108
E3 Series Installation/Operation Manual
—
P/N 9000-0574:I 11/04/10
E3 Series System Connections
Intelligent Loop Interface - Slave Board (ILI-S-E3) Connections
3.4.3 Intelligent Loop Interface - Slave Board (ILI-S-E3) Wiring
Connections
Field wiring connections for the ILI-S-E3 is shown in Table 3.4.3.1.
Designation
Description
Comments
TB1-1, TB1-3
+24 V IN
+24 VDC Input
TB1-2, TB1-4
GND
Common negative from PM-9/PM-9G TB4-2
TB4-1
SLC 2 A-
SLC 2 Style 6 / 7 Return (See Note 1)
TB4-2
SLC 2 A+
SLC 2 Style 6 / 7 Return (See Note 1)
TB4-3
SLC 2 B-
SLC 2 Style 4 / 6 / 7 Out (See Note 1)
TB4-4
SLC 2 B+
SLC 2 Style 4 / 6 / 7 Out (See Note 1)
TB4-5
SLC 1 A-
SLC 1 Style 6 / 7 Return (See Note 1)
TB4-6
SLC 1 A+
SLC 1 Style 6 / 7 Return (See Note 1)
TB4-7
SLC 1 B-
SLC 1 Style 4 / 6 / 7 Out (See Note 1)
TB4-8
SLC 1 B+
SLC 1 Style 4 / 6 / 7 Out (See Note 1)
TB6-1
RS232 GND
To red lead on download cable P/N 75267
RS-232 Download
or Printer Port
TB6-2
RS232 TxD
To black lead on download cable P/N 75267
TB6-3
Supervision
Optional Printer Supervision
TB6-4
RS232 RxD
To green lead on download cable P/N 75267
W1, W2, W3
Factory Jumpers
Factory Use Only (Default OUT)
W4
Local ARCNET
OPEN = Normal Operation
SHORT = If the ILI-S-E3 or ILI-S95-E3 is located at the end of the
ARCNET bus.
SW2-1
Switch
1 ON = SLC 1 DISABLED
(OFF = SLC 1 ENABLED)
SW2-2
Switch
2 ON = SLC 2 DISABLED
(OFF = SLC 2 ENABLED)
SW2-3
Switch
Unused
SW2-4
Switch
4 ON = BUZZER DISABLED
(OFF = BUZZER ENABLED)
SW2-5
Switch
5 ON = 115.2 K BAUD
(OFF = defined by CAMWorks
™)
J2
Local ARCNET
Connects to J5 of the next ILI-E3, ILI95-E3 Series or ANX sub-assembly
J5
Local ARCNET
Connects to J2 from the previous ILI-E3, ILI95-E3 Series or ANX sub-
assembly
NOTE 1:For Style 4, use terminals B+ and B- only. For Style 6, use terminals B+ and B- and connect return wiring
to A+ and A-. For Style 7, wire as for Style 6 and use Isolator Modules and or Isolator Detectors per
recommendations as required.
Table 3.4.3.1 ILI-S-E3 Field Wiring Connections
NOTE: For additional information on the wiring requirements, refer to the ILI-S-E3 Installation
Instructions (P/N 9000-0569).