Section 6: Power Up Procedure
6.1 General
1.
Ensure that all cables and optional modules (if any) are installed and secured per the
Installation Instructions. DO NOT install any field wiring at this time. Connect the End-of-
Line devices to the notification appliance and municipal (if installed) circuits.
2.
Power the panel with AC first. The system will initialize and indicate a
“Battery Missing”
condition.
3.
Connect the batteries, taking care to observe polarity.
4.
The system should be in normal condition. You may proceed with the installation of field
wiring. Check all wiring prior to connection to the control panel. Do not use this panel as a
circuit tester.
6.2 To Set the System Time
1.
Press the <MENU/Back> button on the keypad and enter the Level 1 password, XXXXXX.
2.
To display the Main Menu, press the <OK> button.
3.
To display the Clock Menu, press the Number 4.
4.
The following numbers indicate the number that opens the Time or Date setup:
– Number 1 opens the Time setup.
– Number 2 opens the Date setup.
5.
To enter the data, use the keypad and press the <OK> button when each section is completed.
The <OK> button acts as an <Enter> key.
6.
Press the <Reset/Lamptest> button and ensure that the Time and Date remain correct.
6.3 Automatic Configuration
1.
Press the <Menu/Back> button on the keypad and enter the Level 4 password, YYYYYY.
2.
To display the Main Menu, press the <OK> button.
3.
To display the Configuration Menu, press the Number 1.
4.
Since this is the first time the system is configured, press the Number 1 to initiate the Clear,
then Configure process. This process will place all of the system settings to the factory default
and then read all of the devices correctly connected to the two (2) SLCs. After this process is
complete, the system may be given an initial test to ensure all of the devices have been
installed into the system memory.
!
WARNING: POWER UP REQUIREMENTS:
PRIOR TO THE APPLICATION OF POWER TO THE SYSTEM, ALL CIRCUITS MUST BE CLEAR
OF SHORTS, GROUNDS AND STRAY VOLTAGES. FAILURE TO DO SO COULD CAUSE
IRREVERSIBLE DAMAGE TO THE EQUIPMENT.
NOTE: Auto-configuration is only possible for ILI-MB-E3 and ILI-S-E3 nodes that use the Velociti
®
protocol.