118
E3 Series Installation/Operation Manual
—
P/N 9000-0574:I 11/04/10
E3 Series System Connections
Addressable Node Expander (ANX) Connections
3.7.6.1 ANX-SR Wiring Connections
Table 3.7.6.1.1 lists the field wiring connections for the ANX-SR sub-assembly.
Designation
Description
Comments
TB1-1
+24V
+24 VDC Input from the PM-9/PM-9G TB4-1
TB1-2
GND
Common negative from the PM-9/PM-9G TB4-2
TB1-3
+24V
TB1-4
GND
TB2-1
COM A IN
Local Differential ARCNET
TB2-2
COM B IN
Local Differential ARCNET
TB2-3
COM A OUT
Local Differential ARCNET
TB2-4
COM B OUT
Local Differential ARCNET
TB3-1
RS-232 GND
To red lead on download cable P/N 75267
RS-232 Download
or Printer Port
TB3-2
RS-232 TxD
To black lead on download cable P/N 75267
TB3-3
RS-232 SUPV
Optional Printer Supervision
TB3-4
RS-232 RxD
To green lead on download cable P/N 75267
W1, W2, W3 Factory Jumpers
Factory Use Only or Right (Default OUT)
W4
ARCNET Termination
OPEN = Normal Operation
SHORT = If the ANX is located at the end of the ARCNET bus.
SW1-1
Serial Communication
ON = RS-232 115.2 kbits/sec
OFF = defined by CAMWorks
™
SW1-2 thru
SW1-8
ARCNET Address
(See Section 4)
J1
ETHERNET
To FocalPoint or TCP/IP Network Port
Green LED-Communication link established
(blinks with message traffic)
Yellow LED-100 Mbps speed (Off - 10 Mbps)
J2
Local ARCNET
Connects to J5 of the next ILI-E3, ILI95-E3 Series or ANX
J4
ARCNET Repeater
Connector
Connects to J10 of the RPT-E3
J5
Local ARCNET
Connects to J2 from the previous ILI-E3, ILI95-E3 Series or
ANX
LED1
REC
Network Reconfiguration
LED2
MRC
Network Reconfiguration originating from this node
LED3
DUP
Node
’s Network Address is duplicated at another node
LED4
TX
Node is transmitting data to the network
LED5
RX
Node is receiving data from the network
LED6
RST
Node is resetting
LED7
DG
General Network Fault
Table 3.7.6.1.1 ANX-SR Wiring Connections