in Location 3 of the figure below NOTE For information on the installation of the opposite end of the bonding wire see Section 2 5 2 5 Step 2 Lo...

Page 32: ...the opposite end of the bonding wire to the welded 6 stud on the inner side of the inner door using the 6 nut as shown in Location 2 of the figure below 3 After the panel is wired use the thumbscrews to secure the inner door to the backbox as shown in Location 3 of the figure below Figure 2 5 2 5 1 Cabinet A2 Inner Door Installation BONDING WIRE NUT HEX 6 32 8 PLACES CABINET A2 INNER DOOR LCD E3 K...

Page 33: ...SH LCD CAB A2 Flush Annunciator Installation Instructions The E3BB FLUSH LCD CAB A2 Remote Flush Annunciator assembly typically includes the following Backbox E3BB FLUSH LCD Flush Mount Front Cover LCD E3 Keypad Keyswitch and cable Hardware Kit Figure 2 5 3 1 E3BB FLUSH LCD CAB A2 Remote Flush Annunciator ...

Page 34: ... 1 3 Set the backbox over the top two hole mounting pattern and hang the backbox over the two screw heads 4 Insert and secure two 2 10 screws in the two hole mounting pattern as shown in Locations 3 and 4 of Figure 2 5 3 1 1 Figure 2 5 3 1 1 E3 BB FLUSH LCD CAB A2 Remote Flush Annunciator Backbox Installation NOTE If the fasteners are anchored to wallboard use 10 wall anchors Mountings to concrete...

Page 35: ...he W2 terminal on the LCD E3 display panel as shown in Location 4 of Figure 2 5 3 2 1 For information on the location of the P2 and W2 terminal on the LCD E3 panel refer to Note 1 on the LCD E3 Wiring Diagram in Figure 3 13 4 1 of Section 3 14 4 5 To connect the LCD E3 panel wiring on TB1 refer to TB1 in Figure 3 13 4 1 LCD E3 Wiring Diagram in Section 3 14 4 6 Attach the E3BB FLUSH LCD Flush Moun...

Page 36: ...kbox Cabinet A Trim Rings Optional Accessory Outer Door Inner Door 2 Bay One 1 LCD E3 unit One 1 ASM 16 unit One 1 Blank Plate Optional Hardware Kit Figure 2 5 4 1 Cabinet A or AA 2 Bay Standard View NOTE Cabinet AA may be used with the 2 Bay and 3 Bay outer door A microphone can be installed as an optional accessory in the blank plate For information on the Cabinet A or Cabinet AA installation re...

Page 37: ...two hole mounting pattern as shown in Locations 1 and 2 of the figure below 3 Set the backbox over the top two hole mounting pattern and hang the backbox over the two screw heads 4 Insert and secure two 2 10 screws in the two hole mounting pattern as shown in Locations 3 and 4 of the figure below NOTE Add knockouts to the left and right side of the rear panel of the backbox Do not add knockouts in...

Page 38: ... hole mounting pattern 6 Secure with two 2 6 Hex Kep nuts in the two hole mounting pattern on the left side of the backbox as shown in Locations 7 and 8 of the figure below 7 Insert the Cabinet A trim right ring on the right side of the two hole mounting pattern 8 Secure with two 2 6 Hex Kep nuts in the two hole mounting pattern on the right side of the backbox as shown in Locations 9 and 10 of th...

Page 39: ...he 2 bay or 3 bay outer door on the backbox 2 Secure with three 3 6 32 nuts in the three hole mounting pattern on the left side of the backbox as shown in Locations 1 2 and 3 of the figure below Figure 2 5 4 3 1 Cabinet A or AA 2 Bay and 3 Bay Outer Door Installation CABINET A or AA 2 BAY AND 3 BAY OUTER DOOR CABINET A or AA BACKBOX 1 2 3 1 2 3 NUTS 6 32 3 PLACES ...

Page 40: ...inge pin hole on top of the nylon spacer and secure using the 8 x 5 screw as shown in Location 2 of the figure below 5 After the inner door is secured in place attach the one end of the bonding wire to the top hinge pin using the 8 x 5 screw as shown in Location 3 of the figure below NOTE For information on the installation of the opposite end of the bonding wire see Section 2 5 4 5 Step 3 and Loc...

Page 41: ...e mounting pattern as shown in Location 2 of the figure below 3 Secure the opposite end of the bonding wire to the welded 6 stud on the inner side of the inner door using the 6 nut as shown in Location 3 of the figure below 4 After the panel is wired use the thumbscrews to secure the inner door to the backbox as shown in Location 4 of the figure below Figure 2 5 4 5 1 Cabinet A or AA 2 Bay Inner D...

Page 42: ...abinet A or AA 3 Bay Installation Instructions The E3 Series Cabinet A or Cabinet AA 3 Bay assembly typically includes the following Backbox INI VGC Outer Door Inner Door 3 Bay Hardware Kit Figure 2 5 5 1 Cabinet A or AA 3 Bay Standard View unit or Blank Plate MIC ASM 16s Blank Plates Optional NGA ...

Page 43: ...in hole on top of the nylon spacer and secure using the 8 x 5 screw as shown in Location 2 of the figure below 5 After the inner door is secured in place attach the one end of the bonding wire to the top hinge pin using the 8 x 5 screw as shown in Location 3 of the figure below NOTE For information on the installation of the opposite end of the bonding wire see Section 2 5 5 2 Step 3 and Location ...

Page 44: ...s in the four hole mounting pattern as shown in Location 2 of the figure below 3 Secure the opposite end of the bonding wire to the welded 6 stud on the inner side of the inner door using the 6 nut as shown in Location 4 of the figure below 4 After the panel is wired use the thumbscrews to secure the inner door to the backbox as shown in Location 5 of the figure below Figure 2 5 5 2 1 Cabinet A or...

Page 45: ...ed on top of the ILI MB E3 ILI95 MB E3 DACT E3 RPT E3 ILI S E3 ILI95 S E3 Optional in place of the DACT E3 RPT E3 ANX Optional in place of the DACT E3 RPT E3 Optional Accessory E3 Cabinet B Trim Rings Outer Door Inner Door 2 Bay LCD E3 ASM 16 or blank Plate Hardware Kit Figure 2 5 6 1 Cabinet B Standard View 16 00 19 38 16 69 BACKBOX TOP BACKBOX SIDE PANEL BACKBOX 19 3 8 1 50 16 38 1 25 8 00 1 50 ...

Page 46: ...tions 1 and 2 of the figure below 3 Set the backbox over the top two hole mounting pattern and hang the backbox over the two screw heads 4 Insert and secure two 2 10 screws in the two hole mounting pattern as shown in Locations 3 and 4 of the figure below NOTE Add knockouts to the left and right side of the rear panel of the backbox Do not add knockouts in the center or top of the backbox above th...

Page 47: ...ee hole mounting pattern 6 Secure with three 3 6 Hex Kep nuts in the three hole mounting pattern on the left side of the backbox as shown in Locations 7 8 and 9 of the figure below 7 Insert the Cabinet B trim right ring on the right side of the three hole mounting pattern 8 Secure with three 3 6 Hex Kep nuts in the three hole mounting pattern on the right side of the backbox as shown in Locations ...

Page 48: ...Door Installation 1 Mount the outer door on the backbox 2 Secure with four 4 6 nuts in the four hole mounting pattern on the left side of the backbox as shown in Locations 1 2 3 and 4 of the figure below Figure 2 5 6 3 1 Cabinet B Outer Door Installation CABINETB OUTERDOOR 1 2 3 4 CABINETB BACKBOX NUT 6 HEX 4PLACES ...

Page 49: ... screws 4 40 x 3 8 into the eight 8 standoffs as shown in Location 2 of Figure 2 5 6 4 2 Note PCB orientation 3 Set the PM 9 PM 9G over the standoffs in the backbox and secure the six 6 screws 4 40 x 3 8 in the six hole mounting pattern as shown in Location 3 of Figure 2 5 6 4 2 Note PCB orientation 4 Place the batteries in the backbox The cabinet will accommodate two 2 batteries up to a maximum o...

Page 50: ... ILI MB E3 ILI95 MB E3 8 HOLE MOUNTING PATTERN PM 9 PM 9G 6 HOLE MOUNTING PATTERN STANDOFF 3 16 4 40 x 1 0 8 PLACES PER ILI MB E3 ILI95 MB E3 PCB SCREW 4 40 X 3 8 4 PLACES PER DACT E3 PCB SCREW 4 40 X 3 8 6 PLACES PER PM 9 PM 9G PCB SCREW 4 40 X 3 8 4 PLACES PER RPT E3 PCB NOTE PCB ORIENTATION NOTE PCB ORIENTATION NOTE PCB ORIENTATION 1 3 1 3 3 2 2 2 NOTE THE ANX CAN MOUNT ON TOP OF THE ILI MB E3 ...

Page 51: ...door bottom hinge pin hole on top of the nylon spacer and secure using the 8 x 5 screw as shown in Location 2 of the figure below 5 After the inner door is secured in place attach one end of the bonding wire to the top hinge pin using the 8 x 5 screw as shown in Location 3 of the figure below NOTE For information on the installation of the opposite end of the bonding wire see Section 2 5 6 6 Step ...

Page 52: ...ur hole mounting pattern as shown in Location 2 of the figure below 3 Secure the opposite end of the bonding wire to the welded 6 stud on the inner side of the inner door using the 6 nut as shown in Location 3 of the figure below 4 After the panel is wired use the thumbscrews to secure the inner door to the backbox as shown in Location 4 of the figure below Figure 2 5 6 6 1 Cabinet B Inner Door In...

Page 53: ...ouses the following Backbox batteries Outer Door Door Insert LCD E3 Display B Slim Plate B Slim Plate Optional mounted on top of the ILI MB E3 ILI95 MB E3 Hardware Kit Figure 2 5 7 1 B Slim Cabinet Installation ILI MB E3 ILI95 MB E3 PM 9 PM 9G DACT E3 RPT E3 ANX AC POWER ON POWER FAULT GROUND FAULT ALARM SYSTEM TROUBLE SYSTEM SILENCED MENU BACKSPACE EDIT OK ENTER ...

Page 54: ...two screw heads 4 Insert and secure two 2 10 screws in the two hole mounting patterns as shown in Locations 3 and 4 of Figure 2 5 7 1 1 Figure 2 5 7 1 1 B Slim Cabinet Dimensions NOTE If the fasteners are anchored to a wallboard use 10 wall anchors Mounting to concrete walls should be backed by plywood to insulate the equipment from possible condensation NOTE Add knockouts to the left and right si...

Page 55: ...location of the P2 and W2 terminal on the LCD E3 panel refer to Note 1 on the LCD E3 Wiring Diagram in Figure 3 13 4 1 of Section 3 14 4 5 Mount the LCD E3 Mounting Plate to the Outer Door and secure the four 4 nuts 6 32 HEX KEP in the four hole mounting pattern as shown in Location 5 of Figure 2 5 7 2 1 6 Install the keylock PK625 to the Outer Door and secure with one 1 nut 3 4 x 24 THD HEX as sh...

Page 56: ...tallation To mount the B Slim Cabinet outer door to the backbox secure with four 4 6 Hex Kep nuts in the four hole mounting pattern on the left side of the backbox See Locations 1 2 3 and 4 of Figure 2 5 7 3 1 Figure 2 5 7 3 1 B Slim Cabinet Outer Door Installation B SLIM CABINET E3 OUTER DOOR B SLIM CABINET BACKBOX 1 2 3 4 ...

Page 57: ...ws 4 40 in the eight hole mounting pattern as shown in Location 1 of Figure 2 5 7 4 2 2 Mount the PM 9 PM 9G on the B Slim E3 Plate and secure the six 6 screws 4 40 in the six hole mounting pattern as shown in Location 2 of Figure 2 5 7 4 2 Figure 2 5 7 4 1 B Slim E3 Plate Installation NOTE You can mount the DACT E3 RPT E3 or the ANX on top of the ILI MB E3 ILI95 MB E3 ILI MB E3 ILI95 MB E3 PM 9 P...

Page 58: ...nstallation Figure 2 5 7 4 2 B Slim E3 Plate Exploded View ILI MB E3 ILI95 MB E3 PM 9 PM 9G SCREW 4 40 8 PLACES SCREW 4 40 6 PLACES B SLIM E3 PLATE 1 1 2 2 NOTE MOUNT ANY OF THE FOLLOWING OPTIONAL MODULES ON TOP OF THE ILI MB E3 ILI95 M B E3 DACT E3 RPT E3 ILI S E3 ILI95 S E3 ANX ...

Page 59: ...Plate to Backbox Installation Mount the B Slim E3 sub assembly plate on the studs in the backbox and secure with four 4 8 32 screws as shown in Locations 1 thru 4 of the figure below Figure 2 5 7 5 1 B Slim E3 Sub Assembly Plate to Backbox Installation B SLIM CABINET BACKBOX PM 9 PM 9G 1 2 3 4 1 2 3 4 SCREW 8 32 4 PLACES ...

Page 60: ... Assembly typically houses the following Backbox Telephone Assembly Two Batteries Microphone Assembly E3 Cabinet C Trim Rings Optional Accessory E3 INX C Plate Outer Door E3 INX C Plate Hardware Kit Figure 2 5 8 1 Cabinet C Standard View ILI MB E3 ILI95 MB E3 ANX PM 9 PM 9G DACT E3 INI VG Series RPT E3 Up to a maximum of four 4 AM 50 Series amplifiers Optional ...

Page 61: ...ions 1 and 2 of the figure below 3 Set the backbox over the top two hole mounting pattern and hang the backbox over the two screw heads 4 Insert and secure two 2 10 screws in the two hole mounting pattern as shown in Locations 3 and 4 of the figure below Figure 2 5 8 1 1 Cabinet C Backbox Installation NOTE Add knockouts to the left and right side of the rear panel of the backbox Do not add knockou...

Page 62: ...ur hole mounting pattern 6 Secure with four 4 6 Hex Kep nuts in the four hole mounting pattern on the left side of the backbox as shown in Locations 7 8 9 and 10 of the figure below 7 Insert the Cabinet C trim right ring on the right side of the four hole mounting pattern 8 Secure with four 4 6 Hex Kep nuts in the four hole mounting pattern on the right side of the backbox as shown in Locations 11...

Page 63: ...tallation Mount the E3 INX C Plate outer door to the backbox by securing four 4 6 32 nuts in the four hole mounting pattern on the left side of the backbox See Locations 1 2 3 and 4 of the figure below Figure 2 5 8 3 1 Cabinet C E3 INX C Plate Outer Door Installation NUT HEX 6 32 4PLACES CABINETC INXE3 OUTERDOOR CABINETC BACKBOX 1 2 3 4 ...

Page 64: ...ation 3 of Figure 2 5 8 4 2 4 Mount the PM 9 PM 9G Adapter Plate on top of the PM 9 PM 9G and secure with six 6 screws 4 40 x 1 4 into the six 6 standoffs as shown in Location 4 of Figure 2 5 8 4 2 5 Mount the INI VG on the PM 9 PM 9G Adapter Plate and secure with six 6 screws 4 40 x 1 4 as shown in Location 5 of Figure 2 5 8 4 2 6 Mount two 2 AM 50 Series amplifiers on the E3 INX C plate and secu...

Page 65: ... Plate Exploded View CABINET C E3 INX C PLATE 2 2 DACT E3 RPT E3 INI VG SERIES PM 9 PM 9G ADAPTER PLATE 5 5 SCREW 4 40 x 12 PLACES 5 4 SCREW 4 40 x 8 PLACES STANDOFF 3 16 HEX 4 40 x 1 8 PLACES STANDOFF HEX 4 40 x 2 1 4 6 PLACES PM 9 PM 9G STANDOFF 3 16 HEX 4 40 x 1 8 PLACES MAX SCREW 4 40 x 8 PLACES 1 3 4 4 4 4 4 4 6 7 7 6 7 ...

Page 66: ...ount the E3 INX C Plate sub assemblies plate to the studs in the backbox and secure with six 6 10 32 nuts as shown in Locations 1 thru 6 of the figure below Figure 2 5 8 5 1 Cabinet C E3 INX C Plate to the Backbox Installation CABINET C BACKBOX CABINET C E3 INX C SUB ASSEMBLIES PLATE 1 1 1 3 3 2 4 BATTERIES NUT HEX 10 32 6 PLACES 6 5 2 4 ILI MB E3 ILI MB95 E3 ANX 5 6 ...

Page 67: ...Plate E3 ILI C Plate AM 50 Extender Plate Optional AM 50 Series amplifiers INCC E3 PLATE 7 Bay Inner Door Optional INCC E3 8 Bay Inner Door Hardware Kit Figure 2 5 9 1 Cabinet C E3 INCC C Standard View ILI MB E3 ILI95 MB E3 ANX INI VGC INI VGE DACT E3 PM 9 PM 9G RPT E3 ILI MB E3 ILI95 MB E3 ANX RPT E3 2 ILI E3 or ILI95 E3 Series PM 9 PM 9G DACT E3 1 LCD E3 keypad Combination of four 4 ASM 16s or A...

Page 68: ...llation Mount the E3 INCC C Plate outer door on the backbox by securing four 4 6 32 nuts in the four hole mounting pattern on the left side of the backbox See Locations 1 thru 4 of the figure below Figure 2 5 9 1 1 Cabinet C E3 INCC C Outer Door Installation CABINETC E3 INCC C OUTERDOOR NUT HEX 6 32 4PLACES 1 2 3 4 CABINETC BACKBOX 1 2 3 4 ...

Page 69: ...LI95 MB E3 ANX and secure with eight 8 screws 4 40 x 1 4 into the eight 8 standoffs as shown in Location 2 of Figure 2 5 9 2 2 3 Mount the PM 9 PM 9G over the standoffs on the E3 INCC C plate and secure with six 6 screws 4 40 x 1 4 in the six hole mounting pattern as shown in Location 3 of Figure 2 5 9 2 2 4 Mount the INI VG over the standoffs on the E3 INCC C plate and secure with six 6 screws 4 ...

Page 70: ...I 11 04 10 69 Cabinets Installation Figure 2 5 9 2 2 Cabinet C E3 INCC C Plate Installation CABINET C E3 INCC C PLATE 1 4 SCREW 4 40 x 8 PLACES 3 SCREW 4 40 x 6 PLACES INI VG SERIES DACT E3 RPT E3 STANDOFF 3 16 HEX 4 40 x 1 8 PLACES SCREW 4 40 x 6 PLACES 2 ...

Page 71: ...ount the Cabinet C E3 INCC C sub assembly plate on the studs in the backbox and secure with six 6 10 32 nuts as shown in Locations 1 thru 6 of the figure below Figure 2 5 9 3 1 Cabinet C E3 INCC C Sub Assembly Plate to the Backbox Installation 6 1 2 3 4 5 CABINET C E3 INCC C SUB ASSEMBLIES PLATE CABINET C BACKBOX BATTERIES NUT HEX 10 32 6 PLACES 1 3 4 5 6 2 INI VG SERIES ...

Page 72: ... the PM 9 PM 9G on the E3 ILI C plate and secure the eight 8 screws 3 16 hex 4 40 x 1 4 in the eight hole mounting pattern as shown in Location 3 of Figure 2 5 9 4 2 4 Mount the second ILI E3 or ILI95 E3 Series sub assembly on the E3 ILI C plate and secure the eight 8 standoffs 3 16 hex 4 40 x 1 4 into the eight 8 standoffs as shown in Location 4 of Figure 2 5 9 4 2 5 Mount the third ILI E3 or ILI...

Page 73: ...eration Manual P N 9000 0574 I 11 04 10 Installation Cabinets Figure 2 5 9 4 2 Cabinet C E3 ILI C Plate Exploded View 1 2 3 4 3 1 4 5 5 2 2 5 5 2 5 5 CABINET C E3 ILI C PLATE PM 9 PM 9G SCREW 4 40 X 8 PLACES SCREW 4 40 X 8 PLACES ...

Page 74: ...ing pattern as shown in Location 1 of the figure below 3 Place the E3 INCC C plate or E3 ILI C plate over the AM 50 extender plate and install using two 2 nuts 10 32 in the two hole mounting pattern as shown in Location 2 of the figure below Figure 2 5 9 5 1 Cabinet C AM 50 Extender Plate Installation NOTE Install the FPT GATE 3 Extender Plate in the space reserved for the batteries If you have ba...

Page 75: ...C plate or E3 ILI C sub assembly plate and AM 50 Extender Plate on the studs in the backbox and secure with six 6 10 32 nuts as shown in Locations 1 thru 6 of the figure below Figure 2 5 9 6 1 Cabinet C AM 50 Extender Plate to the Backbox Installation PM 9 PM 9G INI VG SERIES 1 3 5 2 4 6 3 2 4 5 6 1 5 6 ILI MB E3 ILI95 MB E3 ANX CABINETC BACKBOX CABINETC E3 INCC C SUB ASSEM BLIESPLATE SeeNote NUT ...

Page 76: ... following plates over the FPT GATE 3 Extender Plate and install using two 2 nuts 10 32 in the two hole mounting pattern as shown in Location 4 of the figure below Figure 2 5 9 7 1 FPT GATE 3 Extender Plate Installation Cabinet C E3 ILI C plate Cabinet D E3 INX D plate Cabinet C E3 INCC C Plate Cabinet D E3 INCC D plate Cabinet C E3 ILI C plate Cabinet D E3 INX D plate Cabinet C E3 INCC C Plate Ca...

Page 77: ... 6 10 32 nuts as shown in Locations 1 thru 6 of the figure below Figure 2 5 9 8 1 Cabinet C FPT GATE 3 Extender Plate to the Backbox Installation Cabinet C E3 ILI C plate Cabinet D E3 INX D plate Cabinet C E3 INCC C Plate Cabinet D E3 INCC D plate FPT GATE 3 EXTENDER PLATE FPT GATE 3 PM 9 PM 9G INI VG SERIES ILI MB E3 ILI95 MB E3 ANX CABINETC BACKBOX CABINETC E3 INCC C SUB ASSEMBLIES PLATE See Not...

Page 78: ...op of the nylon spacer and secure using the 8 x 5 screw as shown in Location 2 of the figure below 5 After the inner door is secured in place attach one end of the bonding wire to the top hinge pin hole using the 8 x 5 screw as shown in Location 3 of the figure below NOTE 3 The 7 bay or 8 bay inner door is optional NOTE 4 For information on the installation of the opposite end of the bonding wire ...

Page 79: ...crophone box and mount the units to the INCC E3 7 bay inner door by securing six 6 6 32 nuts as shown in Location 3 of the figure below 4 Mount the third bottom row of the telephone and microphone box to the INCC E3 7 bay inner door by securing six 6 6 32 nuts as shown in Location 4 of the figure below 5 Secure the opposite end of the bonding wire to the welded 6 stud on the inner side of the inne...

Page 80: ...er door bottom hinge pin hole on top of the nylon spacer and secure using the 8 x 5 screw as shown in Location 2 of the figure below 5 After the inner door is secured in place attach one end of the bonding wire to the top hinge pin using the 8 x 5 screw as shown in Location 3 of the figure below NOTE For information on the installation of the opposite end of the bonding wire see Section 2 5 9 12 S...

Page 81: ...ox and mount the units to the INCC E3 7 bay inner door by securing six 6 6 32 nuts as shown in Location 3 of the figure below 4 Mount the fourth bottom row of the telephone and microphone box to the INCC E3 7 bay inner door by securing six 6 6 32 nuts as shown in Location 4 of the figure below 5 Secure the opposite end of the bonding wire to the welded 6 stud on the inner side of the inner door us...

Page 82: ...tional Accessory Outer Door Cab D E3 INX D Back Plate ILI MB E3 ILI95 MB E3 ANX INI VG Series DACT E3 PM 9 PM 9G RPT E3 Two 2 AM 50 Series amplifiers Cab D E3 INCC D Plate Up to five 5 ILI MB E3 ILI95 MB E3 ANX or ILI S E3 ILI95 S E3 optional INI VG Series DACT E3 PM 9 PM 9G RPT E3 Inner Door 1 1 LCD E3 Display 1 INCC MIC Combination of ten 10 ASM 16s or ANU 48s Blank Plate s optional 1 INCC TEL I...

Page 83: ... in Locations 1 and 2 of the figure below 3 Set the backbox over the top two hole mounting pattern and hang the backbox on the two screw heads 4 Insert and secure two 2 10 screws in the two hole mounting pattern as shown in Locations 3 and 4 of the figure below Figure 2 5 10 1 1 Cabinet D INX Door Backbox Installation NOTE Add knockouts to the left and right side of the rear panel of the backbox D...

Page 84: ...five hole mounting pattern 6 Secure with five 5 6 Hex Kep nuts in the five hole mounting pattern on the left side of the backbox as shown in Locations 7 8 9 10 and 11 of the figure below 7 Insert the Cabinet D trim right ring on the right side of the five hole mounting pattern 8 Secure with five 5 6 Hex Kep nuts in the five hole mounting pattern on the right side of the backbox as shown in Locatio...

Page 85: ... Installation 1 Mount the door over the studs on the backbox 2 Secure with four 4 6 32 nuts in the four hole mounting pattern on the left side of the backbox See Locations 1 thru 6 of the figure below Figure 2 5 10 3 1 Cabinet D Outer Door Installation CABINETD BACKBOX CABINETD OUTERDOOR NUT HEX 6 32 6PLACES 1 2 3 4 5 6 ...

Page 86: ...the six 6 screws 4 40 x 1 4 into the six hole mounting pattern as shown in Location 3 of Figure 2 5 10 4 2 4 Mount the PM 9 PM 9G on the E3 INX D plate and secure the six 6 screws 4 40 x 1 4 into the six hole mounting pattern as shown in Location 4 of Figure 2 5 10 4 2 5 Mount the AM 50 Series amplifiers on the E3 INX D plate and secure the 8 screws 4 40 x 1 4 into the eight hole mounting pattern ...

Page 87: ...llation DACT E3 RPT E3 STANDOFF 3 16 HEX 4 40 x 1 8 PLACES 1 SCREW 4 40 x 6 PLACES 3 SCREW 4 40 x 8 PLACES 4 SCREW 4 40 x 4 PLACES 5 SCREW 4 40 x 4 PLACES 6 CABINET D E3 INX D PLATE 2 1 3 SCREW 4 40 x 8 PLACES 4 5 6 NOTE IF NO BATTERIES ARE REQUIRED IN CABINET D INSTALL THE FPT GATE 3 EXTENDER PLATE OPTIONAL FPT GATE 3 EXTENDER PLATE OPTIONAL ...

Page 88: ...ure 2 5 10 5 2 5 Mount the first ILI E3 ILI95 E3 Series or ANX sub assembly on the E3 INCC D plate and secure the 8 screws 4 40 x 1 4 into the eight hole mounting pattern as shown in Location 5 of Figure 2 5 10 5 2 6 Mount the second ILI E3 ILI95 E3 Series or ANX sub assembly on the E3 INCC D plate and secure the eight 8 screws 4 40 x 1 4 into the eight hole mounting pattern as shown in Location 6...

Page 89: ...ure 2 5 10 5 2 Cabinet D E3 INCC D Back Plate Installation DACT E3 RPT E3 CABINETD E3 INCC DPLATE STANDOFF 3 16 HEX 4 40x1 8PLACES SCREW 4 40x 8PLACES SCREW 4 40x 6PLACES SCREW 4 40x 8PLACES 1 2 3 4 5 6 7 8 SCREW 4 40x 8PLACES 7 7 7 7 8 8 8 8 SCREW 4 40x 8PLACES STANDOFF 3 16 HEX 4 40x1 8PLACES ...

Page 90: ...figure below Figure 2 5 10 6 1 Cabinet D E3 INCC D Sub Assembly Plate to the Backbox Installation CABINET D BACKBOX CABINET D E3 INCC D PLATE See Note 1 BATTERIES NUT HEX 10 32 8 PLACES DACT E3 RPT E3 INI VG SERIES ILI E3 ILI95 E3 SERIES OR ANX ILI E3 ILI95 E3 SERIES OR ANX 1 2 3 4 5 6 1 2 3 4 5 6 7 8 8 7 NOTE 1 Install either the E3 INX D or the E3 INCC D plate to the backbox ILI E3 ILI95 E3 SERI...

Page 91: ...n hole on top of the nylon spacer and secure using the 8 x 5 screw as shown in Location 2 of the figure below NOTE The 13 bay or 14 bay inner door is optional 5 After the inner door is secured in place attach one end of the bonding wire to the top hinge pin using the 8 x 5 screw as shown in Location 3 of the figure below NOTE For information on the installation of the opposite end of the bonding w...

Page 92: ... securing six 6 6 32 nuts as shown in Location 4 of the figure below 5 Interlock the fourth bottom row of the fourth set of ASM 16 sub assemblies with the fifth top row of the telephone and microphone box Mount the units to the 13 bay inner door by securing six 6 6 32 nuts as shown in Location 5 of the figure below 6 Mount the fifth bottom row of the telephone and microphone box to the 13 bay inne...

Page 93: ... using the 8 x 5 screw as shown in Location 2 of the figure below 5 After the inner door is secured in place attach one end of the bonding wire to the top hinge pin using the 8 x 5 screw as shown in Location 3 of the figure below NOTE 1 The 13 bay or 14 bay inner door is optional NOTE 2 For information on the installation of the opposite end of the bonding wire see Section 2 5 10 10 Step 7 and Loc...

Page 94: ... inner door by securing six 6 6 32 nuts as shown in Location 4 of the figure below 5 Interlock the fourth bottom row of the fourth set of ASM 16 sub assemblies with the fifth top row of the telephone and microphone box and mount the units to the 14 bay inner door by securing six 6 6 32 nuts as shown in Location 5 of the figure below 6 Mount the fifth bottom row of the telephone and microphone box ...

Page 95: ...94 E3 Series Installation Operation Manual P N 9000 0574 I 11 04 10 Installation Cabinets Notes ...

Page 96: ...24 VDC max 2 0 amp Special application Suitable for use with the FM Series door holders TB3 5 TB3 7 Common negative 3 1 2 Relay Connections System Alarm Contacts TB5 2 Normally Open TB5 3 Common TB5 1 Normally Closed Rated 2 amp 30 VDC resistive Transfers upon any system alarm except supervisory Supervisory Contacts TB5 5 Normally Open TB5 6 Common TB5 4 Normally Closed Rated 2 amp 30 VDC resistiv...

Page 97: ...ut TB4 4 2 return TB4 3 out TB4 1 return ILI95 MB E3 Wiring Instructions SLC 1 Style 4 TB7 4 TB7 3 SLC 2 Style 4 TB4 4 TB4 3 SLC 1 Style 6 TB7 4 out TB7 3 out TB7 2 return TB7 1 return SLC 2 Style 6 TB4 4 out TB4 3 out TB4 2 return TB4 1 return Polarity markings indicate the polarity that should be maintained throughout the circuit Polarity connected to the circuit must be observed on all devices ...

Page 98: ...ondition Use UL Listed End of Line Resistor EOL N 33K P N 4700 0484 for Class B Style Y wiring Circuit Ratings 24 VDC Nom FWR Max alarm load 2 0 amp circuit Ground fault test impedance Zero ohms Supervised Power limited 18 AWG minimum MDL3 Series Synchronization Modules must be connected Special application See Compatibility Addendum P N 9000 0427 for a list of Gamewell FCI approved UL Listed noti...

Page 99: ...nections 3 2 Intelligent Loop Interface Main Board Connections Figure 3 2 1 and Figure 3 2 2 illustrate the Intelligent Loop Interface Main Board ILI MB E3 sub assembly Figure 3 2 1 Intelligent Loop Interface Main Board ILI MB E3 Sub Assembly Figure 3 2 2 Intelligent Loop Interface Main Board ILI MB E3 Sub Assembly TB2 TB3 TB1 TB4 TB5 TB6 ...

Page 100: ...CT E3 See Note 3 TB3 3 Earth Ground Connect to water pipe ground TB3 4 Resettable B Auxiliary resettable 24 VDC power TB3 5 GND Common negative TB3 6 Non resettable B Auxiliary non resettable 24 VDC power TB3 7 GND Common negative TB3 8 Municipal Ckt Output to Local Energy City Box or Remote Station or Releasing Solenoid Non Power limited See Note 7 TB3 9 Municipal Ckt Output to Local Energy City ...

Page 101: ...peater Connects to INI VG J7 or J10 of the RPT E3 See Note 4 NOTE 1 Must be IN when connected via a ribbon cable from this ILI95 MB E3 at J1 to a PM 9 PM 9G connector J1 Requires the removal of the JMP 1 on the PM 9 PM 9G Must be OUT when a ribbon cable is not installed in J1 and the ground fault detection is being provided by an INI VG Series node that is being powered from a common PM 9 PM 9G NO...

Page 102: ...EARTH GROUND PER ARTICLE 780 OF THE NATIONAL ELECTRICAL CODE FAILURE TO CONNECT TO A METALLIC GROUND WATER PIPE OR GROUND DRIVEN ROD WILL RESULT IN LOSS OF LIGHTNING PROTECTION REDUCED PROTECTION AGAINST TRANSIENTS AND COULD ADVERSELY AFFECT PROPER SYSTEM OPERATION PANEL NEUTRAL OR CONDUIT GROUND IS NOT ACCEPTABLE USE 14 AWG WIRE MINIMUM LEAVE W1 W2 W3 W4 W5 OPEN TO RPT E3 ARCNET CONNECTOR J10 TO ...

Page 103: ... Intelligent Loop Interface XP95 Main Board Connections Figure 3 3 1 and Figure 3 3 2 illustrate the Intelligent Loop Interface XP95 Main Board ILI95 MB E3 sub assembly Figure 3 3 1 Intelligent Loop Interface XP95 Main Board ILI95 MB E3 Sub Assembly Figure 3 3 2 Intelligent Loop Interface XP95 Main Board ILI95 MB E3 Sub Assembly TB3 TB2 TB1 TB7 TB4 TB5 TB6 ...

Page 104: ...negative TB3 6 Non resettable B Auxiliary non resettable 24 VDC power TB3 7 GND Common negative TB3 8 Municipal Ckt Output to Local Energy City Box or Remote Station or Releasing Solenoid Non Power Limited TB3 9 Municipal Ckt Output to Local Energy City Box or Remote Station or Releasing Solenoid Non Power Limited TB4 1 SLC 2 A SLC 2 Style 6 7 Return See Note 5 TB4 2 SLC 2 A SLC 2 Style 6 7 Return...

Page 105: ...ribbon cable from this ILI95 MB E3 at J1 to a PM 9 PM 9G connector J1 Requires the removal of the JMP 1 on the PM 9 PM 9G Must be OUT when a ribbon cable is not installed in J1 and the ground fault detection is being provided by an INI VG Series node that is being powered from a common PM 9 PM 9G NOTE 2 Connect J1 to PM 9 PM 9G J1 only when the PM 9 PM 9G is NOT powering an INI VG Series sub assem...

Page 106: ... 8 7 TB1 TB2 485A 485B RB GND AB GND MU MU MB PR W7 MB PR W8 J2 1 2 10 9 J4 2 1 16 15 RS232 PORT 15 VDC MAXIMUM 0 05 AMP MAXIMUM UP TO 115 2 K BAUD DEFAULT 8 DATA BITS 1 STOP BIT NO PARITY USE SWITCH SW1 TO SET ILI95 MB E3 PCB NETWORK ADDRESS 1 64 SET TO 0 ZERO FOR STANDALONE MODE SW2 1 2 3 4 5 ENA GFLT DIS W9 AUX TERM OFF ON USE FACTORY W1BSEL W3 BSEL W2 ARCNET TERM OFF W4 ON J5 10 9 2 1 PM 9 PM ...

Page 107: ...ion Style 7 wiring requires the use of an M500X Isolator Module on both sides of a device Wiring Instructions SLC 1 Style 4 TB4 8 TB4 7 SLC 2 Style 4 TB4 4 TB4 3 SLC 1 Style 6 TB4 8 out TB4 6 return TB4 7 out TB4 5 return SLC 2 Style 6 TB4 4 out TB4 4 2 return TB4 3 out TB4 1 return Polarity markings indicate the polarity that should be maintained throughout the circuit Polarity connected to the c...

Page 108: ...nections E3 Series System Connections 3 4 2 Intelligent Loop Interface Slave Board Sub Assembly Figure 3 4 2 1 and illustrate the Intelligent Loop Interface Slave board ILI S E3 sub assembly Figure 3 4 2 1 ILI S E3 Signaling Line Circuit Sub Assembly Figure 3 4 2 2 ILI S E3 Signaling Line Circuit Sub Assembly TB6 TB1 TB4 ...

Page 109: ...lead on download cable P N 75267 TB6 3 Supervision Optional Printer Supervision TB6 4 RS232 RxD To green lead on download cable P N 75267 W1 W2 W3 Factory Jumpers Factory Use Only Default OUT W4 Local ARCNET OPEN Normal Operation SHORT If the ILI S E3 or ILI S95 E3 is located at the end of the ARCNET bus SW2 1 Switch 1 ON SLC 1 DISABLED OFF SLC 1 ENABLED SW2 2 Switch 2 ON SLC 2 DISABLED OFF SLC 2 ...

Page 110: ...FINED BY CamWorks GND LED1 REC NETWORK RECONFIGURATION LED2 MRC NETWORK RECONFIGURATION ORIGINATING FROM THIS NODE LED3 DUP NODE S NETWORK ADRESS IS DUPLICATED AT ANOTHER NODE LED4 TX NODE IS TRANSMITTING DATA TO THE NETWORK LED5 RX NODE IS RECEIVING DATA FROM THE NETWORK LED6 RST NODE IS RESETTING LED7 DG GENERAL NETWORK FAULT LED8 ALRM ALARM CONDITION LED9 SUPV SUPERVISORY OFF NORMAL LED10 TRBL ...

Page 111: ...of an M500X Isolator Module ILI S E3 or XP95 LI Line Isolator or XP95 LIB Line Isolator Base ILI95 S E3 on both sides of a device Wiring Instructions SLC 1 Style 4 TB7 3 TB7 4 SLC 1 Style 6 TB4 3 TB4 4 SLC 2 Style 4 TB7 1 return TB7 2 return TB7 3 out TB7 4 out SLC 2 Style 6 TB4 1 return TB4 2 return TB4 3 out TB4 4 out Polarity markings indicate the polarity that should be maintained throughout t...

Page 112: ...ystem Connections 3 5 2 Intelligent Loop Interface XP95 Slave Board Sub Assembly Figure 3 5 2 1 and Figure 3 5 2 2 illustrate the Intelligent Loop Interface XP95 Slave Board ILI95 S E3 sub assembly Figure 3 5 2 1 ILI95 S E3 Signaling Line Circuit Sub Assembly Figure 3 5 2 2 ILI95 S E3 Signaling Line Circuit Sub Assembly TB4 TB7 TB6 TB1 ...

Page 113: ... TB7 3 SLC 1 B SLC 1 Style 4 6 7 Out See Note 1 TB7 4 SLC 1 B SLC 1 Style 4 6 7 Out See Note 1 W1 W2 W3 Factory Jumpers Factory use only Default OUT W4 Local ARCNET Terms OPEN Normal Operation SHORT IftheILI95 S E3islocated attheendoftheARCNETbus W5 RS 485 AUX Terminal OPEN OFF Normal Operation SHORT ON RS 485 Termination SW2 1 Switch 1 ON SLC 1 DISABLED OFF SLC 1 ENABLED SW2 2 Switch 2 ON SLC 2 D...

Page 114: ... 2 3 4 5 USE FACTORY W1 BSEL W3 BSEL W2 J5 10 9 2 1 1 2 3 4 ON TB4 TB6 PM 9 PM 9G GND DOWNLOAD CABLE P N 75267 TB6 4 RXD TO PIN 3 OF DB9 TB6 3 SUPV TO PIN 9 OF DB9 TB6 2 TXD TO PIN 2 OF DB9 TB6 1 GND TO PIN 5 OF DB9 GND 24VDC GND 24VDC PM 9 PM 9G 24VDC OPT MOD OPT MOD 4 3 2 1 1 2 3 4 4 3 2 1 SLC1 CLASS B STYLE 4 SLC1 CLASS B STYLE 4 SLC1 CLASS A STYLE 6 SLC1 CLASS A STYLE 6 SLC2 CLASS A STYLE 6 SL...

Page 115: ...6 5 3 2 1 7 8 4 6 5 3 2 1 7 8 4 6 5 3 2 1 7 8 4 6 5 3 2 1 7 8 4 6 5 3 2 1 7 8 4 6 5 3 2 1 7 8 4 6 5 3 2 1 7 8 4 6 5 3 2 1 7 8 4 6 5 3 2 1 7 8 4 6 5 3 2 on 9 1 7 8 4 6 5 3 2 1 7 8 4 6 5 3 2 10 on 1 7 8 4 6 5 3 2 on 25 1 7 8 4 6 5 3 2 on 26 on 27 1 7 8 4 6 5 3 2 1 7 8 4 6 5 3 2 1 7 8 4 6 5 3 2 1 7 8 4 6 5 3 2 1 7 8 4 6 5 3 2 1 7 8 4 6 5 3 2 on 33 on 34 1 7 8 4 6 5 3 2 on 35 1 7 8 4 6 5 3 2 1 7 8 4 6...

Page 116: ...ssemblies have the capacity to expand the E3 Series network from 64 nodes to a maximum of 122 nodes The ANX MR UTP allows twisted pair copper interconnections only The ANX MR FO adds Fiber Optic connectivity 3 7 1 ANX Specifications The following are the electrical specifications for the Addressable Node Expander ANX 3 7 2 Minimum Configuration The minimum configuration for use as a working system...

Page 117: ...erface between network nodes ARCNET should be installed in a separate conduit Twisted unshielded pair low capacitance 18 AWG 3 000 ft 914 m 18 AWG 3 1 mm2 Ethernet See Note 2 Data Communications CAT5 Crossover or Straight through 300 ft 100 m 10 100 Ethernet CAT5 NOTE 1 The lightning arresters are required on circuits extending between buildings 999 meter length maximum to meet UL 1459 NOTE 2 The ...

Page 118: ...et connectivity for configuration and or FocalPoint communication The single E3 Series network interface offers a Local Network connection that uses a ribbon cable within a single cabinet To add the twisted pair and or fiber optic connections for communication outside the local network use the RPT E3 UTP or RPT E3 FO sub assemblies Figure 3 7 6 1 Addressable Node Expander Single Ring ANX SR Sub As...

Page 119: ...e P N 75267 W1 W2 W3 Factory Jumpers Factory Use Only or Right Default OUT W4 ARCNET Termination OPEN Normal Operation SHORT If the ANX is located at the end of the ARCNET bus SW1 1 Serial Communication ON RS 232 115 2 kbits sec OFF defined by CAMWorks SW1 2 thru SW1 8 ARCNET Address See Section 4 J1 ETHERNET To FocalPoint or TCP IP Network Port Green LED Communication link established blinks with...

Page 120: ...ND 24VDC TB1 1 2 3 4 GND 24VDC GND 24VDC TB3 RS232 RS232 BSEL W2 BSEL W3 W1 USE FACTORY SW2ON 1 2 3 4 5 LED 1 LED 2 LED 3 LED 4 LED 5 LED 6 LED 7 LED KEY LED1 REC NETWORK RECONFIGURATION LED2 MRC NETWORK RECONFIGURATION ORIGINATING FROM THIS NODE LED3 DUP NODE S NETWORK ADDRESS IS DUPLICATED AT ANOTHER NODE LED4 TX NODE IS TRANSMITTING DATA TO THE NETWORK LED5 RX NODE IS RECEIVING DATA FROM THE NE...

Page 121: ...or configuration or FocalPoint communication The primary E3 Series network interface supports a Local Network connection that uses a ribbon cable within a single cabinet To add the twisted pair and or fiber optic connections for primary communication outside the local network use the RPT E3 UTP or RPT E3 FO sub assemblies The secondary E3 Series network connection does not allow Local Network ribb...

Page 122: ...de Assignment See Table 3 7 7 1 2 SW2 2 RING SELECT Ring Node Assignment See Table 3 7 7 1 2 SW2 3 RING SELECT Ring Node Assignment See Table 3 7 7 1 2 SW2 4 RING SELECT Ring Node Assignment See Table 3 7 7 1 2 SW2 5 Not Used J1 ETHERNET To FocalPoint or TCP IP Network Port Green LED Communication link established blinks with message traffic Yellow LED 100 Mbps speed Off 10 Mbps J2 Local ARCNET Co...

Page 123: ... switch setting for the ANX MR UTP Figure 3 7 7 1 1 ANX MR UTP SW2 Switch Setting Primary Ring Select Switch Secondary Ring Select Switch SW2 POS 1 SW2 POS2 SW2 POS3 SW2 POS4 Ring 0 to Ring 1 Bridge Ring 0 Node 63 Ring 1 Node 62 126 0 0 0 1 Ring 1 Node 62 126 Ring 0 Node 63 0 1 0 0 Table 3 7 7 1 2 ANX MR UTP Primary and Secondary Ring Select Switch Settings Note 1 The TB4 ANX UTP Network Connectio...

Page 124: ...DE LED4 TX NODE IS TRANSMITTING DATA TO THE NETWORK LED5 RX NODE IS RECEIVING DATA FROM THE NETWORK LED6 RST NODE IS RESETTING LED7 DG GENERAL NETWORK FAULT LED8 REC NETWORK RECONFIGURATION LED9 MRC NETWORK RECONFIGURATION ORIGINATING FROM THIS NODE LED10 DUP NODE S NETWORK ADDRESS IS DUPLICATED AT ANOTHER NODE LED11 TX NODE IS TRANSMITTING DATA TO THE NETWORK LED12 RX1 NODE1 IS RECEIVING DATA FRO...

Page 125: ...ti Ring Fiber Optic Pair ANX MR FO The Addressable Node Expander Multi Ring Fiber Optic panel provides the same features as the ANX MR UTP with the following additional feature The ANX MR FO network component includes fiber optic FO connectivity on the secondary network connection Figure 3 7 8 1 ANX MR FO Sub Assembly Figure 3 7 8 2 ANX MR FO Sub Assembly PCB TB4 TB2 TB3 TB1 ...

Page 126: ...MWorks SW1 2 thru SW1 8 Not Used SW2 1 RING SELECT Ring Node Assignment See Table 3 7 8 1 2 SW2 2 RING SELECT Ring Node Assignment See Table 3 7 8 1 2 SW2 3 RING SELECT Ring Node Assignment See Table 3 7 8 1 2 SW2 4 RING SELECT Ring Node Assignment See Table 3 7 8 1 2 SW2 5 Not Used J1 ETHERNET To FocalPoint or TCP IP Network Port Green LED Communication link established blinks with message traffi...

Page 127: ...lustrates the SW2 switch setting for the ANX MR FO Figure 3 7 8 1 1 ANX MR FO SW2 Switch Setting Primary Ring Select Switch Secondary Ring Select Switch SW2 POS 1 SW2 POS2 SW2 POS3 SW2 POS4 Ring 0 to Ring 1 Bridge Ring 0 Node 63 Ring 1 Node 62 126 0 0 0 1 Ring 1 Node 62 126 Ring 0 Node 63 0 1 0 0 Table 3 7 8 1 2 ANX MR FO Primary and Secondary Ring Select Switch Settings Note 1 The TB4 ANX UTP Net...

Page 128: ...NODE IS TRANSMITTING DATA TO THE NETWORK LED5 RX NODE IS RECEIVING DATA FROM THE NETWORK LED6 RST NODE IS RESETTING LED7 DG GENERAL NETWORK FAULT LED8 REC NETWORK RECONFIGURATION LED9 MRC NETWORK RECONFIGURATION ORIGINATING FROM THIS NODE LED10 DUP NODE S NETWORK ADDRESS IS DUPLICATED AT ANOTHER NODE LED11 TX NODE IS TRANSMITTING DATA TO THE NETWORK LED12 RX1 NODE1 IS RECEIVING DATA FROM THE NETWO...

Page 129: ...7 8 4 6 5 3 2 1 7 8 4 6 5 3 2 1 7 8 4 6 5 3 2 1 7 8 4 6 5 3 2 1 7 8 4 6 5 3 2 1 7 8 4 6 5 3 2 1 7 8 4 6 5 3 2 on 9 1 7 8 4 6 5 3 2 1 7 8 4 6 5 3 2 10 on 1 7 8 4 6 5 3 2 on 25 1 7 8 4 6 5 3 2 on 26 on 27 1 7 8 4 6 5 3 2 1 7 8 4 6 5 3 2 1 7 8 4 6 5 3 2 1 7 8 4 6 5 3 2 1 7 8 4 6 5 3 2 1 7 8 4 6 5 3 2 on 33 on 34 1 7 8 4 6 5 3 2 on 35 1 7 8 4 6 5 3 2 1 7 8 4 6 5 3 2 on 36 1 7 8 4 6 5 3 2 1 7 8 4 6 5 3...

Page 130: ...necting the circuit must be clearly marked FIRE ALARM CIRCUIT CONTROL Connections must be accessible only to authorized personnel 3 8 1 1 PM 9 The PM 9 can draw up to 4 6 amps max 120 VAC 60 Hz when under full load See Figure 3 8 1 1 for the AC wiring and ground connections See Table 3 8 5 1 for AC input and battery connections See Table 3 8 5 2 for ground fault options and programming 3 8 1 2 PM ...

Page 131: ...tinuous Output Current 5 amperes max continuous Standby when the PM 9 is used with the ILI E3 or the ILI95 E3 Series See Note 1 5 amperes max continuous Standby when the PM 9G is used with the ILI E3 or the ILI95 E3 Series See Note 1 Output Current 4 amperes max continuous Standby when the PM 9 is used with any AM 50 Series amplifier See Note 2 4 amperes max continuous Standby when the PM 9G is us...

Page 132: ...Power Supply Sub Assembly Figure 3 8 4 1 and Figure 3 8 4 2 illustrate the PM 9 Power Supply sub assembly Figure 3 8 4 1 PM 9 Power Supply Sub Assembly Figure 3 8 4 2 PM 9Power Supply JMP1 TB3 TB4 J1 W1 TB1 1 1 1 1 1 1 1 T1 1 1 1 1 24 VOUT 24 VOUT 24 VOUT GND GND GND PS1 PS2 PS3 BATT BATT GNDSIG 12 HOT BLK GND GRN NEUT WHT 6 25A 250V SLO BLO F1 ...

Page 133: ...I E3 Series ANX INI VGC TB4 5 24VOUT 24 VDC FWR Output to other sub assemblies INI VG ILI95 E3 ILI E3 Series or ANX TB4 6 GND GND Output to INI VG ILI95 E3 ILI E3 Series or ANX JMP1 IN for GND Fault Detection See Note 1 J1 10 PIN Ribbon Cable Connect to the ILI95 MB E3 ILI MB E3 or ANX Connector J1 or INI VG Connector J4 See Note 2 JMP2 Factory Use Only LED 2 Green Lights to indicate AC power LED ...

Page 134: ...ND EXTERNAL POWER OUTPUT 24VDC EXTERNAL POWER OUTPUT GND 24VDC 9 AMPS FROM ANY EXT PWR OUTPUT 9 AMPS TOTAL FROM PM 9 NON PWR LIMITED 120VAC NEUTRAL WHITE NOTE 4 DISABLE THE GROUND FAULT DETECTION CIRCUIT WHEN THE PM 9 IS CONNECTED BY A RIBBON CABLE TO AN ILI MB E3 ILI95 MB E3 OR AN ANX GROUND GREEN 120VAC HOT BLACK TO ILI MB E3 ILI95 MB E3 ANX J1 CONNECTOR OR INI VG J4 CONNECTOR PIN1 D2 D4 D3 GREE...

Page 135: ...Series System Connections PM 9 PM 9G Power Supply Connections 3 8 7 PM 9G Power Supply Sub Assembly Figure 3 8 7 1 and Figure 3 8 7 2 illustrate the Power Supply PM 9G sub assembly Figure 3 8 7 1 Power Supply PM 9G Sub Assembly Figure 3 8 7 2 Power Supply PM 9G Sub Assembly ...

Page 136: ...Series ANX and INI VGC TB4 5 24VOUT 24 VDC FWR Output to other sub assemblies INI VG Series ILI95 E3 ILI E3 Series or ANX TB4 6 GND Common Output to INI VG ILI95 E3 ILI E3 Series or ANX JMP1 IN for GND Fault Detection See Note 1 J1 10 PIN Ribbon Cable Connect to the ILI95 MB E3 ILI MB E3 or ANX Connector J1 or INI VG Series Connector J4 See Note 2 JMP2 Factory Use Only LED 2 Green Lights to indica...

Page 137: ... ANY EXT PWR OUTPUT 9 AMPS TOTAL FROM PM 9G NON PWR LIMITED 240VAC NEUTRAL WHITE NOTE 4 DISABLE THE GROUND FAULT DETECTION CIRCUIT WHEN THE PM 9G IS CONNECTED BY A RIBBON CABLE TO AN ILI MB E3 ILI95 MB E3 OR AN ANX GROUND GREEN 240VAC HOT BLACK TO ILI95 MB E3 ILI MB E3 OR ANX J1 CONNECTOR OR INI VG J4 CONNECTOR PIN1 6 7 1 12 NOTE 3 CONNECTION MUST BE TO A DEDICATED BRANCH CIRCUIT AND MECHANICALLY ...

Page 138: ...SM 16 J2 The address of the ASM 16 in the system is set via a DIP Switch Up to sixteen 16 ASM 16 sub assemblies can be installed The first address must be set to Number 32 For additional information on the connections and addressing information refer to the ASM 16 Installation Instructions P N 9000 0550 3 9 1 Specifications The following list the electrical specifications for the ASM 16 Operating ...

Page 139: ...Series System Connections ASM 16 Addressable Switch Connections 3 9 2 Addressable Switch Sub Assembly ASM 16 Sub Assembly Figure 3 9 2 1 and Figure 3 9 2 2 illustrate the Addressable Switch ASM 16 sub assembly Figure 3 9 2 1 ASM 16 Rear View Figure 3 9 2 2 ASM 16 Front View ...

Page 140: ...INI VGX INI VGE J1 J2 J3 ASM 16 J3 Ribbon Cable Connect To J1 LCD E3 J1 J2 ANU 48 J3 INI VGC INI VGX INI VGE J1 J2 J3 ASM 16 J4 Emulator Factory Use Only J5 Factory use only JMP1 Termination Install Jumper only if the last device is on RS 485 bus Note See Note A in Figure 3 9 4 1 for the ribbon cable connection ASM 16 or ANU 48 to ASM 16 or ANU 48 Wiring From ASM 16 or ANU 48 RS 485 COM A from pre...

Page 141: ...bbon cable connection From INI VGC INI VGX or INI VGE To ASM 16 or ANU 48 ASM 16 or ANU 48 to ASM 16 or ANU 48 Wiring TB6 RS 485 Remote ASM 16 or ANU 48 TB 1 TB6 1 24V Single Discrete Wire TB1 3 24V TB6 2 COMM B Single Discrete Wire TB1 2 COMM B TB6 3 COMM A Single Discrete Wire TB1 1 COMM A TB6 4 GND Single Discrete Wire TB1 4 GND Note See Note D in Figure 3 9 4 1 for the hardwire connection ILI ...

Page 142: ...ASM 16 or ANU 48 to ASM 16 or ANU 48 wiring ASM 16 ANU 48 to ASM 16 ANU 48 RS 485 Connection NOTE C and F From local INI VG or LCD E3 J1 RS 485 Local NOTE B D and E HARDWARE RS 485 Port to from module in Different INCC cabinet From ILI MB E3 IL95 MB E3 TB3 1 TB3 2 TB1 3 and TB1 4 RS 485 RIBBON CABLE Connector to from module In same INCC Cabinet NOTE B To next ASM 16 or ANU 48 TB1 remote in next IN...

Page 143: ...IBBON CABLE IN AND OR OUT CONNECTIONS TO NEXT PREVIOUS MODULE NOTE POSITION PIN 1 JMP4 REMOVE SHUNT AND PLACE SA C CONNECTOR FOR EXTERNAL SOUNDER J3 RS 485 PORT CONNECTIONS ANU 48 OR J2 ASM 16 J1 J2 OR J3 AND INI VG SERIES J3 J2 RS 485 PORT CONNECTORS ANU 48 J1 OR J2 ASM 16 J1 J2 OR J3 AND INI VG SERIES J3 TB1 RS 485 PORT CONNECTS TO THE INI VG SERIES JMP1 J1 RS 485 PORT CONNECTIONS ANU 48 J1 OR J...

Page 144: ...M 16 Programming Address Switch Settings Figure 3 9 6 1 illustrates the ASM 16 programming address switches NOTE Set the first address in the program to switch 32 Figure 3 9 6 1 ASM 16 Programming Address Switch Settings Set this switch 6 UP when connected to the ILI MB E3 ILI95 MB E3 or ANX Set this switch 6 DOWN when connected to the INI VGC ...

Page 145: ...Station Verify that data has been accepted by the Central Station Hang up and release phone lines Communicate in a variety of formats Remote via the RS 485 serial interface 3 10 1 Central Station Reporting UL Listed receivers compatible with the E3 Series are listed in Table 3 10 1 1 Manufacturer Receiver Model Formats Silent Knight Model 9000 SIA 8 SIA 20 SK4 2 3 1 14 3 1 23 Silent Knight Model 9...

Page 146: ...in the devices not ringing in response to an incoming call In most but not all areas the sum of the RENs should not exceed five 5 To be certain of the number of devices that may be connected to the line as determined by the total RENs contact the Telephone Company to determine the maximum REN for the calling area 3 10 3 Specifications The following list the electrical specifications for the DACT E...

Page 147: ... Connections 3 10 4 Digital Alarm Communicator DACT E3 Sub Assembly Figure 3 10 4 1 and Figure 3 10 4 2 illustrate the Digital Alarm Communicator DACT E3 sub assembly Figure 3 10 4 1 DACT E3 Sub Assembly Figure 3 10 4 2 DACT E3 Sub Assembly 1 TB1 TB2 1 TVS2 TVS1 PTC1 PTC2 1 TP4 1 4 STANDBY LINE2 STATUS LINE1 STATUS TP1 TP2 LED3 LED2 LED1 TP3 T1 ...

Page 148: ...T UUU 1 113 00 NN GGT UUU 0 T U 0 Waterflow Alarm Restored SH GGT UUU 3 113 00 NN GGT UUU 2 T U 2 Trouble except Waterflow or Special AMM PID FT GGT UUU 1 373 00 NN GG0 UUU 8 T U 8 Trouble Restored FJ GGT UUU 3 373 00 NN GG0 UUU 7 T U 7 Trouble Waterflow AMM PID ST GGT UUU 1 370 00 NN GG0 UUU 8 T U 8 Trouble Restored Waterflow AMM PID SJ GGT UUU 3 203 00 NN GG0 UUU 7 T U 7 Trouble Special AMM PID ...

Page 149: ...e event to be reported 0 Any Device not listed below 1 General Alarm Device 2 Manual Station Alarm 3 Supervisory Device Non latching 4 Supervisory Device Latching 5 Waterflow Non silenceable 6 Smoke Alarm 7 Non reporting Device 8 Multi level Device NOTE 1 Special AMM PIDs include the following functions Reset Switch Silence Switch Drill Switch Alarm Acknowledge Switch Trouble Acknowledge Switch NO...

Page 150: ...lt 910 RS 232 Supervision Fault 911 Annunciator Fault 912 PM 9 PM 9G Supervision Fault 913 Battery Low 914 Battery Fault 915 AC Fault 916 DC Fault 917 Reserved 918 Battery Charger Fault 919 924 Reserved 925 DACT Account 1 Fault 926 DACT Missing 927 DACT Report Timeout 928 DACT Account 2 Fault 929 DACT Line 1 Fault 930 DACT Line 2 Fault 931 INI Communication Fault 932 INI Node Number Fault Issued i...

Page 151: ...OUT COM B OUT to other devices TB1 5 24 V IN 24 VDC from PM 9 PM 9G TB4 1 TB4 3 or TB4 5 TB1 6 GND GND from PM 9 PM 9G TB4 2 TB4 4 or TB4 6 TB2 1 T1 Tip Line 1 Tip IN from street Non power limited TB2 2 T1 Ring Line 1 Ring IN from street Non power limited TB2 3 P1 Tip Line 1 Tip OUT to phone Non power limited TB2 4 P1 Ring Line 1 Ring OUT to phone Non power limited TB2 5 T2 Tip Line 2 Tip IN from ...

Page 152: ...LED3 STANDBY OFF NORMAL STANDBY MODE ON TRANSMITTING OR IN TROUBLE LED1 LED2 LED3 STANDBY LINE2 STATUS LINE1 STATUS DACT E3 MUST BE THE FIRST DEVICE TO THE TELCO LINES IMPORTANT FROM ILI MB E3 OR ILI95 MB E3 TB3 PIN1 FROM ILI MB E3 OR ILI95 MB E3 TB3 PIN2 RS485 COM A OUT TO NEXT DEVICE RS485 COM B OUT TO NEXT DEVICE FROM ILI MB E3 OR ILI95 MB E3 TB3 PIN6 FROM ILI MB E3 OR ILI95 MB E3 TB3 PIN7 TELC...

Page 153: ... FO The RPT E3 FO communicates to the network by means of fiber optic cable or copper unshielded twisted pair wire 3 11 2 RPT E3 UTP The RPT E3 UTP connects to the network by means of unshielded twisted pair copper wire It is similar to the RPT E3 FO with the exception that connectors U4 U5 U6 and U7 are omitted 3 11 3 Specifications The following list the electrical specifications for the RPT E3 ...

Page 154: ...153 Repeater RPT E3 Connections E3 Series System Connections 3 11 4 Repeater RPT E3 Sub Assembly Figure 3 11 4 1 and Figure 3 11 4 2 illustrate the Repeater RPT E3 sub assembly Figure 3 11 4 1 Repeater RPT E3 Sub Assembly Figure 3 11 4 2 Repeater RPT E3 Sub Assembly ...

Page 155: ...t 1 IN See Note 5 U6 Fiber Port 1 OUT See Note 5 J1 ARCNET Term Short when using the Local Differential ARCNET wiring to Terminal TB3 This is the last device on the local net Note If the first and last devices are SHORT then the device between the two must be OPEN If the ILI E3 ILI95 E3 Series or ANX is the first device and the NGA is the last device then the RPT E3 or J1 would be OPEN J2 GFI Shor...

Page 156: ...s using unshielded twisted pair 18 AWG min 3 000 914 4 m maximum between the following nodes RPT E3 TB1 1 COM1A to INI 7100 TB1 3 INI VG TB1 3 or another RPT E3 TB1 3 RPT E3 TB1 2 COM1B to INI 7100 TB1 4 INI VG TB1 4 or another RPT E3 TB1 4 RPT E3 TB1 3 COM2A to INI 7100 TB1 1 INI VG TB1 1 or another RPT E3 TB1 1 RPT E3 TB1 4 COM2B to INI 7100 TB1 2 INI VG TB1 2 or another RPT E3 TB1 2 NOTE 2 TB2 ...

Page 157: ... Settings for the RPT E3 Port 1 Port 2 Transmit Power J4 J5 J6 J7 J8 J9 OPEN OPEN OPEN OPEN OPEN OPEN 12 5 SHORT OPEN OPEN SHORT OPEN OPEN 25 0 OPEN SHORT OPEN OPEN SHORT OPEN 37 5 SHORT SHORT OPEN SHORT SHORT OPEN 50 0 OPEN OPEN SHORT OPEN OPEN SHORT 67 5 SHORT OPEN SHORT SHORT OPEN SHORT 75 0 OPEN SHORT SHORT OPEN SHORT SHORT 87 5 SHORT SHORT SHORT SHORT SHORT SHORT 100 0 Table 3 11 5 2 Transmit...

Page 158: ...TH GROUND AND ENABLE GROUND DETECTION WHEN REMOTELY MOUNTED NOTE NOT APPLICABLE WHEN USING FIBER OPTIC CONNECTIONS ARCNET LOCAL DIFFERENTIAL TB4 HARD WIRED POWER CONNECTIONS NOT REQUIRED WHEN J10 USED U5 RX2 U7 TX2 U4 RX1 U6 TX1 LEDS D12 ON RECEIVING NETWORK TRANSMISSIONS INTO ARCNET PORT 2 OR U5 OFF OR BLINKING NOT RECEIVING NETWORK TRANSMISSIONS INTO ARCNET PORT 2 OR U5 D11 ON RECEIVING NETWORK ...

Page 159: ...cifications Quantity of the ANU 48 assemblies 1 2 3 4 Maximum resistance of the 24 VDC power 40 20 14 10 circuit ohms to the most distant ANU 48 Table 3 12 1 ANU 48 Resistance Limitations Operating Voltage 24 VDC FWR from PM 9 PM 9G power supply Operating Current 0 011 amp See Note Operating Temperature 32 to 120 F 0 to 49 C Relative Humidity 0 to 93 non condensing at 90 F 32 C Supervised Power li...

Page 160: ...4 10 159 ANU 48 Remote LED Driver Connections E3 Series System Connections 3 12 2 ANU 48 Sub Assembly Figure 3 12 2 1 and Figure 3 12 2 2 illustrate the ANU 48 Remote LED Driver sub assembly Figure 3 12 2 1 ANU 48 Sub Assembly Figure 3 12 2 2 ANU 48 Sub Assembly ...

Page 161: ...EDs 1 to 8 Negative outputs to remote LEDs TB7 1 to 8 LEDs 9 to 17 Negative outputs to remote LEDs TB8 1 to 8 LEDs 18 to 26 Negative outputs to remote LEDs TB9 1 to 8 LEDs 27 to 33 Negative outputs to remote LEDs TB10 1 to 8 LEDs 34 to 42 Negative outputs to remote LEDs TB11 1 to 8 LEDs 43 to 48 Negative outputs to remote LEDs TB12 1 to 8 LED1 48 Positive common output for remote LEDs TB13 1 EXT P...

Page 162: ...7 LED14 LED13 LED15 LED16 LED11 LED9 LED10 LED12 TB1 LED18 LED22 LED24 LED20 LED21 LED23 LED17 LED19 TB8 LED28 LED32 LED30 LED31 LED29 TB9 LED26 LED27 LED25 LED40 LED38 LED36 LED34 LED35 LED39 LED37 LED33 TB10 LED43 LED48 LED46 LED44 LED47 LED45 TB11 LED42 LED41 TB12 TB5 TO ILI E3 OR ILI95 E3 TO TB1 4 TO TB1 3 TO TB3 2 TO TB3 1 TB1 RS485 PORT CONNECTS TO ILI MB E3 ILI95 MB E3 OR INI VG ON 1 2 3 4 ...

Page 163: ... set via the DIP Switch Figure 3 12 5 1 illustrates the ANU 48 address DIP switches and the ANU 48 programming address switch settings For addressing instructions see the ANU 48 Installation Instructions P N 9000 0564 NOTE Set the first address in the program to switch 32 Figure 3 12 5 1 ANU 48 DIP Switches Set this switch 6 UP when connected to the ILI MB E3 or ILI95 MB E3 Set this switch 6 DOWN ...

Page 164: ...motely located via a local RS 485 serial interface The ILI MB E3 or ILI95 MB E3 will support up to six 6 LCD E3 displays See Table 3 13 3 1 for the field wiring connections 3 13 1 Specifications The following list the electrical specifications for the LCD E3 Operating Voltage 24 VDC FWR from PM 9 PM 9G power supply Operating Current 0 024 amp Alarm Current 0 028 amp Operating Temperature 32 to 120...

Page 165: ...11 04 10 E3 Series System Connections LCD E3 Panel Display Connections 3 13 2 LCD E3 Sub Assembly Figure 3 13 2 1 and Figure 3 13 2 2 illustrate the LCD E3 sub assembly Figure 3 13 2 1 LCD E3 Sub Assembly Figure 3 13 2 2 LCD E3 Sub Assembly W1 W2 TB1 J3 J4 J2 J1 ...

Page 166: ... 485A RS 485A output from ILI MB E3 or ILI95 MB E3 TB1 4 RS 485B RS 485B output from ILI MB E3 or ILI95 MB E3 TB1 5 RS 485A RS 485A input from ILI MB E3 or ILI95 MB E3 TB1 6 RS 485B RS 485B input from ILI MB E3 or ILI95 MB E3 TB1 7 GND Connect to earth ground TB1 8 Not used J1 Local RS 485 Alternate RS 485 connection J2 Keypad To keypad J3 Display To display J4 Factory use W1 RS 485 Termination W1...

Page 167: ...T LCD E3 TB1 2 OR LCD 7100 TB1 6 SW1 ADDRESS TO KEY SWITCH LUGS ON DISPLAY RS485 TERMINATION P2 KEYPAD ENABLE DISABLE R20 DISPLAY BACKLIGHT USE R2O TO ADJUST CONTRAST OF DISPLAY SET TO ADDRESSES 1 THRU 6 ADDRESSES 0 ZERO 7 ARE NOT USED DO NOT SET MULTIPLE LCD E3s TO THE SAME ADDRESS FACTORY USE ONLY DO NOT CONNECT FROM LCD E3 DISPLAY KEYPAD 2 1 KEYPAD RS485 PORT CONNECTS TO ANU 48 J1 OR J2 ASM 16 ...

Page 168: ...ences the local audible trouble sounder Operating LEDs provided are 3 14 1 Mounting The LCD 7100 is flush or surface mounted on a standard four gang electrical box 3 14 2 Specifications The following are the LCD 7100 specifications 3 14 3 LCD 7100 Remote Display Sub Assembly Figure 3 14 3 1 illustrates the LCD 7100 remote display sub assembly Figure 3 14 3 1 LCD 7100 Remote Display Sub Assembly Al...

Page 169: ... 1 COM A Connect to BSM TB5 2 or ILI MB E3 or ILI95 MB E3 TB3 1 18 AWG min twisted pair TB1 2 COM B Connect to BSM TB5 1 or ILI MB E3 or ILI95 MB E3 TB3 2 18 AWG min twisted pair TB1 3 Earth GND Connect to earth ground TB1 4 Not used TB1 5 24 VDC Connect to BSM TB4 2 or ILI MB E3 or ILI95 MB E3 TB3 6 16 AWG min twisted pair TB1 6 24V Common Connect to BSM TB4 3 or ILI MB E3 or ILI95 MB E3 TB3 7 16...

Page 170: ...rrent See Note 6 B Enter number of standby hours required See Note 1 C Multiply Line A times hours in Line B enter D Total alarm current from above E Enter alarm sounding period in hours F Multiply Line D times Line E enter G Total of Lines C F enter H Multiply Line G by 1 2 enter Total ampere hours required See Note 2 NOTES NOTE 1 24 hrs for NFPA 72 protected premises or Central Station signaling...

Page 171: ...itor input modules and Control output modules For a list of approved modules refer to the Compatibility Addendum to Gamewell FCI Manuals P N 9000 0427 3 16 4 Monitor Modules Dry contact devices and two wire smoke detectors can be monitored by these modules which act as the interface between the manual station waterflow switch etc and the control panel For a list of approved modules refer to the Co...

Page 172: ...E3 Series Installation Operation Manual P N 9000 0574 I 11 04 10 171 Analog Sensors E3 Series System Connections Notes ...

Page 173: ...3 GHI 4 JKL 5 PRS 7 TUV 8 WXY 9 0 _ Designation Description Comments AC Power On green Lights to indicate the presence of 120 VAC input Alarm red Lights when system is in alarm flashes until alarm is acknowledged Supervisory yellow Lights when supervisory condition exists flashes until trouble acknowledge is performed System Trouble yellow Lights to indicate trouble condition flashes until trouble...

Page 174: ...upervisory events are indicated by a continuous tone from the system piezo sounder and the illumination of the supervisory LED Trouble Trouble conditions are indicated by a continuous tone from the system piezo sounder and the illumination of the yellow trouble LED Acknowledged Acknowledgement of any of these conditions will silence the system sounder leaving the appropriate LEDs illuminated Troub...

Page 175: ...ndition exists in the system Lamp Test Reset Press momentarily and all LEDs including all elements in the display will light momentarily Press and hold to reset the system Menu Back Used to access certain system functions e g Walk Test The display will prompt the operator as to which function applies Menu is pressed to initially put the E3 Series into Menu Mode The Back function will step the oper...

Page 176: ...E3 Series Installation Operation Manual P N 9000 0574 I 11 04 10 175 Switches LCD E3 Programming Operation Instructions Notes ...

Page 177: ...all as indicated below Program Feature Permitted in UL 864 Possible Settings Settings Permitted in UL 864 Trouble Reminder Yes Enabled or Disabled Enabled Menu Selection Description CONFIG Pressing CONFIG on the main menu automatically opens the Autoconfig Menu where automatic configuration of the system is accomplished There are two modes Clear and Reconfigure Can be used to initialize a complete...

Page 178: ...Upload 2 Auto configuration Options 1 or 2 on the Autoconfig Menu 3 Network node map change 4 Manual update via the CS terminal command Menu Selection Description Output ON OFF Forces the toggling on or off of a specified output These outputs can include NAC 1 NAC 2 Municipal Circuit if present and any Addressable Control Point Enable Disable Allows the user to take any addressable device on eithe...

Page 179: ...178 E3 Series Installation Operation Manual P N 9000 0574 I 11 04 10 Programming INFO Menu Selection Notes ...

Page 180: ... Number 1 opens the Time setup Number 2 opens the Date setup 5 To enter the data use the keypad and press the OK button when each section is completed The OK button acts as an Enter key 6 Press the Reset Lamptest button and ensure that the Time and Date remain correct 6 3 Automatic Configuration 1 Press the Menu Back button on the keypad and enter the Level 4 password YYYYYY 2 To display the Main ...

Page 181: ... requirements of NFPA 72 National Fire Alarm Code and or applicable state and local codes 7 2 Maintenance We recommend the replacement of the system standby batteries after three years of service unless otherwise indicated by the battery manufacturer There are no user serviceable components in this equipment Sub assemblies should be returned to the factory for servicing ...

Page 182: ...n these circuits power limited vs non power limited is maintained at the field wiring terminals In order to fully comply with the intent of these requirements however the minimum 1 4 inch separation must also be maintained between the field wiring conductors of power limited circuits and non power limited circuits This may be accomplished by routing the field wiring as shown in Figure 8 2 1 Unless...

Page 183: ... modules Twisted unshielded pair with a characteristic impedance of 120 Ohms 18 AWG 0 78 mm2 minimum 3 000 ft maximum 16 AWG 1 30 mm2 EIA 232 power limited Connects to Printers CRT E3 or PC Twisted unshielded pair 18 AWG 0 78 mm2 minimum 50 15 24 without modem 16 AWG 1 30 mm2 NAC Notification Appliance Circuit E3 power limited 12 18 AWG 3 1 to 0 78 mm2 At alarm current level no more than a 1 2 V d...

Page 184: ...power limited wiring of the E3 Series control panel Figure 8 2 1 E3 Series Power Limited and Non Power Limited Wiring E3 Series Panels Non Power Limited circuit wiring Non Power Limited circuit wiring Non Power Limited circuit wiring Non Power Limited circuit wiring NOTE All other circuits are Power Limited Dotted line denotes Non Power Limited wiring PM 9 PM 9G NOTE Route all Non Power Limited wi...

Page 185: ...184 E3 Series Installation Operation Manual P N 9000 0574 I 11 04 10 Notes ...

Page 186: ...Door to Backbox 77 Cabinet C INCC E3 8 Bay Inner Door to Backbox 79 Cabinet D 81 Cabinet D 13 Bay Inner Door to Backbox 90 Cabinet D 14 Bay Inner Door to Backbox 92 Cabinet D E3 INCC D Plate 87 Cabinet D E3 INX D Plate 85 FPT GATE 3 Extender Plate 75 FPT GATE 3 Extender Plate to Backbox 76 D DACT E3 13 Event Reporting Codes 147 Digital 144 F FPT GATE 3 Extender Plate 75 G Ground Fault Supervision ...

Page 187: ...9 PM 9 169 PM 9G 169 RPT E3 169 U uIP Software License Disclaimer 116 W Wiring Connections ANU 48 160 ANX MR FO 125 ANX MR UTP 121 ANX SR 118 ASM 16 139 DACT E3 150 ILI95 MB E3 95 103 ILI95 S E3 112 113 ILI MB E3 95 99 ILI S E3 106 108 LCD 7100 168 LCD E3 165 PM 9 132 PM 9G 135 Repeater E3 154 Wiring Diagrams ANU 48 161 ANX MR FO 127 ANX MR UTP 123 ANX SR 119 ASM 16 142 DACT E3 151 ILI95 MB E3 105...

Page 188: ...WITH RESPECT TO THE PRODUCTS TRADEMARKS PROGRAMS AND SERVICES RENDERED BY MANUFACTURER INCLUDING WITHOUT LIMITATION INFRINGEMENT TITLE MERCHANTABILITY OR FITNESS FOR ANY PARTICULAR PURPOSE MANUFACTURER SHALL NOT BE LIABLE FOR ANY PERSONAL INJURY OR DEATH WHICH MAY ARISE IN THE COURSE OF OR AS A RESULT OF PERSONAL COMMERCIAL OR INDUSTRIAL USES OF ITS PRODUCTS This document constitutes the only warr...

Page 189: ...Gamewell FCI 12 Clintonville Road Northford CT 06472 1610 USA 203 484 7161 fax 203 484 7118 www gamewell fci com ...

Page 190: ...CFI Security Inc 1845 Northwestern Suite B El Paso Texas 79912 Ph 915 778 6061 Fax 915 778 7046 ...

Reviews: