E3 Series Installation/Operation Manual
—
P/N 9000-0574:I 11/04/10
19
Section 2: Installation
2.1 General
The E3 Series
®
System is a modular system and is shipped unassembled. The backbox, doors, and
sub-assemblies are individually packaged and can be easily assembled.
2.2 Installation Requirements
All components of the E3 Series
®
System should be located per the following requirements:
•
Installations are to be indoors only, in dry lo
cations, protected from rain, water, and rapid
changes in temperature that could cause condensation. Equipment must be securely mounted
on rigid, permanent walls.
•
Operating temperature shall not exceed the
range of 32
° to 120°
F (0 to 49
° C).
•
Operating humidity not to exceed 93%
non-condensing at 90
° F (32° C).
•
There should be adequate space around the installation to allow easy access for operation and
servicing.
•
All sub-assemblies and components are to be
located in compliance with local and national
codes.
•
All installation field wiring shall be in compliance with local and national codes.
2.3 Unpacking and Inspecting Components
Remove all sub-assemblies and accessories from their shipping cartons to access the enclosure.
Remove and inspect the enclosure for shipping damage. Inspect all electronic sub-assemblies for
damage without removing them from their anti-static protective bags. If any pieces are found
damaged, notify the shipping carrier immediately. Report missing components to the Gamewell-
FCI Customer Service.
2.4 Mounting Sub-assemblies
1.
The ILI-MB-E3, ILI95-MB-E3 and/or ANX consist of a main operating board with pluggable
terminal strips. Install this sub-assembly immediately unless any optional units are to be used
in the system. Refer to the Installation Instructions P/N 9000-0579, P/N 9001-0017 and 9001-
0064. Before installing the ILI-MB-E3, ILI95-MB-E3 and/or ANX into the system backbox,
refer to the Installation Instructions shipped with each sub-assembly for the proper procedures:
2.
Install the door after the sub-assemblies are in place. Note that the door can only be installed
(or removed) when it is opened at least 90
° from the backbox.